Emerson 644 manual Sensor Transducer Block, Analog Input AI Function Block, Damping, Channel

Page 31

Reference Manual

00809-0400-4728, Rev AA June 2011

Rosemount 644

Table 3-1.

RB.RECOMMENDED_ACTION

Sensor Transducer Block

 

 

Failed/Maint/Advise

Recommended Action

 

Alarm Type

Active Event

Text String

 

None

None

No action required

 

 

NV Writes Deferred

Non-volatile writes have been deferred, leave

 

Advisory

 

the device powered until the advisory goes

 

 

 

away

 

 

Configuration Error

Re-write the Sensor Configuration

 

 

Primary Value

Confirm the operating range of the applied

 

 

Degraded

sensor and/or verify the sensor connection and

Alerts

Maintenance

 

device environment

 

Calibration Error

Retrim the device

 

Secondary Value

Verify the ambient temperature is within

PlantWeb

 

Degraded

operating limits

 

Electronics Failure

Replace the Device

 

HW / SW Incompatible

Verify the Hardware Revision is compatible with

 

 

the Software Revision

 

 

 

 

 

NV Memory Failure

Reset the device then download the Device

 

Failed

 

Configuration

 

Primary Value Failure

Verify the instrument process is within the

 

 

 

 

 

Sensor range and / or confirm sensor

 

 

 

configuration and wiring.

 

 

Secondary Value

Verify the ambient temperature is within

 

 

Failure

operating limits

NOTE

When the engineering units of the XD_SCALE are selected, the engineering units in the Transducer Block change to the same units. THIS IS THE ONLY WAY TO CHANGE THE ENGINEERING UNITS IN THE SENSOR TRANSDUCER BLOCK.

Damping

Analog Input (AI) Function Block

The damping parameter in the Transducer Block may be used to filter measurement noise. By increasing the damping time, the transmitter will have a slower response time, but will decrease the amount of process noise that is translated to the Transducer Block Primary Value. Because both the LCD and AI Block get input from the Transducer Block, adjusting the damping parameter will effect both blocks.

NOTE

The AI Block has it's own filtering parameter called PV_FTIME. For simplicity, it is better to do filtering in the Transducer Block as damping will be applied to primary value on every sensor update. If filtering is done in AI block, damping will be applied to output every macrocycle. The LCD will display value from Transducer block.

Configure the AI block

A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section.

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The 644 measures both sensor temperature (channel 1) and terminal temperature (channel 2).

3-9

Image 31
Contents 00809-0400-4728, Rev AA June Reference ManualPage Table of Contents TOC-2 Specifications Reference DataAppendix a Appendix BCustomer Central National Response Center International Rosemount Temperature TransmittersPage Process leaks could result in death or serious injury Safety MessagesSection Introduction Explosions could result in death or serious injuryManual OverviewTransmitter Considerations Above 22 20 815 C 1500 F Oven Temperature250 C 482 F Oven Temperature 5 6 7 8 Extension Length ExampleSection Installation Bench Calibration? Within Specifications? Refer to ConfigurationSimulate Sensor Input Rail asymmetric From draining into the transmitter housingMounting Mounting a 644H to a DIN RailTypical European Installation InstallationHead Mount Transmitter with DIN Plate Style Sensor Head Mount Transmitter with Threaded Sensor Typical North American InstallationInstalling the LCD Display LCD Display InstallationPower terminals does not drop below 9 Vdc WiringThermocouple or Millivolt Inputs Sensor ConnectionsSensor Input Approximate Basic Error Sensor Lead Wire Resistance Effect- RTD InputRTD or Ohm Inputs Error due to amb. temp. var. of ± 25 C Pt100 2-wire RTDUngrounded Thermocouple, mV, and RTD/Ohm Inputs Power SupplyFoundation fieldbus Installation Ground the TransmitterGrounded Thermocouple Inputs Overview Safety Messages Section ConfigurationAuto General Block InformationDevice Description Node Address ModesResource Transducer Analog Input Other Link Active Scheduler Block InstallationFoundation Fieldbus Function Blocks CapabilitiesReports FeaturesResource Block UnicodePlantWeb Alerts FeaturesselFailedalarms MaxnotifyFailedmask MaintalarmsRecommended Actions for PlantWeb Alerts Advisory AlarmsRecommendedaction Damping Configure the AI blockSensor Transducer Block Analog Input AI Function BlockLtype Pressure Channel Temperature ChannelXdscale and Outscale Transducer Block Configuration ExamplesFiltering Process AlarmsOutd AlarmtypePARAMINDEX#1 LCD Transducer BlockDisplayparamsel BLKTYPE#1CUSTOMUNITS#1 Operation and MaintenanceOverview UNITSTYPE#1Troubleshooting guide Troubleshooting GuidesProblems with communications flowchart Calpointlo + Calminspan Sensor Transducer Block Xderr messages DiagnosticsRecall Factory Trim Block Blockerr messagesCalibrationerr DescriptionSimulate Manual ModeStatus Simulation00809-0400-4728, Rev AA June AI Blockerr Conditions Troubleshooting AI blockPower Up Symptom Possible Causes Recommended ActionsCondition Name Block Errors8lists conditions reported in the Blockerr parameter 10. Resource BlockSymptom Possible Causes Recommended Action Self Test Procedure for the LCDAuto Specifications Appendix a Specifications Reference DataFunctionalInputs Physical Performance 2 σ -1 σ Foundation Fieldbus SpecificationsRosemount Conformance to Specifications Function BlocksSoftware Upgrade in the Field Power SupplyAlarms Backup Link Active Scheduler LASTable A-1. Rosemount 644 Input Options and Accuracy AccuracyAccuracy Example Table A-2. Ambient Temperature Effect Ambient Temperature EffectThermocouples Temperature Effects Examples 644H DIN a Head Mount Dimensional DrawingsJune LCD DisplayMounting 00809-0400-4728, Rev AALCD Display Cover Sanitary Housing CoversRing 76.2 27.9 74.4 25.4 44.5 70.0 Options Ordering InformationEnclosure Options Standard Configuration StandardAlarm Level Configuration Standard Assemble To Options StandardConsiderations TaggingConfiguration tool Transmitter ConfigurationWith DeltaV, with AMS, or other Foundation fieldbus host or Standard Block Configuration Standard Foundation fieldbus ConfigurationCustom Configuration Requirements Option Code SpecificationAppendix B Product Certifications CE Electromagnetic Compatibility Compliance TestingAtex Directive 94/9/EC North American Certifications Hazardous Locations CertificatesRosemount 644 with Foundation fieldbus Special Conditions for Safe Use Loop/Power TerminalsFisco Loop/Power Terminals European CertificationsFisco Group IIC To 80 C Temperature ClassIECEx Certifications To 60 CSchedule of Limitations Table B-3. Entity ParametersTransmitter I.S Transmitter Fisco Sensor Transmitter SensorDescription Group Code Ukraine GostPattern Approval for Measuring Instruments See Certificate Approval TempInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Appendix C Foundation fieldbus Block Information Basic Setup Resource BlockDefinition Index Parameters and DescriptionsMaintenable FailedenableFeatures Featuresel00809-0400-4728, Rev AA Parameters Descriptions Sensor Transducer BlockDescription Effects transmitter operation Calvandusencoeff PrimaryvaluerangePrimaryvaluetype SensrdetailedstatusTransducertype XderrorSESNOR1DAMPING TransducerdirectoryConvert Calc Analog Measurement AccessAnalog Input AI Function Block Outd Cutoff FilterAckoption AI Parameter TableLolopri Table C-4. LCD Transducer Block Parameters and Descriptions LCD Transducer BlockParameter Index Description Table C-5. PID Block Parameters and Descriptions PID BlockParameter Index Index DIN Rail Threaded Sensor Ungrounded Wiring MODEBLK.TARGETBad Uncertain Lolim Lololim Lolopri Lopri Lower Trim MethodDirect Zero Trim Limited Man Mode Unicode UNITSTYPE# Upper Trim MethodGrounded Ungrounded Wiring Security Self TestIndex-4 Page Emerson Process Management Rosemount Inc Temperature GmbH Pacific Private Limited