Generac 004700-0 Exercising The Generator, Out Of Service Procedure, Adjusting Valve Clearance

Page 17
3.10 MAJOR SERVICE MANUAL

Section 3 – Maintenance

QUIETPACT 40G Recreational Vehicle Generator

3.10 MAJOR SERVICE MANUAL

To obtain a service manual for your generator, con- tact Generac or your nearest Generac Authorized Service Dealer or, go to www.generac.com. Make sure to identify your MODEL NUMBER and SERIES.

3.11 EXERCISING THE GENERATOR

Generac recommends that you start and operate the generator at least once every seven days. Let the unit run for at least 30 minutes to “exercise” the engine.

3.12 OUT OF SERVICE PROCEDURE

3.12.1 REMOVAL FROM SERVICE

If you cannot exercise the generator every seven days, and it is to be out of service longer than 30 days, pre- pare the generator for storage as follows:

1.Start the engine and let it warm up.

2.Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.

Note:

Using a fuel additive such as STA-BIL fuel stabi- lizer, or an equivalent, will prevent gum deposits from forming in the engine’s fuel system.

3.While the engine is still warm from running, drain the oil completely. Refill the crankcase with SAE 10W-30 oil having API classification “For Service SF.”

4.Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.

5.Remove the spark plug and pour two or three tablespoons of clean, fresh engine oil into the spark plug threaded openings. Reinstall and tighten the spark plug.

6.Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.

7.Clean and wipe the entire generator.

3.12.2 RETURN TO SERVICE

To return the unit to service after storage, proceed as follows:

1.Check the tag on the engine for oil viscosity and classification. Verify that the correct recommend- ed oil is used in the engine (see Section 1.5.4, Page 6). If necessary, drain and refill with the proper oil.

2.Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE BAT- TERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery.

3.Clean and wipe the entire generator.

4.Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.

5.Turn OFF all electrical loads. Add fuel if neces- sary and then start the engine.

6.Allow the unit to run for several minutes to warm up.

7.Apply electrical loads to at least 50 percent of the unit’s rated wattage capacity.

8.When the engine is thoroughly warmed up, shut it down.

9.Your generator is now ready for service.

3.13 ADJUSTING VALVE CLEARANCE

After the first 50 hours of operation, you should adjust the valve clearance in the engine.

When adjusting valve clearance, the engine should be at room temperature and the piston should be at Top Dead Center (TDC) of its compression stroke (both valves closed). Correct clearance is 0.001-0.003 inch

(0.03-0.07mm). Adjust valve clearance as follows:

1.Loosen the rocker arm jam nut. Use an allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge (Figure 3.7).

Figure 3.7 — Adjusting Valve Clearance

Generac® Power Systems, Inc. 15

Image 17
Contents This manual should remain with the unit Air-cooled Recreational Vehicle GeneratorsModel QUIETPACT 40G GENERA OHVICONTENTS AUTHORIZED SERVICE DEALER LOCATIONOPERATION AND MAINTENANCE HOW TO OBTAIN SERVICESafety Rules Part II - Installation InstructionsAdjustments Exploded Views and Parts ListsDespite the safe design of this generator GENERAL HAZARDSParts of the generator are rotating and/or hot during operation. Exercise care near running generatorsEXPLOSION HAZARDS ELECTRICAL HAZARDSFIRE HAZARDS Model 004700-0 - QUIETPACT 40G 1.1 GENERATOR IDENTIFICATIONModel Number kW Rating1.5 SPECIFICATIONS 1.3 SAFETYDo not overload the generator. Some installa 1.2 GENERATOR APPLICABILITY1.5.5 GENERATOR Generac does not recommend using any1.5.2 FUEL CONSUMPTION 1.5.3 ENGINE OIL REQUIREMENTS2.4.1 INSTALLATION 2.1.2 START/STOP SWITCH2.1 GENERATOR CONTROL PANEL 2.2 OPTIONAL REMOTE START/STOP PANEL2.4.2 ENGINE LUBRICATION 2.5 STARTING THE GENERATOR2.4.3 FUEL SUPPLY 2.4.4 COOLING AND VENTILATING AIR2.9.2 HIGH TEMPERATURE SWITCH 2.9.1 LOW OIL PRESSURE SWITCHFigure 2.2 - Low Oil Pressure and High Temperature Switches 2.6 STOPPING THE GENERATOR2.9.3 FIELD BOOST 2.10 ADDITIONAL INFORMATION2.10.1 25-HOUR BREAK-IN PERIOD 2.9.4 OVERVOLTAGE PROTECTION3.1 CHECKING THE ENGINE OIL LEVEL Figure 3.1 - Oil Maintenance Features3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER 2.10.4 OPERATION IN HIGH GRASS OR BRUSH3.3.1 CLEANING THE FOAM PRECLEANER 3.3 MAINTAINING THE ENGINE AIR CLEANERFigure 3.2 - Engine Air Cleaner 3.3.2 CLEANING OR REPLACING THE PAPER FILTER3.7 CLEAN SPARK ARRESTOR 3.4 CLEAN AIR INTAKEFigure 3.3 - Cleaning Air Intake Figure 3.4 - Setting the Spark Plug Gap3.9 BATTERY MAINTENANCE 3.8 CLEANING THE GENERATORDo NOT use a forceful spray of water to clean Use tools with insulated handles Wear rubber gloves and boots3.13 ADJUSTING VALVE CLEARANCE 3.12 OUT OF SERVICE PROCEDURE3.12.1 REMOVAL FROM SERVICE 3.12.2 RETURN TO SERVICEFigure 3.8 - Tightening Jam Nut 3.14 RV GENERATOR SERVICE INTERVALSHOULD ATTEMPT INSTALLATION INSTALLATION INSTRUCTIONSPART ONLY QUALIFIED ELECTRICIANS OR CONTRACTORSNOTICE TO INSTALLER FIRE HAZARDS 1.1 PURPOSE AND SCOPE OF THE MANUAL 1.2 SAFETY1.4 EQUIPMENT DESCRIPTION 1.5 GENERATOR ENGINE OPERATING SPEEDVIEW FROM TOP Major Features2.1.1 GENERATOR LOCATION 2.1 LOCATION AND SUPPORT2.1.2 GENERATOR SUPPORT 2.1.3 SUSPENDED MOUNTING2.1.4 GENERATOR RESTRAINT 2.2 GENERATOR COMPARTMENTS2.2.2 COMPARTMENT CONSTRUCTION 2.2.1 COMPARTMENT SIZEFigure 2.6 - Types of Lock Seams 2.2.4 ACOUSTICS2.2.3 SOUND INSULATING MATERIALS Figure 2.8 - Compartment Floor Cutout Drawing 0D8716-C Figure 2.7 - Typical Noise Abatement 2.2.5 COMPARTMENT FLOOR CUTOUTSVIEW FROM TOP All measurements are in millimeters, 25.4 mm = 1”2.3 COOLING AND VENTILATING AIR 2.3.2 TESTING THE INSTALLATION2.4 GASOLINE FUEL SYSTEM 2.3.1 GENERATOR AIRFLOW2.4.1 FUEL TANK 2.5 EXHAUST SYSTEM2.4.2.2 Flexible Fuel Line 2.4.2 GENERATOR FUEL SUPPLY LINE 2.4.2.1 Rigid Fuel LinesFigure 2.12 - Spark Arrestor Installation 2.5.2 EXHAUST SYSTEM SAFETY2.6 ELECTRICAL CONNECTIONS 2.5.1 SPARK ARRESTOR2.6.1 ELECTRICAL JUNCTION BOX 2.6.2 WIRING2.6.3 GENERATOR AC CONNECTIONS 2.6.4 CONDUITFigure 2.14 - Transfer Switch Isolation Method 2.6.5 ISOLATING DIFFERENT POWER SOURCES2.6.6 POWER SUPPLY CORD 2.8 OPTIONAL ACCESSORIES 2.7 BATTERY INSTALLATION2.7.1 RECOMMENDED BATTERY 2.7.2 BATTERY CABLES3.4 TESTING UNDER LOAD 3.1 POST INSTALLATION TESTSDo not make any unnecessary adjustments 3.2 BEFORE INITIAL START-UP3.5 INSTALLATION CHECKLIST 34 Generac Power Systems, Inc Appendix 1 - NotesPROBLEM TROUBLESHOOTING GUIDECAUSE CORRECTIONBROWN Appendix 3 - Electrical Data36 Generac Power Systems, Inc Power DataQUIETPACT Appendix 3 - ElectricalAppendix 4 - Exploded Views and Parts Lists 38 Generac Power Systems, IncEnclosure - Drawing No. 0D8352-E TO CARBDESCRIPTION Appendix 4 - Exploded Views and Parts ListsPART NO. QTY 40 Generac Power Systems, Inc DESCRIPTION 25 24 42 Generac Power Systems, IncDESCRIPTION 44 Generac Power Systems, Inc BOOT CHOKE SOLENOID PLASTIC ASSEMBLY BRACKET GOVERNORASSEMBLY, GOVERNOR LEVER GASKET CARBURETOR/MANIFOLD46 Generac Power Systems, Inc SCREW, HHFC M8-1.25 X 35MM TAPERED CRANKSHAFT ASSEMBLYVALVE SPRING WEAR WASHER OIL PRESSURE RELIEF COVERYOUR WARRANTY RIGHTS AND OBLIGATIONS CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENTMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESEMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTY1 Utility 2 Lawn and Garden Equipment 3 Recreational Vehicle RV Generator 4 Industrial Mobile IM GeneratorWARRANTY SCHEDULE - COMMERCIAL APPLICATIONS GENERAC POWER SYSTEMS’ THREE-YEAR LIMITED WARRANTYWARRANTY SCHEDULE - CONSUMER/PERSONAL APPLICATIONS GENERAC POWER SYSTEMS, INC