C-2 975-0200-01-01

Specifications
Electrical Specifications for XTR 850 Watt

Table C-1

XTR 850 Watt Electrical Specifications for 6 V to 600 V Models

Models 6-110 8-100 12-70 20-42 33-25 40-21 60-14 80-10.5 100-8.5 150-5.6 300-2.8 600-1.4
Output Ratings:
Output Voltage1
Output Current2
Output Power3
6 V
110 A
670 W
8 V
100 A
810 W
12 V
70 A
850 W
20 V
42 A
850 W
33 V
25 A
835 W
40 V
21 A
850 W
60 V
14 A
850 W
80 V
10.5 A
850 W
100 V
8.5 A
860 W
150 V
5.6 A
850 W
300 V
2.8 A
850 W
600 V
1.4 A
850 W
Line Regulation:
Voltage4 (0.005% of rated
output voltage +2 mV)
Current5 (0.01% of rated
output current +2 mA)
2.3 mV
13 mA
2.4 mV
12 mA
2.6 mV
9 mA
3.0 mV
6.2 mA
3.7 mV
4.5 mA
4 mV
4.1 mA
5 mV
3.4 mA
6 mV
3.1 mA
7 mV
2.9 mA
9.5 mV
2.6 mA
17 mV
2.3 mA
32 mV
2.1 mA
Load Regulation
Voltage6 (0.005% of rated
output voltage + 2 mV)
Current7 (0.02% of rated
output current +5 mA
2.3 mV
27 mA
2.4 mV
25 mA
2.6 mV
19 mA
3.0 mV
13.4 mA
3.7 mV
10 mA
4 mV
9.2 mA
5 mV
7.8 mA
6 mV
7.1 mA
7 mV
6.7 mA
9.5 mV
6.1 mA
17 mV
5.6 mA
32 mV
5.3 mA
Output Noise (rms, 300 kHz):
Voltage
Current88 mV
200 mA 8 mV
180 mA 8 mV
120 mA 8 mV
75 mA 8 mV
60 mA 8 mV
45 mA 8 mV
35 mA 8 mV
25 mA 8 mV
20 mA 10 mV
16 mA 25 mV
10 mA 50 mV
6 mA
Output Ripple (p-p, 20 MHz):
Voltage 50 mV 50 mV 50 mV 50 mV 50 mV 50 mV 50 mV 80 mV 80 mV 100 mV 150 mV 250 mV
Maximum Recommended Remote
Sense Line Drop Compensation per
Line9
1 V 1 V 1 V 1.5 V 2 V 2 V 3 V 5 V 5 V 5 V 5 V 5 V
Up-prog. Response Time,
0~Vmax10 60 ms 60 ms 60 ms 60 ms 60 ms 60 ms 60 ms 100 ms 100 ms 100 ms 150 ms 250 ms
Down-prog. Response Time: Full
Load 50 ms 50 ms 50 ms 50 ms 50 ms 50 ms 50 ms 80 ms 100 ms 150 ms 150 ms 250 ms
Down-prog. Response Time: No
Load 300 ms 400 ms 500 ms 600 ms 700 ms 800 ms 900 ms 1000 ms 1200 ms 1800 ms 2200 ms 3500 ms
Over-Voltage Trip Point 0.5–7.5 V 0.5–10 V 1–15 V 1–24 V 2–39 V 2–44 V 3–66 V 3–95 V 3–125 V 3–180 V 5–330 V 5–660 V