York 28971AR manual Dimensions YCAS0090 0100EC SI

Models: 28971AR

1 104
Download 104 pages 9.03 Kb
Page 42
Image 42

Dimensions – YCAS0090 – 0100EC (SI)

 

 

 

3 SPA. @ 127

 

83

178

 

89

 

229

127

 

127

25 TYP.

 

 

 

57

51

 

 

 

 

229

 

432

44

432

51

 

 

 

25 TYP.

25

POWER ENTRY

 

 

CONTROL ENTRY

CONTROL ENTRY

(8) 38,51,64 CONDUIT K.O.'S

 

(7) 13 CONDUIT K.O.'S

(8) 22 DIA. HOLES

 

 

VIEW B-B

 

VIEW C-C

C

C

B

 

MICRO-COMPUTER CONTROL CENTER

OPTIONS PANEL

B

438

43 2235

2321

VIEW A-A

49 (EDGE OF UNIT TO COOLER CONNECTION)

POWER: MULTIPLE POINT WITH TERMINAL BLOCKS

LD05210

NOTES:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

42

YORK INTERNATIONAL

Page 42
Image 42
York 28971AR manual Dimensions YCAS0090 0100EC SI