FORM 201.18-EG1

TEMPERATURE AND FLOWS

(SI Units)

MODEL

LEAVING WATER

COOLER FLOW

 

AIR ON

NUMBER

TEMPERATURE (°C)

 

(L/S)3

CONDENSER (°C)

 

 

 

 

 

 

 

 

YCAS

MIN.1

MAX.2

MIN.

 

MAX.

MIN.

 

MAX

 

 

 

 

 

 

 

 

 

0090EC

4.4

12.8

7.0

 

38.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0100EC

4.4

12.8

8.0

 

38.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0110EC

4.4

12.8

8.0

 

38.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0120EC

4.4

12.8

8.0

 

38.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0130EC

4.4

12.8

9.3

 

37.8

-17.7

 

51.7

0140EC

4.4

12.8

10.7

 

37.8

-17.7

 

51.7

0150EC

4.4

12.8

11.5

 

44.2

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0160EC

4.4

12.8

11.9

 

47.1

-17.7

 

51.7

0170EC

4.4

12.8

12.8

 

47.1

-17.7

 

51.7

0180EC

4.4

12.8

13.8

 

47.1

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0200EC

4.4

12.8

14.4

 

47.1

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0210EC

4.4

12.8

15.6

 

47.1

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0230EC

4.4

12.8

17.2

 

47.1

-17.7

 

51.7

0250EC

4.4

12.8

14.0

 

50.0

-17.7

 

51.7

0270EC

4.4

12.8

14.0

 

50.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0300EC

4.4

12.8

16.0

 

50.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0330EC

4.4

12.8

16.0

 

50.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0360EC

4.4

12.8

19.0

 

67.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0400EC

4.4

12.8

21.0

 

67.0

-17.7

 

51.7

 

 

 

 

 

 

 

 

 

0440EC

4.4

12.8

21.0

 

67.0

-17.7

 

51.7

NOTES:

1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.

2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.

3.The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.

YORK INTERNATIONAL

11

Page 11
Image 11
York 28971AR manual SI Units