Section 3: Configuration

SWITCH BANK 2 (SW2)

Audible Alarm

Switch 1

 

 

 

 

UP

Audible signals enabled

 

DOWN

Audible signals disabled

 

Switch 2 Not Used

 

 

Rating(Amps)CurrentDraw

AC service rating

 

 

 

 

 

Switch 3

Switch

BreakerMaxAC

 

 

 

 

 

4

 

 

 

UP

UP

10 A

8 A

 

DOWN

UP

15 A

12A

 

UP

DOWN

20 A

16A

 

DOWN

DOWN

30 A

24A

Maximum DC

Charging Amps

PS 2.5

 

PS 3.0

 

12V

24V

12V

24V

55

30

55

30

90

45

90

45

100

55

100

60

100

55

120

60

Battery Size

Switch 5, 6, 7, 8

 

 

 

Max DC charging current (amps)

 

 

 

 

Battery

Prosine 2.5

Prosine 3.0

#5

#6

#7

#8

Capacity

12V

24V

12V

24V

 

 

 

 

 

 

 

 

 

UP

UP

UP

UP

50 Ah

11A

11A

11A

11A

DOWN

UP

UP

UP

75 Ah

25A

25A

25A

25A

 

 

 

 

 

 

 

 

 

UP

DOWN

UP

UP

100 Ah

33A

33A

33A

33A

DOWN

DOWN

UP

UP

150 Ah

50A

50A

50A

50A

 

 

 

 

 

 

 

 

 

UP

UP

DOWN

UP

200Ah

67A

50A

67A

60A

DOWN

UP

DOWN

UP

300 Ah

100A

50A

100A

60A

 

 

 

 

 

 

 

 

 

UP

DOWN

DOWN

UP

400 Ah

100A

50A

120A

60A

DOWN

DOWN

DOWN

UP

500 Ah

100A

50A

120A

60A

 

 

 

 

 

 

 

 

 

UP

UP

UP

DOWN

600 Ah

100A

50A

120A

60A

DOWN

UP

UP

DOWN

700 Ah

100A

50A

120A

60A

 

 

 

 

 

 

 

 

 

UP

DOWN

UP

DOWN

800 Ah

100A

50A

120A

60A

DOWN

DOWN

UP

DOWN

1000 Ah

100A

50A

120A

60A

 

 

 

 

 

 

 

 

 

UP

UP

DOWN

DOWN

1200 Ah

100A

50A

120A

60A

DOWN

UP

DOWN

DOWN

1400 Ah

100A

50A

120A

60A

 

 

 

 

 

 

 

 

 

UP

DOWN

DOWN

DOWN

1700 Ah

100A

50A

120A

60A

DOWN

DOWN

DOWN

DOWN

2000 Ah

100A

50A

120A

60A

 

 

 

 

or greater

 

 

 

 

Prosine 2.5/3.0 Installation & Operation Guide

27