Electrical Data (Continued)

OPTIONAL SINGLE-POINT POWER SUPPLY WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS –

2 COMPRESSOR UNITS (SEE FIG. 2)

(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in ‘Option Panel’.

Individual Branch Circuit Protection (Breakers) per Motor Control Center10)

CHILLER

 

 

 

 

 

 

FIELD-SUPPLIED WIRING

 

 

 

 

FIELD PROVIDED POWER SUPPLY

 

 

FACTORY PROVIDED (LUGS) WIRE RANGE 7

MODEL

VOLTS

 

 

 

 

MIN NF

OVER-CURRENT PROTECTION13

 

STANDARD

OPTIONAL NF

YCAS

 

MCA1

 

 

DISC SW2, 9

MIN.3, 5

 

MAX.4, 6

 

TERMINAL BLOCK

DISC. SWITCH

 

 

 

 

 

 

200

407.0

600

450

 

500

 

# 2 - 300

(3) 2/0 - 400

 

230

358.0

400

400

 

500

 

1/0 - 500

2/0 - 500

0090EC

380

218.0

250

250

 

300

 

# 2 - 300

#2 - 300

 

460

182.0

200

200

 

250

 

# 2 - 4/0

# 14 - 250

 

575

143.0

150

175

 

175

 

# 2 - 4/0

# 14 - 250

 

200

428.0

600

500

 

500

 

# 2 - 300

(3) 2/0 - 400

 

230

376.0

400

450

 

500

 

1/0 - 500

(3) 2/0 - 400

0100EC

380

227.0

250

250

 

300

 

# 2 - 300

250 - 500

 

460

189.0

200

225

 

250

 

# 2 - 4/0

# 14 - 250

 

575

150.0

200

175

 

200

 

# 2 - 4/0

# 14 - 250

 

200

521.0

600

600

 

700

 

1/0 - 500

(3) 2/0 - 400

 

230

452.0

600

600

 

600

 

# 2 - 300

(3) 2/0 - 400

0110EC

380

269.0

400

300

 

350

 

1/0 - 500

250 - 500

 

460

225.0

250

250

 

300

 

# 2 - 300

# 14 - 250

 

575

181.0

200

225

 

250

 

# 2 - 4/0

# 14 - 250

 

200

545.0

600

700

 

700

 

1/0 - 500

(2) 250 - 500

 

230

472.0

600

600

 

600

 

# 2 - 300

(3) 2/0 - 400

0120EC

380

280.0

400

350

 

400

 

1/0 - 500

250 - 500

 

460

235.0

250

300

 

300

 

# 2 - 300

250 - 500

 

575

189.0

200

225

 

250

 

# 2 - 4/0

# 14 - 250

 

200

619.3

800

700

 

700

 

(3) 2/0 - 500

(3)

2/0-400

 

230

543.9

600

600

 

700

 

(2) 2/0 - 500

(2) 250-500

0130EC

380

329.8

400

400

 

450

 

(2) 1/0 - 300

(2)

3/0-250

 

460

272.8

400

300

 

350

 

2/0 - 500

(2)

3/0-250

 

575

217.4

250

250

 

300

 

2/0 - 500

# 6 - 350

 

200

665.9

800

800

 

800

 

(3) 2/0 - 500

(3)

2/0-400

 

230

584.4

800

700

 

800

 

(3) 2/0 - 500

(2) 250-500

0140EC

380

354.3

400

400

 

450

 

(2) 1/0 - 300

(2)

3/0-250

 

460

293.0

400

350

 

400

 

(2) 1/0 - 300

(2)

3/0-250

 

575

233.6

250

300

 

300

 

2/0 - 500

# 6 - 350

 

200

698.9

800

800

 

800

 

(3) 2/0 - 500

(3)

2/0-400

 

230

612.4

800

700

 

800

 

(3) 2/0 - 500

(3)

2/0-400

0150EC

380

371.4

400

450

 

500

 

(2) 2/0 - 500

(2)

3/0-250

 

460

307.0

400

350

 

400

 

(2) 1/0 - 300

(2)

3/0-250

 

575

245.6

400

300

 

300

 

2/0 - 500

(2)

3/0-250

 

200

729.4

800

1000

 

800

 

(3) 2/0 - 500

(3)

2/0-400

 

230

638.4

800

800

 

800

 

(3) 2/0 - 500

(3)

2/0-400

0160EC

380

387.2

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

320.0

400

400

 

400

 

(2) 1/0 - 300

(2)

3/0-250

 

575

256.6

400

300

 

300

 

2/0 - 500

(2)

3/0-250

 

200

761.9

800

1000

 

1000

 

(3) 2/0 - 500

(3)

2/0-400

 

230

667.2

800

800

 

800

 

(3) 2/0 - 500

(3)

2/0-400

0170EC

380

404.7

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

335.0

400

400

 

400

 

(2) 1/0 - 300

(2)

3/0-250

 

575

267.8

400

300

 

350

 

2/0 - 500

(2)

3/0-250

 

200

787.9

1000

1000

 

1000

 

(3) 2/0 - 500

(4)

4/0-500

 

230

690.2

800

800

 

800

 

(3) 2/0 - 500

(3)

2/0-400

0180EC

380

418.7

600

500

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

347.0

400

400

 

450

 

(2) 1/0 - 300

(2)

3/0-250

 

575

276.8

400

350

 

350

 

(2) 1/0 - 300

(2)

3/0-250

 

200

851.5

1000

1000

 

1000

 

(3) 2/0 - 500

(4)

4/0-500

 

230

748.5

800

1000

 

800

 

(3) 2/0 - 500

(3)

2/0-400

0200EC

380

455.3

600

600

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

375.3

400

450

 

450

 

(2) 2/0 - 500

(2)

3/0-250

 

575

298.8

400

350

 

350

 

(2) 1/0 - 300

(2)

3/0-250

 

200

891.5

1000

1000

 

1000

 

(3) 2/0 - 500

(4)

4/0-500

 

230

782.3

1000

1000

 

1000

 

(3) 2/0 - 500

(4)

4/0-500

0210EC

380

475.3

600

600

 

600

 

(2) 2/0 - 500

(2) 250-500

 

460

392.8

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

575

312.5

400

350

 

400

 

(2) 1/0 - 300

(2)

3/0-250

 

200

923.5

1000

1200

 

1200

 

(3) 2/0 - 500

(4)

4/0-500

 

230

809.3

1000

1000

 

1000

 

(3) 2/0 - 500

(4)

4/0-500

0230EC

380

491.3

600

600

 

600

 

(2) 2/0 - 500

(2) 250-500

 

460

406.8

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

575

323.5

400

400

 

450

 

(2) 1/0 - 300

(2)

3/0-250

See page 89 for Electrical Data footnotes.

82

YORK INTERNATIONAL

Page 82
Image 82
York 28971AR manual Chiller FIELD-SUPPLIED Wiring