Section 4: Inverter/Charger Installation

ProsinePROsine

Output Power De-rating at Elevated Temperature

Output power (Watts)

4000

 

 

 

 

3000

 

 

 

PS 2.5

(Watt)

 

 

 

2000

 

 

 

PS 3.0

 

 

 

 

1000

 

 

 

 

0

 

 

 

 

0

20

40

60

80

 

Ambient temperature (deg. C)

 

WARNING Explosion hazard: This equipment contains components which tend to produce arcs or sparks. To prevent fire or explosion do not install the Prosine inverter/charger in compartments containing batteries or flammable materials or in locations which require ignition protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks, or joints, fittings, or other connection between components of the fuel system.

Safe—Do not install the inverter/charger in the same compartment as vented (non-sealed) batteries or in any compartment capable of storing flammable liquids such as gasoline. The Prosine inverter/charger is not ignition protected. Do not install it an engine or gas tank compartment or any other location where ignition protected equipment is required. These gases are very corrosive and prolonged exposure will damage the Prosine inverter/charger.

Close to batteries and the AC distribution box—Avoid excessive cable lengths, which reduce input and output power due to wire resistance. Use the recommended wire lengths and sizes.

Protected from battery acid—Never allow battery acid to drip on the Prosine inverter/charger or its wiring when reading specific gravity or filling the battery.

Prosine Installation & Operation Guide

43