Electrical Data (Continued)
OPTIONAL
CIRCUIT BREAKERS – 3 & 4 COMPRESSOR UNITS (SEE FIG. 7)
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or
in ‘Option Panel’. Individual System Circuit Breakers in each Motor Control Center.)
|
|
|
|
|
|
| FIELD SUPPLIED WIRING |
|
| ||
CHILLER |
|
| FIELD PROVIDED POWER SUPPLY |
|
| FACTORY PROVIDED (LUGS) WIRE RANGE7 | |||||
MODEL | VOLTS |
|
|
|
|
|
|
|
|
|
|
YCAS | MCA1 | MIN NF |
| TERMINAL BLOCK | NF DISC. SWITCH | ||||||
| DISC SW2, 9 | MIN.3, 5 |
| MAX.4, 6 |
| (LUGS) WIRE RANGE | (LUGS) WIRE RANGE | ||||
| 380 | 561 | 600 | 600 |
| 700 |
| (2) | (2) | ||
0250EC | 460 | 464 | 600 | 500 |
| 500 |
| (2) | (2) | ||
| 575 | 372 | 400 | 400 |
| 450 |
| (2) # | (3) | ||
| 380 | 651 | 800 | 800 |
| 800 |
| (2) | (3) | ||
0270EC | 460 | 534 | 600 | 600 |
| 700 |
| (2) | (2) | ||
| 575 | 427 | 600 | 500 |
| 500 |
| (2) | (2) | ||
| 380 | 678 | 800 | 800 |
| 800 |
| (3) | (3) | ||
0300EC | 460 | 559 | 600 | 600 |
| 700 |
| (2) | (2) | ||
| 575 | 445 | 600 | 500 |
| 500 |
| (2) | (2) | ||
| 380 | 745 | 800 | 800 |
| 800 |
| (3) | (3) | ||
0330EC | 460 | 612 | 800 | 700 |
| 700 |
| (2) | (3) | ||
| 575 | 487 | 600 | 600 |
| 600 |
| (2) | (2) | ||
| 380 | 835 | 1000 | 1000 |
| 1000 |
| (3) | (4) | ||
0360EC | 460 | 689 | 800 | 800 |
| 800 |
| (3) | (3) | ||
| 575 | 550 | 600 | 600 |
| 600 |
| (2) | (2) | ||
| 380 | 896 | 1000 | 1000 |
| 1000 |
| (3) | (4) | ||
0400EC | 460 | 739 | 1000 | 800 |
| 800 |
| (3) | (4) | ||
| 575 | 589 | 800 | 700 |
| 700 |
| (2) | (3) | ||
| 380 | 991 | 1200 | 1200 |
| 1200 |
| (3) | (4) | ||
0440EC | 460 | 812 | 1000 | 1000 |
| 1000 |
| (3) | (4) | ||
| 575 | 647 | 800 | 800 |
| 800 |
| (2) | (3 |
See page 89 for Electrical Data footnotes.