sheets supplied with your heater paperwork. See the General Safety Section for safety precautions con- cerning domestic hot water applications.
gas pressure switch automatically shuts down the heater if gas manifold pressure rises above the recom- mended setting of 5.0 in. WC for natural gas, and 11.5 in. WC for propane gas.
Fig. 35: Operating Control
Low Water Cut-Off (Optional)
The low water
Fig. 36: Low Water Cut-Off
High and Low Gas Pressure Switches
The low gas pressure switch (standard) connection mounts upstream of the gas valve to ensure that suffi- cient gas pressure is present for proper regulator performance. The low gas pressure switch automati- cally shuts down the heater if gas supply drops below the factory setting of 5.0 in. WC for natural gas, and 10.0 in. WC for propane gas.
The high gas pressure switch (optional) connection mounts
Fig. 37: High/Low Gas Pressure Switch
Fig. 38: Fan-Proving Switch
Fig. 39: Blocked Vent Switch
43