AC Bypass Selector
optimize the charging profile. The remote output jacks enable you to remotely mount the standard and/or the ACS control panels, described later in this section of this manual.
AC Bypass Selector
The small slide switch located between the Batt Temp jack and the Remote Output jacks is the AC Bypass selector switch. The default position of this switch is On. In the On position, the inverter/ charger operates as programmed. When the switch is in the Bypass position, the inverter/charger is Off, and AC current bypasses the inverter/charger to supply
the AC loads directly.
DC Terminals & Covers
The DC cabling connectors are located on the bottom of the Prosine inverter/charger. Each connector is an M10 x 1.5 stainless steel stud and nut. The studs are about
approximately
Adjacent to the DC terminals is the chassis ground lug. The chassis ground lug provides a ground path for DC fault current from the inverter/charger chassis to ensure your battery fuse opens in the event of a fault.
AC Terminals & Covers
On the bottom of the Prosine inverter/charger, alongside the DC connectors, a
provided for the AC
AC
Adjacent to the AC terminal block is a black bracket with two
6 | Prosine 2.5/3.0 Installation & Operation Guide |