York 28971AR manual Dimensions YCAS0360 SI

Models: 28971AR

1 104
Download 104 pages 9.03 Kb
Page 66
Image 66

Dimensions – YCAS0360 (SI)

All dimensions are in mm unless otherwise noted.

178

CONTROL ENTRY

(12)22 CONDUIT K.O.'S

229

711

51 TYP.

51

305 120

CONTROL OPENING

(229 HIGH)

51

POWER

OPENING (533 HIGH)

1067

800

VIEW B-B

B

CONTROL TRANSFORMER SERVICE SWITCH

2331

VIEW A-A

VIEW C-C

MICRO-COMPUTER

CONTROL CENTER

BOPTIONS PANEL C

543

C

651 (EDGE OF UNIT TO COOLER CONNECTION)

LD03999

191

LD04000

NOTES:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

66

YORK INTERNATIONAL

Page 66
Image 66
York 28971AR manual Dimensions YCAS0360 SI