Emerson manual Table A-1. Rosemount 644 Input Options and Accuracy, Accuracy Example

Page 52

Rosemount 644

Reference Manual

00809-0400-4728, Rev AA June 2011

Accuracy

Table A-1. Rosemount 644 Input Options and Accuracy

Sensor

Sensor

Input

 

Recommended

Digital

D/A

Options

Reference

Ranges

 

Min. Span(1)

Accuracy(2)

Accuracy(3)

2-, 3-, 4-wire RTDs

 

°C

°F

 

°C

°F

°C

°F

 

Pt 100 (α = 0.00385)

IEC 751

–200 to 850

–328 to

1562

10

18

± 0.15

± 0.27

±0.03% of span

Pt 200 (α = 0.00385)

IEC 751

–200 to 850

–328 to

1562

10

18

± 0.15

± 0.27

±0.03% of span

Pt 500 (α = 0.00385)

IEC 751

–200 to 850

–328 to

1562

10

18

± 0.19

± 0.34

±0.03% of span

Pt 1000 (α = 0.00385)

IEC 751

–200 to 300

–328 to 572

10

18

± 0.19

± 0.34

±0.03% of span

Pt 100 (α = 0.003916)

JIS 1604

–200 to 645

–328 to 1193

10

18

± 0.15

± 0.27

±0.03% of span

Pt 200 (α = 0.003916)

JIS 1604

–200 to 645

–328 to 1193

10

18

± 0.27

± 0.49

±0.03% of span

Ni 120

Edison Curve No. 7

–70 to 300

–94 to

572

10

18

± 0.15

± 0.27

±0.03% of span

Cu 10

Edison Copper Winding No. 15

–50 to 250

–58 to

482

10

18

±1.40

± 2.52

±0.03% of span

Pt 50 (α = 0.00391)

GOST 6651-94

–200 to 550

–328 to

1022

10

18

± 0.30

± 0.54

±0.03% of span

Pt 100 (α = 0.00391)

GOST 6651-94

–200 to 550

–328 to

1022

10

18

± 0.15

± 0.27

±0.03% of span

Cu 50 (α = 0.00426)

GOST 6651-94

–50 to 200

–58 to

392

10

18

±1.34

± 2.41

±0.03% of span

Cu 50 (α = 0.00428)

GOST 6651-94

–185 to 200

–301 to 392

10

18

±1.34

± 2.41

±0.03% of span

Cu 100 (α = 0.00426)

GOST 6651-94

–50 to 200

–58 to

392

10

18

±0.67

± 1.20

±0.03% of span

Cu 100 (α = 0.00428)

GOST 6651-94

–185 to 200

–301 to 392

10

18

±0.67

± 1.20

±0.03% of span

Thermocouples(4)

 

 

 

 

 

 

 

 

 

Type B(5)

NIST Monograph 175, IEC 584

100 to 1820

212 to 3308

25

45

± 0.77

± 1.39

±0.03% of span

Type E

NIST Monograph 175, IEC 584

–50 to 1000

–58 to 1832

25

45

± 0.20

± 0.36

±0.03% of span

Type J

NIST Monograph 175, IEC 584

–180 to 760

–292 to

1400

25

45

± 0.35

± 0.63

±0.03% of span

Type K(6)

NIST Monograph 175, IEC 584

–180 to 1372

–292 to

2501

25

45

± 0.50

± 0.90

±0.03% of span

Type N

NIST Monograph 175, IEC 584

–200 to 1300

–328 to

2372

25

45

± 0.50

± 0.90

±0.03% of span

Type R

NIST Monograph 175, IEC 584

0 to 1768

32 to 3214

25

45

± 0.75

± 1.35

±0.03% of span

Type S

NIST Monograph 175, IEC 584

0 to 1768

32 to 3214

25

45

± 0.70

± 1.26

±0.03% of span

Type T

NIST Monograph 175, IEC 584

–200 to 400

–328 to 752

25

45

± 0.35

± 0.63

±0.03% of span

DIN Type L

DIN 43710

–200 to 900

–328 to

1652

25

45

± 0.35

± 0.63

±0.03% of span

DIN Type U

DIN 43710

–200 to 900

–328 to 1112

25

45

± 0.35

± 0.63

±0.03% of span

Type W5Re/W26Re

ASTM E 988-96

0 to 2000

32 to 3632

25

45

± 0.70

± 1.26

±0.03% of span

GOST Type L

GOST R 8.585-2001

–200 to 800

–328 to

1472

25

45

± 1.00

± 1.26

±0.03% of span

Other Input Types

 

 

 

 

 

 

 

 

 

Millivolt Input

 

–10 to

100 mV

 

 

 

±0.015

mV

±0.03% of span

2-, 3-, 4-wire Ohm Input

 

0 to 2000 ohms

 

 

 

±0.45 ohm

±0.03% of span

(1)No minimum or maximum span restrictions within the input ranges. Recommended minimum span will hold noise within accuracy specification with damping at zero seconds.

(2)The published digital accuracy applies over the entire sensor input range. Digital output can be accessed by HART or FOUNDATION fieldbus Communications or Rosemount control system.

(3)Total Analog accuracy is the sum of digital and D/A accuracies. This is not applicable for FOUNDATION fieldbus.

(4)Total digital accuracy for thermocouple measurement: sum of digital accuracy +0.5 °C. (cold junction accuracy).

(5)Digital accuracy for NIST Type B T/C is ±3.0 °C (±5.4 °F) from 100 to 300 °C (212 to 572 °F).

(6)Digital accuracy for NIST Type K T/C is ±0.70 °C (±1.26 °F) from –180 to –90 °C (–292 to –130 °F).

Accuracy Example

When using a Pt 100 (α = 0.00385) sensor input:

Total accuracy = ±0.15 °C.

No D/A accuracy effects apply

A-6

Image 52
Contents Reference Manual 00809-0400-4728, Rev AA JunePage Table of Contents Specifications Reference Data Appendix aAppendix B TOC-2Rosemount Temperature Transmitters Customer Central National Response Center InternationalPage Safety Messages Section IntroductionExplosions could result in death or serious injury Process leaks could result in death or serious injuryManual OverviewTransmitter Considerations 22 20 815 C 1500 F Oven Temperature 250 C 482 F Oven Temperature 5 6 7 8 Extension LengthExample AboveSection Installation Bench Calibration? Within Specifications? Refer to ConfigurationSimulate Sensor Input From draining into the transmitter housing MountingMounting a 644H to a DIN Rail Rail asymmetricTypical European Installation InstallationHead Mount Transmitter with DIN Plate Style Sensor Typical North American Installation Head Mount Transmitter with Threaded SensorLCD Display Installation Installing the LCD DisplayWiring Power terminals does not drop below 9 VdcSensor Connections Thermocouple or Millivolt InputsSensor Input Approximate Basic Error Sensor Lead Wire Resistance Effect- RTD InputRTD or Ohm Inputs Pt100 2-wire RTD Error due to amb. temp. var. of ± 25 CPower Supply Foundation fieldbus InstallationGround the Transmitter Ungrounded Thermocouple, mV, and RTD/Ohm InputsGrounded Thermocouple Inputs Section Configuration Overview Safety MessagesGeneral Block Information Device Description Node AddressModes AutoLink Active Scheduler Block Installation Resource Transducer Analog Input OtherCapabilities Foundation Fieldbus Function BlocksFeatures Resource BlockUnicode ReportsFeaturessel FailedalarmsMaxnotify PlantWeb AlertsMaintalarms FailedmaskRecommended Actions for PlantWeb Alerts Advisory AlarmsRecommendedaction Configure the AI block Sensor Transducer BlockAnalog Input AI Function Block DampingLtype Pressure Channel Temperature ChannelXdscale and Outscale Configuration Examples Transducer BlockProcess Alarms FilteringAlarmtype OutdLCD Transducer Block DisplayparamselBLKTYPE#1 PARAMINDEX#1Operation and Maintenance OverviewUNITSTYPE#1 CUSTOMUNITS#1Troubleshooting Guides Troubleshooting guideProblems with communications flowchart Calpointlo + Calminspan Diagnostics Recall Factory TrimBlock Blockerr messages Sensor Transducer Block Xderr messagesDescription CalibrationerrManual Mode StatusSimulation SimulateTroubleshooting AI block Power UpSymptom Possible Causes Recommended Actions 00809-0400-4728, Rev AA June AI Blockerr ConditionsBlock Errors 8lists conditions reported in the Blockerr parameter10. Resource Block Condition NameSymptom Possible Causes Recommended Action Self Test Procedure for the LCDAuto Specifications Appendix a Specifications Reference DataFunctionalInputs Physical Performance Foundation Fieldbus Specifications Rosemount Conformance to SpecificationsFunction Blocks 2 σ -1 σPower Supply AlarmsBackup Link Active Scheduler LAS Software Upgrade in the FieldTable A-1. Rosemount 644 Input Options and Accuracy AccuracyAccuracy Example Table A-2. Ambient Temperature Effect Ambient Temperature EffectThermocouples Temperature Effects Examples Dimensional Drawings 644H DIN a Head MountLCD Display Mounting00809-0400-4728, Rev AA JuneLCD Display Cover Sanitary Housing CoversRing 76.2 27.9 74.4 25.4 44.5 70.0 Ordering Information OptionsConfiguration Standard Alarm Level Configuration StandardAssemble To Options Standard Enclosure Options StandardTagging ConsiderationsConfiguration tool Transmitter ConfigurationWith DeltaV, with AMS, or other Foundation fieldbus host or Standard Foundation fieldbus Configuration Custom ConfigurationRequirements Option Code Specification Standard Block ConfigurationAppendix B Product Certifications CE Electromagnetic Compatibility Compliance TestingAtex Directive 94/9/EC North American Certifications Hazardous Locations CertificatesRosemount 644 with Foundation fieldbus Loop/Power Terminals Fisco Loop/Power TerminalsEuropean Certifications Special Conditions for Safe UseTemperature Class IECEx CertificationsTo 60 C Fisco Group IIC To 80 CTable B-3. Entity Parameters Transmitter I.S Transmitter Fisco SensorTransmitter Sensor Schedule of LimitationsUkraine Gost Pattern Approval for Measuring Instruments See CertificateApproval Temp Description Group CodeInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Appendix C Foundation fieldbus Block Information Basic Setup Resource BlockDefinition Parameters and Descriptions IndexFailedenable FeaturesFeaturesel Maintenable00809-0400-4728, Rev AA Parameters Descriptions Sensor Transducer BlockDescription Effects transmitter operation Primaryvaluerange PrimaryvaluetypeSensrdetailedstatus CalvandusencoeffXderror SESNOR1DAMPINGTransducerdirectory TransducertypeAnalog Measurement Access Analog Input AI Function BlockOutd Cutoff Filter Convert CalcAI Parameter Table AckoptionLolopri Table C-4. LCD Transducer Block Parameters and Descriptions LCD Transducer BlockParameter Index Description Table C-5. PID Block Parameters and Descriptions PID BlockParameter Index Index Ungrounded Wiring MODEBLK.TARGET Bad UncertainLolim Lololim Lolopri Lopri Lower Trim Method DIN Rail Threaded SensorLimited Man Mode Unicode UNITSTYPE# Upper Trim Method Grounded Ungrounded WiringSecurity Self Test Direct Zero TrimIndex-4 Page Temperature GmbH Pacific Private Limited Emerson Process Management Rosemount Inc