Electrical Data (Continued)

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER –

2 COMPRESSOR UNITS (SEE FIG.4)

(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in ‘Option Panel’.

No internal Individual System Circuit Protection per Motor Control Center10.)

MODEL

 

 

FIELD SUPPLIED WIRING

 

 

SYSTEM #1

 

 

 

SYSTEM #2

 

VOLTS

 

FACTORY SUPPLIED BREAKER

COMPRESSOR

 

FANS11, 12

COMPRESSOR

 

FANS11, 12

 

YCAS

MCA1

 

 

 

 

RATING2

WIRE RANGE7 (LUGS)

RLA

X-LRA

QTY

FLA(ea)

LRA(ea)

RLA

X-LRA

 

QTY

FLA(ea)

LRA(ea)

 

 

 

 

 

380

218

300

 

#N/A

84

681

 

3

4.8

23.0

84

681

 

3

4.8

 

23.0

0090EC

460

182

250

# 14 - 250

70

542

 

3

4.0

19.0

70

542

 

3

4.0

 

19.0

 

575

143

200

# 14 - 250

55

431

 

3

3.1

15.2

55

431

 

3

3.1

 

15.2

 

380

227

300

250 - 500

88

681

 

3

4.8

23.0

88

681

 

3

4.8

 

23.0

0100EC

460

189

250

# 14 - 250

73

542

 

3

4.0

19.0

73

542

 

3

4.0

 

19.0

 

575

150

200

# 14 - 250

58

431

 

3

3.1

15.2

58

431

 

3

3.1

 

15.2

 

380

269

350

250 - 500

121

900

 

3

5.2

21.0

86

681

 

3

5.2

 

21.0

0110EC

460

225

300

# 14 - 250

99

719

 

3

5.0

27.0

71

542

 

3

5.0

 

27.0

 

575

181

250

# 14 - 250

81

574

 

3

3.9

26.0

56

431

 

3

3.9

 

26.0

 

380

280

400

250 - 500

130

900

 

3

5.2

21.0

86

681

 

3

5.2

 

21.0

0120EC

460

235

300

250 - 500

107

719

 

3

5.0

27.0

71

542

 

3

5.0

 

27.0

 

575

189

250

# 14 - 250

87

574

 

3

3.9

26.0

56

431

 

3

3.9

 

26.0

0130EC

460

273

400

(2)

3/0-250

107

719

 

4

4.0

19.0

107

719

 

4

4.0

 

19.0

575

217

250

# 6 - 350

86

574

 

4

3.1

15.2

86

574

 

4

3.1

 

15.2

 

 

 

 

0140EC

460

293

400

(2)

3/0-250

116

719

 

4

4.0

19.0

116

719

 

4

4.0

 

19.0

575

234

400

(2)

3/0-250

93

574

 

4

3.1

15.2

93

574

 

4

3.1

 

15.2

 

 

 

 

0150EC

460

307

400

(2)

3/0-250

128

893

 

4

4.0

19.0

115

719

 

4

4.0

 

19.0

575

246

400

(2)

3/0-250

103

714

 

4

3.1

15.2

92

574

 

4

3.1

 

15.2

 

 

 

 

0160EC

460

320

400

(2)

3/0-250

128

893

 

4

4.0

19.0

128

893

 

4

4.0

 

19.0

575

257

400

(2)

3/0-250

103

714

 

4

3.1

15.2

103

714

 

4

3.1

 

15.2

 

 

 

 

0170EC

460

335

400

(2)

3/0-250

140

893

 

4

4.0

19.0

128

893

 

4

4.0

 

19.0

575

268

400

(2)

3/0-250

112

714

 

4

3.1

15.2

103

714

 

4

3.1

 

15.2

 

 

 

 

0180EC

460

347

400

(2)

3/0-250

140

893

 

4

4.0

19.0

140

893

 

4

4.0

 

19.0

575

277

400

(2)

3/0-250

112

714

 

4

3.1

15.2

112

714

 

4

3.1

 

15.2

 

 

 

 

0200EC

460

375

600

(3)

2/0-400

149

893

 

5

4.0

19.0

149

893

 

5

4.0

 

19.0

575

299

400

(2)

3/0-250

119

714

 

5

3.1

15.2

119

714

 

5

3.1

 

15.2

 

 

 

 

0210EC

460

393

600

(3)

2/0-400

163

893

 

5

4.0

19.0

149

893

 

5

4.0

 

19.0

575

313

400

(2)

3/0-250

130

714

 

5

3.1

15.2

119

714

 

5

3.1

 

15.2

 

 

 

 

0230EC

460

407

600

(3)

2/0-400

163

893

 

5

4.0

19.0

163

893

 

5

4.0

 

19.0

575

324

400

(2)

3/0-250

130

714

 

5

3.1

15.2

130

714

 

5

3.1

 

15.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Wye-Delta Compressor Start not available with this option.

See page 89 for Electrical Data footnotes.

Electrical Notes

LEGEND

 

ACR-LINE

ACROSS THE LINE START

C.B.

CIRCUIT BREAKER

D.E.

DUAL ELEMENT FUSE

DISC SW

DISCONNECT SWITCH

FACT CB

FACTORY-MOUNTED CIRCUIT BREAKER

FLA

FULL LOAD AMPS

HZ

HERTZ

MAX

MAXIMUM

MCA

MINIMUM CIRCUIT AMPACITY

MIN

MINIMUM

MIN NF

MINIMUM NON-FUSED

RLA

RUNNING LOAD AMPS

S.P. WIRE

SINGLE-POINT WIRING

Y-

WYE-DELTA START

X-LRA

ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS

Y-LRA

WYE-DELTA INRUSH LOCKED ROTOR AMPS

88

VOLTAGE CODE

-17 = 200-3-60 -28 = 230-3-60 -40 = 380-3-60 -46 = 460-3-60 -58 = 575-3-60