Emerson 644 manual Hazardous Locations Certificates, North American Certifications

Page 64

Rosemount 644

Reference Manual

00809-0100-4728, Rev AA June 2011

HAZARDOUS LOCATIONS CERTIFICATES

Rosemount 644 with FOUNDATION fieldbus

North American Certifications

Factory Mutual (FM) Approvals

I5 FM Intrinsically Safe and Non-incendive

Intrinsically Safe FISCO for use in Class I, II, III, Division 1, Groups A, B, C, D, E, F, and G; when installed per control drawing 00644-2075. Temperature Code: T4A (Tamb = – 50 °C to 60 °C).

Nonincendive for use in Class I, Division 2, Groups A, B, C, and D. Temperature Code: T5 (Tamb = – 50 °C to 85 °C);

T6 (Tamb = – 50 °C to 70 °C)

When installed per Rosemount control drawing 00644-2075

E5 FM Explosion Proof

Explosion Proof for Class I, Division 1, Groups B, C, and D. Nonincendive for use in Class 1, Division 2, Groups A, B, C, and D.

Temperature Code: T5 (Tamb = – 50 °C to 85 °C)

When installed per Rosemount control drawing 00644-1049

Dust Ignition Proof for Class II/III, Division 1, Groups E, F, G. Temperature Code: T5 (Ta = – 50 °C to 85 °C)

When installed per Rosemount drawing 00644-1049. (J5, J6 and J8 options only.)

Canadian Standards Association (CSA) Approvals

I6 CSA Intrinsically Safe

Intrinsically Safe and FISCO for Class I, Division 1, groups A, B, C, and D when connected per Rosemount drawing 00644-2076.

Temperature code: T4 (Tamb = – 50 °C to 60 °C);

Suitable for Class I, Division 2, groups A, B, C, and D (must be installed in a suitable enclosure)

K6 CSA Intrinsically Safe, Explosion-proof

Includes Intrinsically Safe “I6” and Explosion-Proof for Class I, Division 1, groups B, C, and D.

Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G. Dust-Ignition Proof for Class III, Division 1

Seal not required.

CSA Enclosure Type 4X

Temperature Code: T4 (Tamb = – 50 °C to 60 °C);

T5 (Tamb = – 50 °C to 85 °C)

NOTE:

(For J5 and J6 enclosure options only)

B-2

Image 64
Contents Reference Manual 00809-0400-4728, Rev AA JunePage Table of Contents Specifications Reference Data Appendix aAppendix B TOC-2Rosemount Temperature Transmitters Customer Central National Response Center InternationalPage Safety Messages Section IntroductionExplosions could result in death or serious injury Process leaks could result in death or serious injuryManual OverviewTransmitter Considerations 22 20 815 C 1500 F Oven Temperature 250 C 482 F Oven Temperature 5 6 7 8 Extension LengthExample AboveSection Installation Bench Calibration? Within Specifications? Refer to ConfigurationSimulate Sensor Input From draining into the transmitter housing MountingMounting a 644H to a DIN Rail Rail asymmetricTypical European Installation InstallationHead Mount Transmitter with DIN Plate Style Sensor Typical North American Installation Head Mount Transmitter with Threaded SensorLCD Display Installation Installing the LCD DisplayWiring Power terminals does not drop below 9 VdcSensor Connections Thermocouple or Millivolt InputsSensor Input Approximate Basic Error Sensor Lead Wire Resistance Effect- RTD InputRTD or Ohm Inputs Pt100 2-wire RTD Error due to amb. temp. var. of ± 25 CPower Supply Foundation fieldbus InstallationGround the Transmitter Ungrounded Thermocouple, mV, and RTD/Ohm InputsGrounded Thermocouple Inputs Section Configuration Overview Safety MessagesGeneral Block Information Device Description Node AddressModes AutoLink Active Scheduler Block Installation Resource Transducer Analog Input OtherCapabilities Foundation Fieldbus Function BlocksFeatures Resource BlockUnicode ReportsFeaturessel FailedalarmsMaxnotify PlantWeb AlertsMaintalarms FailedmaskRecommended Actions for PlantWeb Alerts Advisory AlarmsRecommendedaction Configure the AI block Sensor Transducer BlockAnalog Input AI Function Block DampingLtype Pressure Channel Temperature ChannelXdscale and Outscale Configuration Examples Transducer BlockProcess Alarms FilteringAlarmtype OutdLCD Transducer Block DisplayparamselBLKTYPE#1 PARAMINDEX#1Operation and Maintenance OverviewUNITSTYPE#1 CUSTOMUNITS#1Troubleshooting Guides Troubleshooting guideProblems with communications flowchart Calpointlo + Calminspan Diagnostics Recall Factory TrimBlock Blockerr messages Sensor Transducer Block Xderr messagesDescription CalibrationerrManual Mode StatusSimulation SimulateTroubleshooting AI block Power UpSymptom Possible Causes Recommended Actions 00809-0400-4728, Rev AA June AI Blockerr ConditionsBlock Errors 8lists conditions reported in the Blockerr parameter10. Resource Block Condition NameSymptom Possible Causes Recommended Action Self Test Procedure for the LCDAuto Specifications Appendix a Specifications Reference DataFunctionalInputs Physical Performance Foundation Fieldbus Specifications Rosemount Conformance to SpecificationsFunction Blocks 2 σ -1 σPower Supply AlarmsBackup Link Active Scheduler LAS Software Upgrade in the FieldTable A-1. Rosemount 644 Input Options and Accuracy AccuracyAccuracy Example Table A-2. Ambient Temperature Effect Ambient Temperature EffectThermocouples Temperature Effects Examples Dimensional Drawings 644H DIN a Head MountLCD Display Mounting00809-0400-4728, Rev AA JuneLCD Display Cover Sanitary Housing CoversRing 76.2 27.9 74.4 25.4 44.5 70.0 Ordering Information OptionsConfiguration Standard Alarm Level Configuration StandardAssemble To Options Standard Enclosure Options StandardTagging ConsiderationsConfiguration tool Transmitter ConfigurationWith DeltaV, with AMS, or other Foundation fieldbus host or Standard Foundation fieldbus Configuration Custom ConfigurationRequirements Option Code Specification Standard Block ConfigurationAppendix B Product Certifications CE Electromagnetic Compatibility Compliance TestingAtex Directive 94/9/EC North American Certifications Hazardous Locations CertificatesRosemount 644 with Foundation fieldbus Loop/Power Terminals Fisco Loop/Power TerminalsEuropean Certifications Special Conditions for Safe UseTemperature Class IECEx CertificationsTo 60 C Fisco Group IIC To 80 CTable B-3. Entity Parameters Transmitter I.S Transmitter Fisco SensorTransmitter Sensor Schedule of LimitationsUkraine Gost Pattern Approval for Measuring Instruments See CertificateApproval Temp Description Group CodeInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Appendix C Foundation fieldbus Block Information Basic Setup Resource BlockDefinition Parameters and Descriptions IndexFailedenable FeaturesFeaturesel Maintenable00809-0400-4728, Rev AA Parameters Descriptions Sensor Transducer BlockDescription Effects transmitter operation Primaryvaluerange PrimaryvaluetypeSensrdetailedstatus CalvandusencoeffXderror SESNOR1DAMPINGTransducerdirectory TransducertypeAnalog Measurement Access Analog Input AI Function BlockOutd Cutoff Filter Convert CalcAI Parameter Table AckoptionLolopri Table C-4. LCD Transducer Block Parameters and Descriptions LCD Transducer BlockParameter Index Description Table C-5. PID Block Parameters and Descriptions PID BlockParameter Index Index Ungrounded Wiring MODEBLK.TARGET Bad UncertainLolim Lololim Lolopri Lopri Lower Trim Method DIN Rail Threaded SensorLimited Man Mode Unicode UNITSTYPE# Upper Trim Method Grounded Ungrounded WiringSecurity Self Test Direct Zero TrimIndex-4 Page Temperature GmbH Pacific Private Limited Emerson Process Management Rosemount Inc