York 28971AR manual Dimensions YCAS0360 English, View A-A View C-C

Models: 28971AR

1 104
Download 104 pages 9.03 Kb
Page 64
Image 64

Dimensions – YCAS0360 (English)

28"

7"

CONTROL OPENING (9" HIGH)

42"

CONTROL ENTRY

(12)1/2" CONDUIT K.O.'S

2"

12"

4 3/4"

2"

31 1/2"

9"

2" TYP.

POWER OPENING (21" HIGH)

VIEW B-B

B

CONTROL

TRANSFORMER

SERVICE SWITCH

91-13/16"

VIEW A-A

NOTES:

VIEW C-C

7 1/2"

LD03996

MICRO-COMPUTER

CONTROL CENTER

BOPTIONS PANEL C

21-3/8"

C

25-5/8" (EDGE OF UNIT TO COOLER CONNECTION)

LD03995

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6';control panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher than the unit.

64

YORK INTERNATIONAL

Page 64
Image 64
York 28971AR manual Dimensions YCAS0360 English, View A-A View C-C