Important Safety Instructions

WARNING

This chapter contains important safety and operating instructions for Sine Wave

Plus AC Conduit Boxes (ACCB). Read and keep this Sine Wave Plus AC

Conduit Box (ACCB) Installation Guide for future reference.

1.Before installing the ACCB, read all instructions and cautionary markings on the ACCB and all appropriate sections of this guide.

2.Do not expose the ACCB to rain, snow, or spray. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the ACCB in a zero-clearance compartment. Overheating may result. Minimum clearance for ventilation around the unit must be six inches at the end and three inches top and bottom.

3.Use only attachments recommended or sold by the manufacturer. Doing otherwise may result in a risk of fire, electric shock, or injury to persons.

4.The ACCB is designed to be permanently connected to your inverter. It can be mounted on a vertical surface (or wall) or on a shelf. Xantrex recommends that all wiring be done by a certified technician or electrician to ensure adherence to the local and national electrical codes applicable in your application.

5.To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not operate the ACCB, or inverter, with damaged or substandard wiring.

6.Do not install the ACCB if it has received a sharp blow, been dropped, or otherwise damaged in any way. If the unit is damaged, see the Warranty section at the end of this guide.

7.To reduce the risk of electrical shock, disconnect all power to the ACCB and the Sine Wave Plus Inverter/Charger before attempting any maintenance or cleaning or working on the ACCB.

8.The ACCB is provided with an equipment-grounding conductor which must be connected to the inverter/system equipment ground.

975-0046-01-01

v