Wiring for Dual Inverter Configurations
Wiring for Dual Inverter Configurations
Series stacked Sine Wave Plus inverters with ACCBs installed are wired essentially the same as single inverters, with the following differences.
Installing the
The
Remove the hole plug for the slot to be used by the cable only. Do not remove any other hole plugs. Ensure that the all the other hole plugs are still in place as shown in Figure
Grommet
Hole Plug
Figure
AC Neutral Wiring for Dual Configurations
All of the AC wiring for dual Sine Wave Plus inverters remains the same, except for two changes in the neutral wiring:
1.All NEUTRAL IN wiring goes only to the neutral terminals in the L1 ACCB (attached to the L1 Sine Wave Plus inverter).
2.A neutral bond between the inverters is created by connecting an owner supplied #6 AWG THHN neutral wire (white) from the ACCB neutral terminal attached to the L1 Sine Wave Plus inverter to the ACCB neutral terminal attached to the L2 Sine Wave Plus inverter.