Dimensions – YCAS0400 - 0440 (SI)
All dimensions are in mm unless otherwise noted.
CONTROL ENTRY
(12)13 CONDUIT K.O.'S
229
711
51 TYP.
VIEW
51
120
178
CONTROL
OPENING1067 (229 HIGH)
51
305
800
POWER
OPENING (533 HIGH)
VIEW | 191 | LD04008 |
|
CONTROL CENTER
B | B | OPTIONS PANEL |
|
| |
|
| C |
| 543 |
CONTROL |
|
TRANSFORMER | C |
SERVICE SWITCH |
|
NOTES:
2331
VIEW A-A
651 (EDGE OF UNIT TO COOLER CONNECTION)
LD04007
1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.