Electrical Data (Continued)

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION – 2 COMPRESSOR UNITS (SEE FIG. 3)

(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in ‘Option Panel’.

No Internal Branch Circuit Protection (Breakers) per Motor Control Center10)

CHILLER

 

 

 

 

 

 

FIELD-SUPPLIED WIRING

 

 

 

 

FIELD PROVIDED POWER SUPPLY

 

 

FACTORY PROVIDED (LUGS) WIRE RANGE 7

MODEL

VOLTS

 

 

 

YCAS

 

MCA1

MIN NF

OVER-CURRENT PROTECTION13

 

STANDARD

OPTIONAL NF

 

DISC SW2, 9

MIN.3, 5

 

MAX.4, 6

 

TERMINAL BLOCK

DISC. SWITCH

 

 

 

 

 

 

380

218

250

250

 

300

 

# 2 - 300

 

#N/A

0090EC

460

182

200

200

 

250

 

# 2 - 4/0

# 14 - 250

 

575

143

150

175

 

175

 

# 2 - 4/0

# 14 - 250

 

380

227

250

250

 

300

 

# 2 - 300

250 - 500

0100EC

460

189

200

225

 

250

 

# 2 - 4/0

# 14 - 250

 

575

150

200

175

 

200

 

# 2 - 4/0

# 14 - 250

 

380

269

400

300

 

350

 

1/0 - 500

250 - 500

0110EC

460

225

250

250

 

300

 

# 2 - 300

# 14 - 250

 

575

181

200

225

 

250

 

# 2 - 4/0

# 14 - 250

 

380

280

400

350

 

400

 

1/0 - 500

250 - 500

0120EC

460

235

250

300

 

300

 

# 2 - 300

250 - 500

 

575

189

200

225

 

250

 

# 2 - 4/0

# 14 - 250

0130EC

460

273

400

300

 

350

 

# 1 - 500

(2)

3/0-250

575

217

250

250

 

300

 

# 1 - 500

# 6 - 350

 

 

 

0140EC

460

293

400

350

 

400

 

(2) # 2 - 300

(2)

3/0-250

575

234

250

300

 

300

 

# 1 - 500

# 6 - 350

 

 

 

0150EC

460

307

400

350

 

400

 

(2) # 2 - 300

(2)

3/0-250

575

246

400

300

 

300

 

# 1 - 500

(2)

3/0-250

 

 

 

0160EC

460

320

400

400

 

400

 

(2) # 2 - 300

(2)

3/0-250

575

257

400

300

 

350

 

# 1 - 500

(2)

3/0-250

 

 

 

0170EC

460

335

400

400

 

450

 

(2) # 2 - 300

(2)

3/0-250

575

268

400

300

 

350

 

# 1 - 500

(2)

3/0-250

 

 

 

0180EC

460

347

400

400

 

450

 

(2) # 2 - 300

(2)

3/0-250

575

277

400

350

 

350

 

(2) # 2 - 300

(2)

3/0-250

 

 

 

0200EC

460

375

400

450

 

500

 

(2) # 1 - 500

(2)

3/0-250

575

299

400

350

 

400

 

(2) # 2 - 300

(2)

3/0-250

 

 

 

0210EC

460

393

600

450

 

500

 

(2) # 1 - 500

(2) 250-500

575

313

400

350

 

400

 

(2) # 2 - 300

(2)

3/0-250

 

 

 

0230EC

460

407

600

450

 

500

 

(2) # 1 - 500

(2) 250-500

575

324

400

400

 

450

 

(2) # 2 - 300

(2)

3/0-250

 

 

 

See page 89 for Electrical Data footnotes.