Wiring for Off-Grid Applications Using an AC Distribution Panel and an External Generator Disconnect
To make the hot connections:
1.Connect the factory-installed hot (black) wire from the Inverter Input Breaker in the ACCB to the AC2 GEN terminal in the inverter.
2.Connect the factory-installed hot wire (black) from the Inverter Output Breaker in the ACCB to the INV OUT terminal in the inverter.
3.Connect a HOT (Black) wire AC OUT in the ACCB to the HOT IN in the AC Distribution Panel.
4.Connect a hot (black) wire from the generator disconnect to the AC IN terminal in the ACCB.
4
3
1 2
Figure 1-17Hot Connections for an Off-grid Application with an AC Distribution Panel and an External Generator Disconnect