Emerson 644 manual Parameters and Descriptions, Index

Page 82

Rosemount 644

Reference Manual

00809-0400-4728, Rev AA June 2011

Parameters and Descriptions

The table below lists all of the configurable parameters of the Resource Block, including the descriptions and index numbers for each.

Table C-1. Resource Block Parameters and Descriptions

 

Index

 

Parameter

Number

Description

ACK_OPTION

38

Selection of whether alarms associated with the function block will be

 

 

automatically acknowledged.

ADVISE_ACTIVE

82

Enumerated list of advisory conditions within a device.

ADVISE_ALM

83

Alarm indicating advisory alarms. These conditions do not have a direct impact on the

 

 

process or device integrity.

ADVISE_ENABLE

80

Enabled ADVISE_ALM alarm conditions. Corresponds bit for bit to the ADVISE_ACTIVE.

 

 

A bit on means that the corresponding alarm condition is enabled and will be detected. A

 

 

bit off means the corresponding alarm condition is disabled and will not be detected.

ADVISE_MASK

81

Mask of ADVISE_ALM. Corresponds bit of bit to ADVISE_ACTIVE. A bit on means that

 

 

the condition is masked out from alarming.

ADVISE_PRI

79

Designates the alarming priority of the ADVISE_ALM

ALARM_SUM

37

The current alert status, unacknowledged states, unreported states, and disabled states

 

 

of the alarms associated with the function block.

ALERT_KEY

04

The identification number of the plant unit.

BLOCK_ALM

36

The block alarm is used for all configuration, hardware, connection failure or system

 

 

problems in the block. The cause of the alert is entered in the subcode field. The first alert

 

 

to become active will set the Active status in the Status parameter. As soon as the

 

 

Unreported status is cleared by the alert reporting task, another block alert may be

 

 

reported without clearing the Active status, if the subcode has changed.

BLOCK_ERR

06

This parameter reflects the error status associated with the hardware or software

 

 

components associated with a block. It is a bit string, so that multiple errors may be

 

 

shown.

CLR_FSTATE

30

Writing a Clear to this parameter will clear the device FAIL_SAFE if the field condition has

 

 

cleared.

CONFIRM_TIME

33

The time the resource will wait for confirmation of receipt of a report before trying again.

 

 

Retry will not happen when CONFIRM_TIME=0.

CYCLE_SEL

20

Used to select the block execution method for this resource. The 644 supports the

 

 

following:

 

 

Scheduled: Blocks are only executed based on the function block schedule.

 

 

Block Execution: A block may be executed by linking to another blocks completion.

CYCLE_TYPE

19

Identifies the block execution methods available for this resource.

DD_RESOURCE

09

String identifying the tag of the resource which contains the Device Description for

 

 

this resource.

DD_REV

13

Revision of the DD associated with the resource - used by an interface device to locate

 

 

the DD file for the resource.

DEFINE_WRITE_LOCK

60

Allows the operator to select how WRITE_LOCK behaves. The initial value is “lock

 

 

everything”. If the value is set to “lock only physical device” then the resource and

 

 

transducer blocks of the device will be locked but changes to function blocks will be

 

 

allowed.

DETAILED_STATUS

55

Indicateds the state of the transmitter. See Resource Block detailed status codes.

DEV_REV

12

Manufacturer revision number associated with the resource - used by an interface device

 

 

to locate the DD file for the resource.

DEV_STRING

43

This is used to load new licensing into the device. The value can be written but will always

 

 

read back with a value of 0.

DEV_TYPE

11

Manufacturer’s model number associated with the resource - used by interface devices to

 

 

locate the DD file for the resource.

DIAG_OPTIONS

46

Indicates which diagnostics licensing options are enabled.

DISTRIBUTOR

42

Reserved for use as distributor ID. No Foundation enumerations defined at this time.

DOWNLOAD_MODE

67

Gives access to the boot block code for over-the-wire downloads.

 

 

0 = Uninitialized

 

 

1 = Run mode

 

 

2 = Download mode

C-2

Image 82
Contents Reference Manual 00809-0400-4728, Rev AA JunePage Table of Contents Appendix B Specifications Reference DataAppendix a TOC-2Rosemount Temperature Transmitters Customer Central National Response Center InternationalPage Explosions could result in death or serious injury Safety MessagesSection Introduction Process leaks could result in death or serious injuryManual OverviewTransmitter Considerations Example 22 20 815 C 1500 F Oven Temperature250 C 482 F Oven Temperature 5 6 7 8 Extension Length AboveSection Installation Bench Calibration? Within Specifications? Refer to ConfigurationSimulate Sensor Input Mounting a 644H to a DIN Rail From draining into the transmitter housingMounting Rail asymmetricTypical European Installation InstallationHead Mount Transmitter with DIN Plate Style Sensor Typical North American Installation Head Mount Transmitter with Threaded SensorLCD Display Installation Installing the LCD DisplayWiring Power terminals does not drop below 9 VdcSensor Connections Thermocouple or Millivolt InputsSensor Input Approximate Basic Error Sensor Lead Wire Resistance Effect- RTD InputRTD or Ohm Inputs Pt100 2-wire RTD Error due to amb. temp. var. of ± 25 CGround the Transmitter Power SupplyFoundation fieldbus Installation Ungrounded Thermocouple, mV, and RTD/Ohm InputsGrounded Thermocouple Inputs Section Configuration Overview Safety MessagesModes General Block InformationDevice Description Node Address AutoLink Active Scheduler Block Installation Resource Transducer Analog Input OtherCapabilities Foundation Fieldbus Function BlocksUnicode FeaturesResource Block ReportsMaxnotify FeaturesselFailedalarms PlantWeb AlertsMaintalarms FailedmaskRecommended Actions for PlantWeb Alerts Advisory AlarmsRecommendedaction Analog Input AI Function Block Configure the AI blockSensor Transducer Block DampingLtype Pressure Channel Temperature ChannelXdscale and Outscale Configuration Examples Transducer BlockProcess Alarms FilteringAlarmtype OutdBLKTYPE#1 LCD Transducer BlockDisplayparamsel PARAMINDEX#1UNITSTYPE#1 Operation and MaintenanceOverview CUSTOMUNITS#1Troubleshooting Guides Troubleshooting guideProblems with communications flowchart Calpointlo + Calminspan Block Blockerr messages DiagnosticsRecall Factory Trim Sensor Transducer Block Xderr messagesDescription CalibrationerrSimulation Manual ModeStatus SimulateSymptom Possible Causes Recommended Actions Troubleshooting AI blockPower Up 00809-0400-4728, Rev AA June AI Blockerr Conditions10. Resource Block Block Errors8lists conditions reported in the Blockerr parameter Condition NameSymptom Possible Causes Recommended Action Self Test Procedure for the LCDAuto Specifications Appendix a Specifications Reference DataFunctionalInputs Physical Performance Function Blocks Foundation Fieldbus SpecificationsRosemount Conformance to Specifications 2 σ -1 σBackup Link Active Scheduler LAS Power SupplyAlarms Software Upgrade in the FieldTable A-1. Rosemount 644 Input Options and Accuracy AccuracyAccuracy Example Table A-2. Ambient Temperature Effect Ambient Temperature EffectThermocouples Temperature Effects Examples Dimensional Drawings 644H DIN a Head Mount00809-0400-4728, Rev AA LCD DisplayMounting JuneLCD Display Cover Sanitary Housing CoversRing 76.2 27.9 74.4 25.4 44.5 70.0 Ordering Information OptionsAssemble To Options Standard Configuration StandardAlarm Level Configuration Standard Enclosure Options StandardTagging ConsiderationsConfiguration tool Transmitter ConfigurationWith DeltaV, with AMS, or other Foundation fieldbus host or Requirements Option Code Specification Standard Foundation fieldbus ConfigurationCustom Configuration Standard Block ConfigurationAppendix B Product Certifications CE Electromagnetic Compatibility Compliance TestingAtex Directive 94/9/EC North American Certifications Hazardous Locations CertificatesRosemount 644 with Foundation fieldbus European Certifications Loop/Power TerminalsFisco Loop/Power Terminals Special Conditions for Safe UseTo 60 C Temperature ClassIECEx Certifications Fisco Group IIC To 80 CTransmitter Sensor Table B-3. Entity ParametersTransmitter I.S Transmitter Fisco Sensor Schedule of LimitationsApproval Temp Ukraine GostPattern Approval for Measuring Instruments See Certificate Description Group CodeInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Appendix C Foundation fieldbus Block Information Basic Setup Resource BlockDefinition Parameters and Descriptions IndexFeaturesel FailedenableFeatures Maintenable00809-0400-4728, Rev AA Parameters Descriptions Sensor Transducer BlockDescription Effects transmitter operation Sensrdetailedstatus PrimaryvaluerangePrimaryvaluetype CalvandusencoeffTransducerdirectory XderrorSESNOR1DAMPING TransducertypeOutd Cutoff Filter Analog Measurement AccessAnalog Input AI Function Block Convert CalcAI Parameter Table AckoptionLolopri Table C-4. LCD Transducer Block Parameters and Descriptions LCD Transducer BlockParameter Index Description Table C-5. PID Block Parameters and Descriptions PID BlockParameter Index Index Lolim Lololim Lolopri Lopri Lower Trim Method Ungrounded Wiring MODEBLK.TARGETBad Uncertain DIN Rail Threaded SensorSecurity Self Test Limited Man Mode Unicode UNITSTYPE# Upper Trim MethodGrounded Ungrounded Wiring Direct Zero TrimIndex-4 Page Temperature GmbH Pacific Private Limited Emerson Process Management Rosemount Inc