Electrical Data (Continued)

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL SYSTEM

CIRCUIT BREAKERS – 3 & 4 COMPRESSOR UNITS (SEE FIG. 7)

(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)

in ‘Option Panel’. Individual System Circuit Breakers in each Motor Control Center.)

 

 

 

 

 

 

 

FIELD SUPPLIED WIRING

 

 

CHILLER

 

 

FIELD PROVIDED POWER SUPPLY

 

 

FACTORY PROVIDED (LUGS) WIRE RANGE7

MODEL

VOLTS

 

 

 

 

 

 

 

 

 

 

YCAS

MCA1

MIN NF

OVER-CURRENT PROTECTION13

 

TERMINAL BLOCK

NF DISC. SWITCH

 

DISC SW2, 9

MIN.3, 5

 

MAX.4, 6

 

(LUGS) WIRE RANGE

(LUGS) WIRE RANGE

 

380

561

600

600

 

700

 

(2)

2/0-500

(2)

250-500

0250EC

460

464

600

500

 

500

 

(2)

1/0-300

(2)

250-500

 

575

372

400

400

 

450

 

(2) # 2-4/0

(3)

2/0-250

 

380

651

800

800

 

800

 

(2)

2/0-500

(3)

2/0-400

0270EC

460

534

600

600

 

700

 

(2)

2/0-500

(2)

250-500

 

575

427

600

500

 

500

 

(2)

1/0-300

(2)

250-500

 

380

678

800

800

 

800

 

(3)

1/0-300

(3)

2/0-400

0300EC

460

559

600

600

 

700

 

(2)

2/0-500

(2)

250-500

 

575

445

600

500

 

500

 

(2)

1/0-500

(2)

250-500

 

380

745

800

800

 

800

 

(3)

1/0-300

(3)

2/0-400

0330EC

460

612

800

700

 

700

 

(2)

2/0-500

(3)

2/0-400

 

575

487

600

600

 

600

 

(2)

1/0-300

(2)

250-500

 

380

835

1000

1000

 

1000

 

(3)

2/0-500

(4)

4/0-500

0360EC

460

689

800

800

 

800

 

(3)

1/0-300

(3)

2/0-400

 

575

550

600

600

 

600

 

(2)

2/0-500

(2)

250-500

 

380

896

1000

1000

 

1000

 

(3)

2/0-500

(4)

4/0-500

0400EC

460

739

1000

800

 

800

 

(3)

2/0-500

(4)

4/0-500

 

575

589

800

700

 

700

 

(2)

2/0-500

(3)

2/0-400

 

380

991

1200

1200

 

1200

 

(3)

2/0-500

(4)

4/0-500

0440EC

460

812

1000

1000

 

1000

 

(3)

2/0-500

(4)

4/0-500

 

575

647

800

800

 

800

 

(2)

2/0-500

(3 )2/0-400