Emerson 644 Primaryvaluerange, Primaryvaluetype, Sensrdetailedstatus, Calvandusencoeff, Sensorsn

Page 86

 

Reference Manual

Rosemount 644

00809-0400-4728, Rev AA

June 2011

Table C-2. Sensor Transducer Block Parameters and Descriptions

 

Index

 

 

Notes on how changing this parameter

Parameter

Number

Description

effects transmitter operation.

PRIMARY_VALUE_RANGE

15

The high and low range limit values, the

No effect.

 

 

engineering unit code, and the number of digits

 

 

 

to the right of the decimal point to be used to

 

 

 

display the final value.

 

 

 

Valid engineering units are the following:

 

 

 

1130

= Pa

 

 

 

1133

= kPa

 

 

 

1137

= bar

 

 

 

1138

= mbar

 

 

 

1139

= torr

 

 

 

1140

= atm

 

 

 

1141

= psi

 

 

 

1144

= g/cm2

 

 

 

1145

= kg/cm2

 

 

 

1148

= inH2O @ 68 °F

 

 

 

1151

= mmH2O @ 68 °F

 

 

 

1154

= ftH2O @ 68 °F

 

 

 

1156

= inHg @ 0 °C

 

 

 

1158

= mmHg @ 0 °C

 

PRIMARY_VALUE_TYPE

13

Type of measurement represented by the

No effect.

 

 

primary value.

 

 

 

107 = Differential pressure

 

 

 

108 = Gage pressure

 

 

 

109 = Absolute pressure

 

SENSR_DETAILED_STATUS

37

Indicates the number of remote seals that are

 

 

 

attached to the device. See Remote Seal

 

 

 

Number Codes.

 

CAL_VAN_DUSEN_COEFF

38

Indicates the type of remote seals that are

 

 

 

attached to the device. See Remote Seal Type

 

 

 

Codes.

 

SECONDARY_VALUE_RANG

30

The secondary value, related to the sensor.

No effect.

SECONDARY_VALUE_UNIT

29

Engineering units to be used with

No effect.

 

 

SECONDARY_VALUE.

 

 

 

1001 °C

 

 

 

1002 °F

 

SENSOR_CAL_DATE

25

The last date on which the calibration was

No effect.

 

 

performed.This is intended to reflect the

 

 

 

calibration of that part of the sensor that is

 

 

 

usually wetted by the process.

 

SENSOR_CAL_LOC

24

The last location of the sensor calibration. This

No effect.

 

 

describes the physical location at which the

 

 

 

calibration was performed.

 

SENSOR_CAL_METHOD

23

The method of last sensor calibration.

No effect.

OPEN_SNSR_HOLDOFF

34

The type of last sensor calibration.

No effect.

SENSOR_CAL_WHO

26

The name of the person responsible for the last

No effect.

 

 

sensor calibration.

 

SECONDARY_VALUE

28

Defines the type of fill fluid used in the sensor.

No effect.

SENSOR_CONNECTION

27

Defines the construction material of the isolating

No effect.

 

 

diaphragms.

 

SENSOR_RANGE

21

The high and low range limit values, the

No effect.

 

 

engineering units code, and the number of digits

 

 

 

to the right of the decimal point for the sensor.

 

SENSOR_SN

22

Serial number of the sensor.

No effect.

SENSOR_TYPE

20

Type of sensor connected with the transducer

No effect.

 

 

block.

 

ST_REV

01

The revision level of the static data associated

No effect.

 

 

with the function block.

 

C-6

Image 86
Contents Reference Manual 00809-0400-4728, Rev AA JunePage Table of Contents Appendix B Specifications Reference DataAppendix a TOC-2Rosemount Temperature Transmitters Customer Central National Response Center InternationalPage Explosions could result in death or serious injury Safety MessagesSection Introduction Process leaks could result in death or serious injuryTransmitter OverviewManual Considerations Example 22 20 815 C 1500 F Oven Temperature250 C 482 F Oven Temperature 5 6 7 8 Extension Length AboveSection Installation Simulate Sensor Input Within Specifications? Refer to ConfigurationBench Calibration? Mounting a 644H to a DIN Rail From draining into the transmitter housingMounting Rail asymmetricHead Mount Transmitter with DIN Plate Style Sensor InstallationTypical European Installation Typical North American Installation Head Mount Transmitter with Threaded SensorLCD Display Installation Installing the LCD DisplayWiring Power terminals does not drop below 9 VdcSensor Connections Thermocouple or Millivolt InputsRTD or Ohm Inputs Sensor Lead Wire Resistance Effect- RTD InputSensor Input Approximate Basic Error Pt100 2-wire RTD Error due to amb. temp. var. of ± 25 CGround the Transmitter Power SupplyFoundation fieldbus Installation Ungrounded Thermocouple, mV, and RTD/Ohm InputsGrounded Thermocouple Inputs Section Configuration Overview Safety MessagesModes General Block InformationDevice Description Node Address AutoLink Active Scheduler Block Installation Resource Transducer Analog Input OtherCapabilities Foundation Fieldbus Function BlocksUnicode FeaturesResource Block ReportsMaxnotify FeaturesselFailedalarms PlantWeb AlertsMaintalarms FailedmaskRecommendedaction Advisory AlarmsRecommended Actions for PlantWeb Alerts Analog Input AI Function Block Configure the AI blockSensor Transducer Block DampingXdscale and Outscale Pressure Channel Temperature ChannelLtype Configuration Examples Transducer BlockProcess Alarms FilteringAlarmtype OutdBLKTYPE#1 LCD Transducer BlockDisplayparamsel PARAMINDEX#1UNITSTYPE#1 Operation and MaintenanceOverview CUSTOMUNITS#1Troubleshooting Guides Troubleshooting guideProblems with communications flowchart Calpointlo + Calminspan Block Blockerr messages DiagnosticsRecall Factory Trim Sensor Transducer Block Xderr messagesDescription CalibrationerrSimulation Manual ModeStatus SimulateSymptom Possible Causes Recommended Actions Troubleshooting AI blockPower Up 00809-0400-4728, Rev AA June AI Blockerr Conditions10. Resource Block Block Errors8lists conditions reported in the Blockerr parameter Condition NameAuto Self Test Procedure for the LCDSymptom Possible Causes Recommended Action FunctionalInputs Appendix a Specifications Reference DataSpecifications Physical Performance Function Blocks Foundation Fieldbus SpecificationsRosemount Conformance to Specifications 2 σ -1 σBackup Link Active Scheduler LAS Power SupplyAlarms Software Upgrade in the FieldAccuracy Example AccuracyTable A-1. Rosemount 644 Input Options and Accuracy Thermocouples Ambient Temperature EffectTable A-2. Ambient Temperature Effect Temperature Effects Examples Dimensional Drawings 644H DIN a Head Mount00809-0400-4728, Rev AA LCD DisplayMounting JuneRing 76.2 27.9 74.4 25.4 44.5 70.0 Sanitary Housing CoversLCD Display Cover Ordering Information OptionsAssemble To Options Standard Configuration StandardAlarm Level Configuration Standard Enclosure Options StandardTagging ConsiderationsWith DeltaV, with AMS, or other Foundation fieldbus host or Transmitter ConfigurationConfiguration tool Requirements Option Code Specification Standard Foundation fieldbus ConfigurationCustom Configuration Standard Block ConfigurationAtex Directive 94/9/EC CE Electromagnetic Compatibility Compliance TestingAppendix B Product Certifications Rosemount 644 with Foundation fieldbus Hazardous Locations CertificatesNorth American Certifications European Certifications Loop/Power TerminalsFisco Loop/Power Terminals Special Conditions for Safe UseTo 60 C Temperature ClassIECEx Certifications Fisco Group IIC To 80 CTransmitter Sensor Table B-3. Entity ParametersTransmitter I.S Transmitter Fisco Sensor Schedule of LimitationsApproval Temp Ukraine GostPattern Approval for Measuring Instruments See Certificate Description Group CodeInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Definition Basic Setup Resource BlockAppendix C Foundation fieldbus Block Information Parameters and Descriptions IndexFeaturesel FailedenableFeatures Maintenable00809-0400-4728, Rev AA Description Effects transmitter operation Sensor Transducer BlockParameters Descriptions Sensrdetailedstatus PrimaryvaluerangePrimaryvaluetype CalvandusencoeffTransducerdirectory XderrorSESNOR1DAMPING TransducertypeOutd Cutoff Filter Analog Measurement AccessAnalog Input AI Function Block Convert CalcAI Parameter Table AckoptionLolopri Parameter Index Description LCD Transducer BlockTable C-4. LCD Transducer Block Parameters and Descriptions Parameter Index PID BlockTable C-5. PID Block Parameters and Descriptions Index Lolim Lololim Lolopri Lopri Lower Trim Method Ungrounded Wiring MODEBLK.TARGETBad Uncertain DIN Rail Threaded SensorSecurity Self Test Limited Man Mode Unicode UNITSTYPE# Upper Trim MethodGrounded Ungrounded Wiring Direct Zero TrimIndex-4 Page Temperature GmbH Pacific Private Limited Emerson Process Management Rosemount Inc