Dimensions – YCAS0300 - 0330 (SI)

All dimensions are in mm unless otherwise noted.

CONTROL ENTRY

(12)22 CONDUIT K.O.'S

229

711

51 TYP.

VIEW B-B

178

CONTROL

 

OPENING

51

(229 HIGH)

 

 

51

 

305

120

 

 

POWER

 

OPENING

 

(533 HIGH)

1067

800

NOTES:

VIEW C-C

191

LD03984

 

MICRO-COMPUTER

CONTROL CENTER

B

B OPTIONS PANEL

 

 

C

 

511

CONTROL

C

TRANSFORMER

SERVICE SWITCH

 

112 (EDGE OF UNIT TO COOLER CONNECTION)

2331

VIEW A-A

LD03983

 

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

62