Analog Input (AI) Function Block

Status

Along with the measured or calculated PV value, every FOUNDATION fieldbus block passes an additional parameter called STATUS. The PV and STATUS are passed from the Transducer Block to the Analog Input Block. The STATUS can be one of the following: GOOD, BAD, or UNCERTAIN. When there are no problems detected by the self-diagnostics of the block, the STATUS will be GOOD. If a problem occurs with the hardware in the device or the quality of the process variable is compromised for some reason, the STATUS will become either BAD or UNCERTAIN depending upon the nature of the problem. It is important that the Control Strategy that makes use of the Analog Input Block is configured to monitor the STATUS and take action where appropriate when the STATUS is no longer GOOD.

Simulation

Simulate replaces the channel value coming from the Sensor Transducer Block. For testing purposes, it is possible to manually drive the output of the

Analog Input Block to a desired value. There are two ways to do this.

Manual Mode

To change only the OUT_VALUE and not the OUT_STATUS of the AI Block, place the TARGET MODE of the block to MANUAL. Then, change the OUT_VALUE to the desired value.

Simulate

1.If the SIMULATE switch is in the OFF position, move it to the ON position. If the SIMULATE jumper is already in the ON position, you must move it to off and place it back in the ON position.

NOTE

As a safety measure, the switch must be reset every time power is interrupted to the device in order to enable SIMULATE. This prevents a device that is tested on the bench from getting installed in the process with SIMULATE still active.

2.To change both the OUT_VALUE and OUT_STATUS of the AI Block, set the TARGET MODE to AUTO.

3.Set SIMULATE_ENABLE_DISABLE to ‘Active.’

4.Enter the desired SIMULATE_VALUE to change the OUT_VALUE and SIMULATE_STATUS_QUALITY to change the OUT_STATUS. If errors occur when performing the above steps, be sure that the SIMULATE jumper has been reset after powering up the device.

3-21

Image 43
Contents 00809-0400-4728, Rev AA June Reference ManualPage Table of Contents TOC-2 Specifications Reference DataAppendix a Appendix BCustomer Central National Response Center International Rosemount Temperature TransmittersPage Process leaks could result in death or serious injury Safety MessagesSection Introduction Explosions could result in death or serious injuryManual OverviewTransmitter Considerations Above 22 20 815 C 1500 F Oven Temperature250 C 482 F Oven Temperature 5 6 7 8 Extension Length ExampleSection Installation Bench Calibration? Within Specifications? Refer to ConfigurationSimulate Sensor Input Rail asymmetric From draining into the transmitter housingMounting Mounting a 644H to a DIN RailTypical European Installation InstallationHead Mount Transmitter with DIN Plate Style Sensor Head Mount Transmitter with Threaded Sensor Typical North American InstallationInstalling the LCD Display LCD Display InstallationPower terminals does not drop below 9 Vdc WiringThermocouple or Millivolt Inputs Sensor ConnectionsSensor Input Approximate Basic Error Sensor Lead Wire Resistance Effect- RTD InputRTD or Ohm Inputs Error due to amb. temp. var. of ± 25 C Pt100 2-wire RTDUngrounded Thermocouple, mV, and RTD/Ohm Inputs Power SupplyFoundation fieldbus Installation Ground the TransmitterGrounded Thermocouple Inputs Overview Safety Messages Section ConfigurationAuto General Block InformationDevice Description Node Address ModesResource Transducer Analog Input Other Link Active Scheduler Block InstallationFoundation Fieldbus Function Blocks CapabilitiesReports FeaturesResource Block UnicodePlantWeb Alerts FeaturesselFailedalarms MaxnotifyFailedmask MaintalarmsRecommended Actions for PlantWeb Alerts Advisory AlarmsRecommendedaction Damping Configure the AI blockSensor Transducer Block Analog Input AI Function BlockLtype Pressure Channel Temperature ChannelXdscale and Outscale Transducer Block Configuration ExamplesFiltering Process AlarmsOutd AlarmtypePARAMINDEX#1 LCD Transducer BlockDisplayparamsel BLKTYPE#1CUSTOMUNITS#1 Operation and MaintenanceOverview UNITSTYPE#1Troubleshooting guide Troubleshooting GuidesProblems with communications flowchart Calpointlo + Calminspan Sensor Transducer Block Xderr messages DiagnosticsRecall Factory Trim Block Blockerr messagesCalibrationerr DescriptionSimulate Manual ModeStatus Simulation00809-0400-4728, Rev AA June AI Blockerr Conditions Troubleshooting AI blockPower Up Symptom Possible Causes Recommended ActionsCondition Name Block Errors8lists conditions reported in the Blockerr parameter 10. Resource BlockSymptom Possible Causes Recommended Action Self Test Procedure for the LCDAuto Specifications Appendix a Specifications Reference DataFunctionalInputs Physical Performance 2 σ -1 σ Foundation Fieldbus SpecificationsRosemount Conformance to Specifications Function BlocksSoftware Upgrade in the Field Power SupplyAlarms Backup Link Active Scheduler LASTable A-1. Rosemount 644 Input Options and Accuracy AccuracyAccuracy Example Table A-2. Ambient Temperature Effect Ambient Temperature EffectThermocouples Temperature Effects Examples 644H DIN a Head Mount Dimensional DrawingsJune LCD DisplayMounting 00809-0400-4728, Rev AALCD Display Cover Sanitary Housing CoversRing 76.2 27.9 74.4 25.4 44.5 70.0 Options Ordering InformationEnclosure Options Standard Configuration StandardAlarm Level Configuration Standard Assemble To Options StandardConsiderations TaggingConfiguration tool Transmitter ConfigurationWith DeltaV, with AMS, or other Foundation fieldbus host or Standard Block Configuration Standard Foundation fieldbus ConfigurationCustom Configuration Requirements Option Code SpecificationAppendix B Product Certifications CE Electromagnetic Compatibility Compliance TestingAtex Directive 94/9/EC North American Certifications Hazardous Locations CertificatesRosemount 644 with Foundation fieldbus Special Conditions for Safe Use Loop/Power TerminalsFisco Loop/Power Terminals European CertificationsFisco Group IIC To 80 C Temperature ClassIECEx Certifications To 60 CSchedule of Limitations Table B-3. Entity ParametersTransmitter I.S Transmitter Fisco Sensor Transmitter SensorDescription Group Code Ukraine GostPattern Approval for Measuring Instruments See Certificate Approval TempInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Appendix C Foundation fieldbus Block Information Basic Setup Resource BlockDefinition Index Parameters and DescriptionsMaintenable FailedenableFeatures Featuresel00809-0400-4728, Rev AA Parameters Descriptions Sensor Transducer BlockDescription Effects transmitter operation Calvandusencoeff PrimaryvaluerangePrimaryvaluetype SensrdetailedstatusTransducertype XderrorSESNOR1DAMPING TransducerdirectoryConvert Calc Analog Measurement AccessAnalog Input AI Function Block Outd Cutoff FilterAckoption AI Parameter TableLolopri Table C-4. LCD Transducer Block Parameters and Descriptions LCD Transducer BlockParameter Index Description Table C-5. PID Block Parameters and Descriptions PID BlockParameter Index Index DIN Rail Threaded Sensor Ungrounded Wiring MODEBLK.TARGETBad Uncertain Lolim Lololim Lolopri Lopri Lower Trim MethodDirect Zero Trim Limited Man Mode Unicode UNITSTYPE# Upper Trim MethodGrounded Ungrounded Wiring Security Self TestIndex-4 Page Emerson Process Management Rosemount Inc Temperature GmbH Pacific Private Limited