Xantrex Technology XHR, XFR, XFR3 Accumulated Status, Status, and Fault Registers, Operation

Models: XHR, XFR, XFR3

1 62
Download 62 pages 62.83 Kb
Page 52
Image 52
Accumulated Status, Status, and Fault Registers

Operation

Accumulated Status, Status, and Fault Registers

Accumulated Status, Status, and Fault Registers

The GPIB option card uses three separate registers which are always active. They are the accumulated status, status, and fault registers. You can use the status commands shown in Table 3.8, “Status Commands” to activate the registers. The bit register has twelve conditions, each assigned a bit weight. When querying a register, the controller returns a response which is the sum of the weights of all relevant conditions.

Example:

ASTS?

Query the Accumulated Status register.

 

ASTS <771>

Controller response.

 

 

771 = 512 + 256 + 2 + 1 = PON + REM + CC + CV

 

 

Table 3.10 Accumulated Status, Status, and Fault Registers

 

Condition

 

Mnemonic

Bit Position

Bit Weight

 

 

 

 

 

Constant voltage operation

 

CV

0

1

 

 

 

 

 

Constant current operation

 

CC

1

2

 

 

 

 

 

Not used

 

2

4

 

 

 

 

 

Overvoltage protection tripped

 

OV

3

8

 

 

 

 

Over temperature protection tripped

OT

4

16

 

 

 

 

Supply external shutdown active (J7-1)

SD

5

32

 

 

 

 

 

Foldback mode operation

 

FOLD

6

64

 

 

 

 

 

Remote programming error

 

ERR

7

128

 

 

 

 

Power ON (accumulated status, status

PON

8

256

registers only)

 

 

 

 

Remote mode (accumulated status, status

REM

9

512

registers only)

 

 

 

 

AC fail condition

 

ACF

10

1024

 

 

 

 

 

Output fail condition

 

OPF

11

2048

 

 

 

 

 

Sense protection tripped

 

SNSP

12

4096

Notes:

1.All mnemonics can be masked or unmasked.

2.The error (ERR) bit is reset in the accumulated status, status, and serial poll registers with an error query (ERR?).

3.The accumulated status register is cleared with an accumulated status query (ASTS?).

4.A fault is cleared with a fault query (FAULT?).

50

Operating Manual for GPIB for XHR/XFR Series Power Supply

Page 52
Image 52
Xantrex Technology XHR, XFR, XFR3 Accumulated Status, Status, and Fault Registers, Operation, Example, Condition, Mnemonic