Page 90

Rosemount 644

Reference Manual

00809-0400-4728, Rev AA June 2011

Table C-3. Definitions of Analog Input Function Block System Parameters

 

Index

 

 

 

 

 

Parameter

No.

Available Values

Units

Default

Read/Write

Description

LO_ALM

35

Not applicable

None

Not applicable

Read only

The LO alarm data, which includes a value of the

 

 

 

 

 

 

alarm, a timestamp of occurrence and the state

 

 

 

 

 

 

of the alarm.

LO_LIM

30

Out_Scale(2)

Out_Scale(2)

Not applicable

Read and Write

The setting for the alarm limit used to detect the

 

 

 

 

 

 

LO alarm condition.

LO_LO_ALM

36

Not applicable

None

Not applicable

Read only

The LO LO alarm data, which includes a value of

 

 

 

 

 

 

the alarm, a timestamp of occurrence and the

 

 

 

 

 

 

state of the alarm.

LO_LO_LIM

32

Out_Scale(2)

Out_Scale(2)

Not applicable

Read and Write

The setting for the alarm limit used to detect the

 

 

 

 

 

 

LO LO alarm condition.

LO_LO_PRI

31

0 – 15

None

1

Read and Write

The priority of the LO LO alarm.

LO_PRI

29

0 – 15

None

1

Read and Write

The priority of the LO alarm.

LOW_CUT

17

> = 0

Out_Scale(2)

0

Read and Write

If percentage value of transducer input fails

 

 

 

 

 

 

below this, PV = 0.

MODE_BLK

05

Auto

None

Not applicable

Read and Write

The actual, target, permitted, and normal modes

 

 

Manual

 

 

 

of the block.

 

 

Out of Service

 

 

 

Target: The mode to “go to”

 

 

 

 

 

 

Actual: The mode the “block is currently in”

 

 

 

 

 

 

Permitted: Allowed modes that target may take

 

 

 

 

 

 

on

 

 

 

 

 

 

Normal: Most common mode for target

OUT

08

Out_Scale(2) ± 10%

Out_Scale(2)

Not applicable

Read and Write

The block output value and status.

OUT_D

37

Discrete_State 1 – 16

None

Disabled

Read and Write

Discrete output to indicate a selected alarm

 

 

 

 

 

 

condition.

OUT_SCALE

11

Any output range

All available

none

Read and Write

The high and low scale values, engineering units

 

 

 

 

 

 

code, and number of digits to the right of the

 

 

 

 

 

 

decimal point associated with OUT.

PV

07

Not applicable

Out_Scale(2)

Not applicable

Read only

The process variable used in block execution.

PV_FTIME

18

> = 0

Seconds

0

Read and Write

The time constant of the first-order PV filter. It is

 

 

 

 

 

 

the time required for a 63% change in the IN

 

 

 

 

 

 

value.

SIMULATE

09

Not applicable

None

Disable

Read and Write

A group of data that contains the current

 

 

 

 

 

 

transducer value and status, the simulated

 

 

 

 

 

 

transducer value and status, and the

 

 

 

 

 

 

enable/disable bit.

ST_REV

01

Not applicable

None

0

Read only

The revision level of the static data associated

 

 

 

 

 

 

with the function block. The revision value will be

 

 

 

 

 

 

incremented each time a static parameter value

 

 

 

 

 

 

in the block is changed.

STATUS_OPTS

14

Propagate fault forward

 

0

Read and Write

 

 

 

Uncertain if Limited

 

 

 

 

 

 

Bad if Limited

 

 

 

 

 

 

Uncertain if Man Mode

 

 

 

 

STDDEV

39

0 – 100

Percent

0

Read and Write

The average absolute error between the PV and

 

 

 

 

 

 

its previous mean value over that evaluation time

 

 

 

 

 

 

defined by VAR_SCAN.

STRATEGY

03

0 – 65535

None

0

Read and Write

The strategy field can be used to identify

 

 

 

 

 

 

grouping of blocks. This data is not checked or

 

 

 

 

 

 

processed by the block.

TAG_DESC

02

32 text characters

None

none

Read and Write

The user description of the intended application

 

 

 

 

 

 

of the block.

UPDATE_EVT

20

Not applicable

None

Not applicable

Read only

This alert is generated by any change to the

 

 

 

 

 

 

static data.

XD_SCALE

10

Any sensor range

inH2O (68 °F)

AI1(1): Customer

 

In all Rosemount devices the units of the

 

 

 

inHg (0 °C)

specification

 

transducer block is forced to match the unit code.

 

 

 

ftH2O (68 °F)

 

 

 

 

 

 

mmH2O (68 °F)

or

 

 

 

 

 

mmHg (0 °C)

inH2O (68 °F) for

 

 

 

 

 

psi

 

 

 

 

 

bar

DP/GP rng 1, 2, 3)

 

 

 

 

 

mbar

 

 

 

 

 

 

g/cm2

or

 

 

 

 

 

kg/cm2

 

 

 

 

 

 

Pa

psi for DP/GP rng

 

 

 

 

 

kPa

4, 5 AP/644 all rng

 

 

 

 

 

torr

AI2 deg C

 

 

 

 

 

atm

 

 

 

 

 

deg C

 

 

 

 

 

 

deg F

 

 

 

(1)The host system may write over default values pre-configured by Rosemount Inc.

(2)Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale

C-10

Image 90
Contents Reference Manual 00809-0400-4728, Rev AA JunePage Table of Contents Appendix B Specifications Reference DataAppendix a TOC-2Rosemount Temperature Transmitters Customer Central National Response Center InternationalPage Explosions could result in death or serious injury Safety MessagesSection Introduction Process leaks could result in death or serious injuryOverview ManualTransmitter Considerations Example 22 20 815 C 1500 F Oven Temperature250 C 482 F Oven Temperature 5 6 7 8 Extension Length AboveSection Installation Within Specifications? Refer to Configuration Bench Calibration?Simulate Sensor Input Mounting a 644H to a DIN Rail From draining into the transmitter housingMounting Rail asymmetricInstallation Typical European InstallationHead Mount Transmitter with DIN Plate Style Sensor Typical North American Installation Head Mount Transmitter with Threaded SensorLCD Display Installation Installing the LCD DisplayWiring Power terminals does not drop below 9 VdcSensor Connections Thermocouple or Millivolt InputsSensor Lead Wire Resistance Effect- RTD Input Sensor Input Approximate Basic ErrorRTD or Ohm Inputs Pt100 2-wire RTD Error due to amb. temp. var. of ± 25 CGround the Transmitter Power SupplyFoundation fieldbus Installation Ungrounded Thermocouple, mV, and RTD/Ohm InputsGrounded Thermocouple Inputs Section Configuration Overview Safety MessagesModes General Block InformationDevice Description Node Address AutoLink Active Scheduler Block Installation Resource Transducer Analog Input OtherCapabilities Foundation Fieldbus Function BlocksUnicode FeaturesResource Block ReportsMaxnotify FeaturesselFailedalarms PlantWeb AlertsMaintalarms FailedmaskAdvisory Alarms Recommended Actions for PlantWeb AlertsRecommendedaction Analog Input AI Function Block Configure the AI blockSensor Transducer Block DampingPressure Channel Temperature Channel LtypeXdscale and Outscale Configuration Examples Transducer BlockProcess Alarms FilteringAlarmtype OutdBLKTYPE#1 LCD Transducer BlockDisplayparamsel PARAMINDEX#1UNITSTYPE#1 Operation and MaintenanceOverview CUSTOMUNITS#1Troubleshooting Guides Troubleshooting guideProblems with communications flowchart Calpointlo + Calminspan Block Blockerr messages DiagnosticsRecall Factory Trim Sensor Transducer Block Xderr messagesDescription CalibrationerrSimulation Manual ModeStatus SimulateSymptom Possible Causes Recommended Actions Troubleshooting AI blockPower Up 00809-0400-4728, Rev AA June AI Blockerr Conditions10. Resource Block Block Errors8lists conditions reported in the Blockerr parameter Condition NameSelf Test Procedure for the LCD Symptom Possible Causes Recommended ActionAuto Appendix a Specifications Reference Data SpecificationsFunctionalInputs Physical Performance Function Blocks Foundation Fieldbus SpecificationsRosemount Conformance to Specifications 2 σ -1 σBackup Link Active Scheduler LAS Power SupplyAlarms Software Upgrade in the FieldAccuracy Table A-1. Rosemount 644 Input Options and AccuracyAccuracy Example Ambient Temperature Effect Table A-2. Ambient Temperature EffectThermocouples Temperature Effects Examples Dimensional Drawings 644H DIN a Head Mount00809-0400-4728, Rev AA LCD DisplayMounting JuneSanitary Housing Covers LCD Display CoverRing 76.2 27.9 74.4 25.4 44.5 70.0 Ordering Information OptionsAssemble To Options Standard Configuration StandardAlarm Level Configuration Standard Enclosure Options StandardTagging ConsiderationsTransmitter Configuration Configuration toolWith DeltaV, with AMS, or other Foundation fieldbus host or Requirements Option Code Specification Standard Foundation fieldbus ConfigurationCustom Configuration Standard Block ConfigurationCE Electromagnetic Compatibility Compliance Testing Appendix B Product CertificationsAtex Directive 94/9/EC Hazardous Locations Certificates North American CertificationsRosemount 644 with Foundation fieldbus European Certifications Loop/Power TerminalsFisco Loop/Power Terminals Special Conditions for Safe UseTo 60 C Temperature ClassIECEx Certifications Fisco Group IIC To 80 CTransmitter Sensor Table B-3. Entity ParametersTransmitter I.S Transmitter Fisco Sensor Schedule of LimitationsApproval Temp Ukraine GostPattern Approval for Measuring Instruments See Certificate Description Group CodeInstallation Drawings Rosemount Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 00809-0100-4728, Rev AA June 00809-0100-4728, Rev AA June Sheet 2 Rosemount Rosemount 00809-0100-4728, Rev AA June Sheet 2 00809-0100-4728, Rev AA June Sheet 3 Basic Setup Resource Block Appendix C Foundation fieldbus Block InformationDefinition Parameters and Descriptions IndexFeaturesel FailedenableFeatures Maintenable00809-0400-4728, Rev AA Sensor Transducer Block Parameters DescriptionsDescription Effects transmitter operation Sensrdetailedstatus PrimaryvaluerangePrimaryvaluetype CalvandusencoeffTransducerdirectory XderrorSESNOR1DAMPING TransducertypeOutd Cutoff Filter Analog Measurement AccessAnalog Input AI Function Block Convert CalcAI Parameter Table AckoptionLolopri LCD Transducer Block Table C-4. LCD Transducer Block Parameters and DescriptionsParameter Index Description PID Block Table C-5. PID Block Parameters and DescriptionsParameter Index Index Lolim Lololim Lolopri Lopri Lower Trim Method Ungrounded Wiring MODEBLK.TARGETBad Uncertain DIN Rail Threaded SensorSecurity Self Test Limited Man Mode Unicode UNITSTYPE# Upper Trim MethodGrounded Ungrounded Wiring Direct Zero TrimIndex-4 Page Temperature GmbH Pacific Private Limited Emerson Process Management Rosemount Inc