Category II – A heater which operates with a
Category III – A heater which operates with a positive vent pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
Category IV – A heater which operates with a positive vent pressure and with a vent gas temperature that may cause excessive condensate production in the vent.
See Table K for appliance category requirements.
NOTE: For additional information on appliance categorization, see appropriate ANSI Z21 Standard and the NFGC (U.S.), or B149 (Canada), or applicable provisions of local building codes.
CAUTION: When condensate traps are installed, condensate must be routed to an appropriate container for neutralization before disposal, as required by local codes.
WARNING: Contact the manufacturer of the vent material if there is any question about the appliance categorization and suitability of a vent material for application on a Category III or IV vent system. Using improper venting materials can result in personal injury, death or property damage.
Support of Vent Stack
The weight of the vent stack or chimney must not rest on the heater vent connection. Support must be pro- vided in compliance with applicable codes. The vent should also be installed to maintain proper clearances from combustible materials.
Use insulated vent pipe spacers where the vent pass- es through combustible roofs and walls.
NOTE: During winter months check the vent cap and make sure no blockage occurs from
Vent Terminal Location
1.Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.
2.Give special attention to the location of the vent termination to avoid possibility of property dam- age or personal injury.
3.Gases may form a white vapor plume in winter. The plume could obstruct a window view if the ter- mination is installed near windows.
4.Prevailing winds, in combination with
5.The bottom of the vent terminal and the air intake shall be located at least 12 in. above grade, includ- ing normal snow line.
6.
7.
|
|
|
|
|
|
|
|
| Combustion | Exhaust | Heater Venting | Certified | Combustion Air |
| |
| Air Supply | Configuration | Category | Materials |
| Inlet Material |
|
|
|
|
|
|
|
|
|
|
| Vertical Natural | I | “B” Vent |
|
|
|
| From Inside Building | Draft Venting |
|
|
| ||
|
|
|
|
|
| ||
| Horizontal Through- | III | Stainless Steel |
|
|
| |
|
|
|
|
| |||
|
| (Gas Tight) |
|
|
| ||
|
|
|
|
|
| ||
|
| Vertical Natural | I | “B” Vent | Galvanized Steel |
| |
| From Outside Building | Draft Venting |
| PVC |
| ||
|
|
|
|
| |||
| (Direct Venting) | Horizontal Through- | III | Stainless Steel |
| ABS |
|
|
|
| CPVC |
| |||
|
| (Gas Tight) |
|
| |||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
Table K: Venting Category Requirements
26