Application Data
UNIT LOCATION
The YCAS chillers are designed for outdoor installation. When selecting a site for installation, be guided by the following requirements:
1.Installation sites may be either on a roof or on ground level. (See FOUNDATION)
2.Select a place having an adequate supply of fresh air for the condensers. Recommended clearances for all units are shown on the DIMENSIONS pages.
3.Avoid locations near windows or structures where normal operating sounds may be objectionable.
4.The standard condenser fans are
5.When it is desirable to surround the unit(s), it is recommended that the screening be able to pass the required chiller CFM without exceeding 0.1" external static pressure.
6.Protection against corrosive environments is available by supplying the units with either copper fins, or cured phenolic or
7.On installations where winter operation is intended and snow accumulations are expected, additional elevation must be provided to insure normal condenser air flow.
FOUNDATION
The unit should be mounted on a flat and level foundation, ground or roof, capable of supporting the entire operating weight of the equipment. Operating weights are given in the PHYSICAL DATA tables.
Roof Locations – Adequate structural strength to safely support the entire weight of the unit and service personnel must be provided. Care must be taken not to damage the roof during installation. If the roof is “bonded”, consult building contractor or architect for special installation requirements. Roof installations should incorporate the use of
minimize the transmission of vibration into building structure. Additional support should be provided to the roof at the
Ground Locations – Units must be installed on a substantial base that will not settle and cause strain on the refrigerant lines, resulting in possible leaks. A one- piece concrete slab, with footers extending below the frost line, is recommended. The slab should not be tied to the main building foundation as noises will telegraph.
Mounting holes (5/8") are provided in the base rails for bolting the unit to its foundation. See DIMENSIONS for location of the mounting holes.
For ground installations, precautions should be taken to protect the unit from tampering by, or injury to, unauthorized persons. Fasteners on access panels will prevent casual tampering; however, further safety precautions, such as unit enclosure options, a fenced- in enclosure, or locking devices on the panels may be advisable. Check local authorities for safety regula- tions.
CHILLED LIQUID PIPING
The chilled liquid piping system should be laid out so that the circulating pump discharges into the cooler. The inlet and outlet
A strainer (40 mesh) is recommended for use on the INLET line to the cooler, and must be in place at initial operation of the water pumps.
Chilled liquid lines exposed to the weather should be wrapped with a supplemental heater cable and insulated, or glycol should be added to the chilled liquid to protect against freezing if
A flow switch is available as an accessory on all units. A flow switch must be installed in the leaving water piping of the cooler and must not be used to start and stop the unit.