Emerson 644 manual Security Self Test, Limited Man Mode Unicode UNITSTYPE# Upper Trim Method

Page 95

Reference Manual

00809-0100-4728, Rev KA June 2011

Rosemount 644

R

Recommended Actions . . . . . . . . 3-8PlantWeb Alarms . . . . . . . . . . 3-8RECOMMENDED_ACTION . . . . 3-8Reference data . . . . . . . . . . . . . A-8Reports . . . . . . . . . . . . . . . . . . . 3-5Resource Block . . . . 3-4,3-23,C-1Block Errors . . . . . . . . . . . . . 3-23Block Information . . . . . . . . . .C-1Configuration . . . . . . . . . . . . . 3-4Detailed Status . . . . . . . . . . . 3-23FEATURES, FEATURES_SEL 3-5Parameters . . . . . . . . . . . . . .C-2BLOCK_ERR . . . . . . . . . . 3-23Summary Status . . . . . . . . . . 3-23Resource block . . . . . . . . . . . . .C-1Return of Materials . . . . . . . . . . . 1-4

RTD

Ungrounded . . . . . . . . . . . . . 2-11Wiring . . . . . . . . . . . . . . . . . . 2-9

S

Security . . . . . . . . . . . . . . . . . . 3-5

Self Test . . . . . . . . . . . . . . . . . 3-24

Sensor

Connection

Diagram . . . . . . . . . . . . . . 2-8

Millivolt . . . . . . . . . . . . . . . . . 2-8

Ohm . . . . . . . . . . . . . . . . . . . 2-9

RTD . . . . . . . . . . . . . . . . . . . 2-9

Thermocouple . . . . . . . . . . . . 2-8

Wiring . . . . . . . . . . . . . . . . . . 2-8

Sensor Calibration . . . . . . . . . . 3-18

Sensor Transducer Block . . 3-4,3-9,

3-18, . . . . . . . . . . . . . . . . . . . .C-5

Block Information . . . . . . . . . .C-5

Configuration . . . . . . . . . . . . . 3-9

Operation and Maintenance . . 3-18

Parameters . . . . . . . . . . . . . .C-5

Simulate . . . . . . . . . . . . . . . . . 3-21

Simulation . . . . . . . . . . . . . . . . 3-21

Manual Mode . . . . . . . . . . . . 3-21

Soft W Lock, Hard W Lock . . . . . 3-5

Specifications

Performance . . . . . . . . . . . . . A-3

Status . . . . . . . . . . . . . . . . . . . 3-21

AI block . . . . . . . . . . . . . . . . 3-13

STATUS_OPTIONS . . . . . . . . . 3-13

Supported Units . . . . . . . . . . . . 3-10

Switches

Simulate . . . . . . . . . . . . . . . 3-21

T

Trim

. . . . . . 3-9

Zero

Troubleshooting

. . . . . 3-16

Flowchart

. . . . . 3-16

LCD Transducer block

. . . . . 3-24

Reference table

. . . . . 3-16

Resource Block

. . . . . 3-23

Types of Modes

. . . . . . 3-2

Auto

Man

. . . . . . 3-2

Other Types of Modes

. . . . . . 3-2

Out of Service

. . . . . . 3-2

U

Uncertain

Limited . . . . . . . . . . . . . . . . 3-13

Man Mode . . . . . . . . . . . . . . 3-13

Unicode . . . . . . . . . . . . . . . . . . 3-5

UNITS_TYPE_# . . . . . . . . . . . 3-15

Upper Trim Method . . . . . . . . . 3-18

V

Virtual Communication Relationship (VCRs) . . . . . . . . . . . . . . . . . . . 3-4

Network Parameters . . . . . . . . 3-4

W

Wiring . . . . . . . . . . . . . . . . . . . 2-7

Sensor Connection . . . . . . . . 2-8

Diagram . . . . . . . . . . . . . . 2-8

Millivolt . . . . . . . . . . . . . . . 2-8

Ohm . . . . . . . . . . . . . . . . . 2-9

RTD . . . . . . . . . . . . . . . . . 2-9

Thermocouple . . . . . . . . . . 2-8

X

XD_SCALE . . . . . . . . . . . . . . . 3-9XD_SCALE, OUT_SCALE . . . . 3-10

L_TYPE

Direct . . . . . . . . . . . . . . . 3-10

Z

Zero Trim . . . . . . . . . . . . . . . . . 3-9

Index-3

Image 95
Contents 00809-0400-4728, Rev AA June Reference ManualPage Table of Contents TOC-2 Specifications Reference DataAppendix a Appendix BCustomer Central National Response Center International Rosemount Temperature TransmittersPage Process leaks could result in death or serious injury Safety MessagesSection Introduction Explosions could result in death or serious injuryTransmitter OverviewManual Considerations Above 22 20 815 C 1500 F Oven Temperature250 C 482 F Oven Temperature 5 6 7 8 Extension Length ExampleSection Installation Simulate Sensor Input Within Specifications? Refer to ConfigurationBench Calibration? Rail asymmetric From draining into the transmitter housingMounting Mounting a 644H to a DIN RailHead Mount Transmitter with DIN Plate Style Sensor InstallationTypical European Installation Head Mount Transmitter with Threaded Sensor Typical North American InstallationInstalling the LCD Display LCD Display InstallationPower terminals does not drop below 9 Vdc WiringThermocouple or Millivolt Inputs Sensor ConnectionsRTD or Ohm Inputs Sensor Lead Wire Resistance Effect- RTD InputSensor Input Approximate Basic Error Error due to amb. temp. var. of ± 25 C Pt100 2-wire RTDUngrounded Thermocouple, mV, and RTD/Ohm Inputs Power SupplyFoundation fieldbus Installation Ground the TransmitterGrounded Thermocouple Inputs Overview Safety Messages Section ConfigurationAuto General Block InformationDevice Description Node Address ModesResource Transducer Analog Input Other Link Active Scheduler Block InstallationFoundation Fieldbus Function Blocks CapabilitiesReports FeaturesResource Block UnicodePlantWeb Alerts FeaturesselFailedalarms MaxnotifyFailedmask MaintalarmsRecommendedaction Advisory AlarmsRecommended Actions for PlantWeb Alerts Damping Configure the AI blockSensor Transducer Block Analog Input AI Function BlockXdscale and Outscale Pressure Channel Temperature ChannelLtype Transducer Block Configuration ExamplesFiltering Process AlarmsOutd AlarmtypePARAMINDEX#1 LCD Transducer BlockDisplayparamsel BLKTYPE#1CUSTOMUNITS#1 Operation and MaintenanceOverview UNITSTYPE#1Troubleshooting guide Troubleshooting GuidesProblems with communications flowchart Calpointlo + Calminspan Sensor Transducer Block Xderr messages DiagnosticsRecall Factory Trim Block Blockerr messagesCalibrationerr DescriptionSimulate Manual ModeStatus Simulation00809-0400-4728, Rev AA June AI Blockerr Conditions Troubleshooting AI blockPower Up Symptom Possible Causes Recommended ActionsCondition Name Block Errors8lists conditions reported in the Blockerr parameter 10. Resource BlockAuto Self Test Procedure for the LCDSymptom Possible Causes Recommended Action FunctionalInputs Appendix a Specifications Reference DataSpecifications Physical Performance 2 σ -1 σ Foundation Fieldbus SpecificationsRosemount Conformance to Specifications Function BlocksSoftware Upgrade in the Field Power SupplyAlarms Backup Link Active Scheduler LASAccuracy Example AccuracyTable A-1. Rosemount 644 Input Options and Accuracy Thermocouples Ambient Temperature EffectTable A-2. Ambient Temperature Effect Temperature Effects Examples 644H DIN a Head Mount Dimensional DrawingsJune LCD DisplayMounting 00809-0400-4728, Rev AARing 76.2 27.9 74.4 25.4 44.5 70.0 Sanitary Housing CoversLCD Display Cover Options Ordering InformationEnclosure Options Standard Configuration StandardAlarm Level Configuration Standard Assemble To Options StandardConsiderations TaggingWith DeltaV, with AMS, or other Foundation fieldbus host or Transmitter ConfigurationConfiguration tool Standard Block Configuration Standard Foundation fieldbus ConfigurationCustom Configuration Requirements Option Code SpecificationAtex Directive 94/9/EC CE Electromagnetic Compatibility Compliance TestingAppendix B Product Certifications Rosemount 644 with Foundation fieldbus Hazardous Locations CertificatesNorth American Certifications Special Conditions for Safe Use Loop/Power TerminalsFisco Loop/Power Terminals European CertificationsFisco Group IIC To 80 C Temperature ClassIECEx Certifications To 60 CSchedule of Limitations Table B-3. Entity ParametersTransmitter I.S Transmitter Fisco Sensor Transmitter SensorDescription Group Code Ukraine GostPattern Approval for Measuring Instruments See Certificate Approval TempInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Definition Basic Setup Resource BlockAppendix C Foundation fieldbus Block Information Index Parameters and DescriptionsMaintenable FailedenableFeatures Featuresel00809-0400-4728, Rev AA Description Effects transmitter operation Sensor Transducer BlockParameters Descriptions Calvandusencoeff PrimaryvaluerangePrimaryvaluetype SensrdetailedstatusTransducertype XderrorSESNOR1DAMPING TransducerdirectoryConvert Calc Analog Measurement AccessAnalog Input AI Function Block Outd Cutoff FilterAckoption AI Parameter TableLolopri Parameter Index Description LCD Transducer BlockTable C-4. LCD Transducer Block Parameters and Descriptions Parameter Index PID BlockTable C-5. PID Block Parameters and Descriptions Index DIN Rail Threaded Sensor Ungrounded Wiring MODEBLK.TARGETBad Uncertain Lolim Lololim Lolopri Lopri Lower Trim MethodDirect Zero Trim Limited Man Mode Unicode UNITSTYPE# Upper Trim MethodGrounded Ungrounded Wiring Security Self TestIndex-4 Page Emerson Process Management Rosemount Inc Temperature GmbH Pacific Private Limited