Reference Manual
00809-0400-4728, Rev AA June 2011
Rosemount 644
LCD TRANSDUCER
BLOCK
Table C-4. LCD Transducer Block Parameters and Descriptions
Parameter | Index | Description |
ALERT_KEY | 4 | The identification number of the plant unit. |
BLK_TAG_1 | 15 | The tag of the block containing DP1. |
BLK_TAG_2 | 21 | The tag of the block containing DP2. |
BLK_TAG_3 | 27 | The tag of the block containing DP3. |
BLK_TAG_4 | 33 | The tag of the block containing DP4. |
BLK_TYPE_1 | 14 | The enumerated block type for DP1's block. |
BLK_TYPE_2 | 20 | The enumerated block type for DP2's block. |
BLK_TYPE_3 | 26 | The enumerated block type for DP3's block. |
BLK_TYPE_4 | 32 | The enumerated block type for DP4's block. |
BLOCK_ALM | 8 | The BLOCK_ALM is used for all configuration, hardware, connection failure or system problems |
|
| in the block. The cause of the alert is entered in the subcode field. The first alert to become active |
|
| will set the Active status in the Status attribute. As soon as the Unreported status is cleared by the |
|
| alert reporting task, another block alert may be reported without clearing the Active status, if the |
|
| subcode has changed. |
BLOCK_ERR | 6 | This parameter reflects the error status associated with the hardware or software components |
|
| associated with a block. it is a bit string, so that multiple errors may be shown. |
COLLECTION_DIRECTORY | 12 | A directory that specifies the number, starting indicies, and DD Item ID's of the data collections in |
|
| each transducer block. |
CUSTOM_TAG_1 | 17 | The block description that is displayed for DP1. |
CUSTOM_TAG _2 | 23 | The block description that is displayed for DP2. |
CUSTOM_TAG _3 | 29 | The block description that is displayed for DP3. |
CUSTOM_TAG _4 | 35 | The block description that is displayed for DP4. |
CUSTOM_UNITS_1 | 19 | This is the user entered units that are displayed when UNITS_TYPE_1=Custom. |
CUSTOM_UNITS _2 | 25 | This is the user entered units that are displayed when UNITS_TYPE_2=Custom. |
CUSTOM_UNITS _3 | 31 | This is the user entered units that are displayed when UNITS_TYPE_3=Custom. |
CUSTOM_UNITS _4 | 37 | This is the user entered units that are displayed when UNITS_TYPE_4=Custom. |
DISPLAY_PARAM_SEL | 13 | This will determine which Display Parameters are active. |
|
| Bit 0 = DP1 |
|
| Bit 1 = DP2 |
|
| Bit 2 = DP3 |
|
| Bit 3 = DP4 |
|
| Bit 4 = Bar Graph enable |
MODE_BLK | 5 | The actual, target, permitted, and normal modes of the block. |
PARAM_INDEX_1 | 16 | The relative index of DP1 within its block. |
PARAM_INDEX_2 | 22 | The relative index of DP2 within its block. |
PARAM_INDEX_3 | 28 | The relative index of DP3 within its block. |
PARAM_INDEX_4 | 34 | The relative index of DP4 within its block. |
ST_REV | 1 | The revision level of the static data associated with the function block. |
STRATEGY | 3 | The strategy field can be used to identify grouping of blocks. |
TAG_DESC | 2 | The user description of the intended application of the block. |
TRANSDUCER_DIRCTORY | 9 | A directory that specifies the number and starting indicies of the transducers in the transducer |
|
| block. |
TRANSDUCER_TYPE | 10 | Identifies the transducer that follows. |
UNITS_TYPE_1 | 18 | This parameter determines where the units for the display parameter come from. |
UNITS_TYPE_2 | 24 | This parameter determines where the units for the display parameter come from. |
UNITS_TYPE_3 | 30 | This parameter determines where the units for the display parameter come from. |
UNITS_TYPE_4 | 36 | This parameter determines where the units for the display parameter come from. |
UPDATE_EVT | 7 | This alert is generated by any change to the staic data. |
XD_ERROR | 11 | Provides additional error codes related to transducer blocks. |