FORM 201.18-EG1

LCWT

(°C)

AIR TEMPERATURE – CONDENSER (°C)

25

 

 

30

 

 

35

 

 

40

 

 

45

 

 

50

 

kWo

kWE

COP

kWo

kWE

COP

kWo

kWE

COP

kWo

kWE

COP

kWo

kWE

COP

kWo

kWE

COP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

YCAS0440EC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

1509.5

360.3

3.8

1454.9

413.0

3.3

1411.4

473.9

2.8

1375.9

543.0

2.4

1306.7

593.4

2.1

1017.9

516.8

1.9

6.0

1553.6

363.9

3.9

1496.7

417.0

3.3

1450.9

478.5

2.8

1413.8

548.6

2.4

1334.7

594.7

2.1

1023.9

510.3

1.9

7.0

1598.6

367.3

4.0

1539.3

420.9

3.4

1491.7

483.2

2.9

1452.6

554.2

2.5

1358.8

593.4

2.2

1031.7

504.5

1.9

8.0

1644.5

370.7

4.1

1582.7

424.7

3.5

1532.6

487.7

3.0

1492.2

559.8

2.5

1380.3

590.3

2.2

1039.2

498.7

2.0

9.0

1691.3

374.0

4.2

1627.3

428.6

3.5

1574.8

492.3

3.0

1532.3

565.4

2.6

1398.2

585.5

2.3

1045.9

492.6

2.0

10.0

1738.9

377.3

4.2

1672.2

432.4

3.6

1617.8

496.9

3.1

1569.0

568.4

2.6

1418.2

581.5

2.3

1053.8

486.9

2.0

11.0

1787.3

380.6

4.3

1718.2

436.2

3.7

1661.7

501.6

3.1

1605.3

570.7

2.7

1438.3

577.4

2.4

1061.6

481.3

2.1

12.0

1836.6

383.9

4.4

1765.1

440.1

3.7

1706.3

506.3

3.2

1642.0

573.0

2.7

1458.7

573.4

2.4

1069.4

475.8

2.1

13.0

1886.7

387.1

4.5

1812.8

444.0

3.8

1751.7

511.1

3.2

1679.7

575.3

2.8

1479.3

569.5

2.5

1077.1

470.3

2.1

NOTES:

 

 

1.

kW

=

Compressor Input Power

2.

EER

=

Chiller EER (includes power from compressors, fans, and control panel’s 0.8 KW)

3.LCWT = Leaving Chilled Water Temperature

4.Ratings based on 2.4 GPM cooler water per ton

5.Rated in accordance with ARI Standard 550/590.