Local Operation
3-36 975-0200-01-01
To reset the power supply:
1. Turn the front panel power switch to the Off position.
2. Allow the unit to power down.
3. When the fans are off and the front panel displays are not illuminated,
turn the power switch to the On position.
4. Press and hold the OUTPUT ON/OFF and AUX ON/OFF buttons.
The front panel should display P5U S rS.
5. When the display reads P5u Clr, release the OUTPUT ON/OFF and
AUX ON/OFF buttons. After 1 second the model number will appear
on the display for 1 second.
The power supply has been reset.
Foldback delay 0.5 s
Analog programming Off
Analog programming range Max
| Current Share Mode | MASTer | Off
Alarm Output Latches 0 × 87 (or all latches enabled)
Alarms Mask 0 × FF (all enabled)
Interlock Disabled
Voltage Analog Programming Off
Voltage APG Scale 10 V
Current Analog Programming Off
Current APG Scale 10 V
Table 3-9
Power Supply Default Settings
Parameter Setting