Section 3: Configuration
Inverter Configuration
All the items on the Inverter menu are configuration parameters. The first two items are Load Sense parameters. The remaining items are high- and
Load Sense Parameters. You can define a minimum load at which the inverter will provide AC power. Any load that draws less than the minimum current, adjustable from 1 to 1401 watts, will not activate the inverter. Loads that draw more than the minimum current will activate the inverter from Standby mode to Invert mode. A minimum setting of zero will disable Load Sense altogether. Power consumption by the inverter when it is not on Standby is about 60 watts. When Load Sense is enabled and the inverter is in Standby mode, power consumption is about three watts, conserving your batteries.
LOAD SENSE TURN- ON POWER:00 W
ENTER
LOAD SENSE TURN- ON POWER:1401 W
ENTER
When Load Sense mode is active
ENTER
ENTER
High and Low Voltage Alarms & Cutoffs. The Prosine inverter/charger features integrated circuitry to protect excessive charging and discharging of your batteries, and an audible warning alarm to alert you to when high- and
DC INPUT RANGE: LO ALARM:10.0V
DC INPUT RANGE: HI ALARM:14.0V
DC INPUT RANGE: LO CUTOFF:10.0V
DC INPUT RANGE: HI CUTOFF:14.0V
DC INPUT RANGE: LO ALARM:12.0V
DC INPUT RANGE: HI ALARM:16.0V
DC INPUT RANGE: LO CUTOFF:12.0V
DC INPUT RANGE: HI CUTOFF:16.0V
ESCAPE
ESCAPE
ESCAPE
ESCAPE
Prosine 2.5/3.0 Installation & Operation Guide | 33 |