Dimensions – YCAS0090 – 0100EC (English)

 

 

 

3 SPA. @ 5"

 

3 1/4"

7"

 

3 1/2"

 

9"

5"

 

5"

1" TYP.

 

 

 

2 1/4"

2"

 

 

 

 

9"

 

17"

1 3/4"

17"

2"

 

 

 

1" TYP.

1"

POWER ENTRY

 

 

CONTROL ENTRY

CONTROL ENTRY

(8) 1 1/2",2",2 1/2" CONDUIT K.O.'S

 

(7) 1/2" CONDUIT K.O.'S

(8) 7/8" DIA. HOLES

VIEW B-B

VIEW C-C

LD04469

C

C

B

 

CONTROL

 

TRANSFORMER

 

SERVICE SWITCH

 

1 11/16"

88"

91 3/8"

LD04470

VIEW A-A

MICRO-COMPUTER CONTROL CENTER

OPTIONS PANEL

B

17 1/4"

1 15/16" (EDGE OF UNIT TO COOLER CONNECTION)

POWER: MULTIPLE POINT WITH TERMINAL BLOCKS

NOTES:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6';control panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wallaym be higher than the unit.

40

YORK INTERNATIONAL

Page 40
Image 40
York 28971AR manual Dimensions YCAS0090 0100EC English, View A-A