9.Install a coupling, nipple, union and sediment trap onto the
10.Replace the left and right front panels on the heater.
Gas Supply Pressure
A minimum of 5.0 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and
When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity for the combined load.
The gas valve pressure regulator(s) on the heater are nominally preset at 3.5 in. WC for natural gas, and
10.5in. WC for propane gas. The pressure at the gas valve outlet tap, measured with a manometer, while in operation should be 3.5 ± 0.1 in. WC for natural gas and 10.5 in. ± 0.1 in. WC for propane gas. If an adjust- ment is needed, remove the adjustment screw cover and turn the adjustment screw clockwise to increase pressure or
Electrical Power Connections
Installations must follow these codes:
•National Electrical Code and any other national, state, provincial or local codes or regulations hav- ing jurisdiction.
•Safety wiring must be NEC Class 1.
•Heater must be electrically grounded as required by the NEC.
•In Canada, CSA C22. 1 C.E.C. Part 1.
The heater is wired for 120 VAC, <12 amps. The volt- age is indicated on the
Install a separate disconnect means for each load. Use appropriately sized wire as defined by NEC, CSA and/or local code. All primary wiring should be 125% of minimum rating.
If any of the original wire as supplied with the heater must be replaced, it must be replaced with 105°C wire or its equivalent.
Field-Connected Controllers
It is strongly recommended that all
NOTE:
Check the Power Source
WARNING: Using a
Fig. 17: Gas Valves
22