Error Code Table

Error

Description of Fault

Possible Cause

Solution

Code

 

 

 

 

 

 

 

002

Battery Voltage is too low

1. Discharged battery.

1. Charge battery.

 

 

2. Old or faulty battery.

2. Battery may not be hold-

 

 

 

ing charge properly. If

 

 

 

flooded, check electro-

 

 

 

lyte level and fill with dis-

 

 

 

tilled water if necessary.

 

 

 

Equalization may help if

 

 

 

recommended by the bat-

 

 

 

tery manufacturer. Battery

 

 

 

may be faulty and require

 

 

 

replacement.

 

 

3. Battery cables to the Pros-

3. Check cable size and

 

 

ine inverter/charger are too

length against recom-

 

 

small, too long, or there is a

mendations in this man-

 

 

loose connection.

ual. Check and tighten all

 

 

 

connections. Large loads

 

 

 

may draw the voltage

 

 

 

down very quickly on a

 

 

 

small battery or in an

 

 

 

installation with cables

 

 

 

that are too small or too

 

 

 

long.

 

 

 

 

003

Battery Voltage is too high.

1. External charger or alterna-

1. Correct or disconnect the

 

 

tor has output voltage

external charging source.

 

 

greater than 16 V.

 

 

 

2. A 12V Prosine inverter/

2. Make sure the battery

 

 

charger could be connected

bank is nominal 12V for a

 

 

to a 24V battery (two batter-

12v Prosine.

 

 

ies in series).

 

 

 

 

 

006,065

Microprocessor communi-

Remote display cable is

Check display cable con-

 

cation error.

pinched or has loose connec-

nections and attempt

 

 

tion.

restart. If the problem per-

 

 

 

sists, try a replacement

 

 

 

cable.

 

 

 

If the problem persists, call

 

 

 

Xantrex.

 

 

 

 

90

Prosine 2.5/3.0 Installation & Operation Guide