◆2.9.3 FIELD BOOST

Section 2 – Operation

QUIETPACT 40G Recreational Vehicle Generator

2.9.3 FIELD BOOST

The Controller Circuit Board houses a field boost diode and resistor that are not part of the automatic choke circuit. These two components are part of a “field boost” circuit (Figure 2.3). During engine cranking only, a positive DC (battery) voltage is deliv- ered through the diode, resistor, brushes and slip rings, to the generator rotor. Application of this volt- age to the rotor “flashes the field” whenever it is start- ed. Flashing of the field each time the generator starts makes sure that a sufficiently strong magnetic field is available to produce “pickup” voltage in the stator windings.

Figure 2.3 – Field Boost Circuit

The voltage regulator also incorporates a “voltage surge protection circuit.” This circuit prevents trou- blesome surges in the generator AC output voltage. Voltage surge is a common cause of damage to elec- tronic equipment.

2.10 ADDITIONAL INFORMATION

2.10.1 25-HOUR BREAK-IN PERIOD

The first 25 hours of operation is the break-in period for the generator. Properly breaking in the generator is essential to minimize fuel consumption and pro- vide maximum engine performance. During this 25- hour break-in period, follow this procedure:

Run the unit at varying electrical loads to help seat the engine piston rings properly.

Check the engine oil level frequently. Add oil if needed. It is normal for the generator engine to consume more oil than is normal until the piston rings have properly seated.

For the 75-hour operation following the break-in period, avoid light electrical loads. Load the generator at 50 percent (or more) of its rated wattage capacity. Repeated light loads during these 75 hours can cause improper seating of engine pis- ton rings, resulting in blowby and high oil con- sumption.

After operating the unit for 25 hours, complete the tasks recommended under Section 2.10.2.

2.9.4 OVERVOLTAGE PROTECTION

A solid-state voltage regulator (Figure 2.4) controls the generator’s AC output voltage. This regulator sup- plies an excitation current to the rotor. By regulating the rotor’s excitation current, the strength of its mag- netic field is regulated and, in turn, the voltage deliv- ered to connected electrical loads is controlled. When the AC frequency is 60 Hertz, voltage is regulated at 120 volts (voltage-to-frequency ratio is 2-to-1).

Figure 2.4 – Solid State Voltage Regulator

2.10.2 25-HOUR CHECK-UP

After the 25-hour break-in period, contact a Generac Authorized Service Dealer for the following mainte- nance. The vehicle owner is responsible for any charges:

Change the engine crankcase oil and oil filter.

Check the oil level.

Inspect the cooling and ventilation openings.

Check the engine carburetor adjustments.

Check the engine ignition system.

Inspect the entire electrical system.

Inspect the engine exhaust system.

2.10.3 ATTENTION REQUIRED

AFTER SUBMERSION

If the recreational vehicle generator has been sub- merged in water, it MUST NOT be started and oper- ated. Following any submersion in water, have a Generac Authorized Service Dealer thoroughly clean and dry the generator.

10 Generac® Power Systems, Inc.

Image 12
Contents Air-cooled Recreational Vehicle Generators This manual should remain with the unitModel QUIETPACT 40G GENERA OHVIAUTHORIZED SERVICE DEALER LOCATION CONTENTSOPERATION AND MAINTENANCE HOW TO OBTAIN SERVICEPart II - Installation Instructions Safety RulesAdjustments Exploded Views and Parts ListsGENERAL HAZARDS Despite the safe design of this generatorParts of the generator are rotating and/or hot during operation. Exercise care near running generatorsELECTRICAL HAZARDS FIRE HAZARDSEXPLOSION HAZARDS 1.1 GENERATOR IDENTIFICATION Model 004700-0 - QUIETPACT 40GModel Number kW Rating1.3 SAFETY 1.5 SPECIFICATIONSDo not overload the generator. Some installa 1.2 GENERATOR APPLICABILITYGenerac does not recommend using any 1.5.5 GENERATOR1.5.2 FUEL CONSUMPTION 1.5.3 ENGINE OIL REQUIREMENTS2.1.2 START/STOP SWITCH 2.4.1 INSTALLATION2.1 GENERATOR CONTROL PANEL 2.2 OPTIONAL REMOTE START/STOP PANEL2.5 STARTING THE GENERATOR 2.4.2 ENGINE LUBRICATION2.4.3 FUEL SUPPLY 2.4.4 COOLING AND VENTILATING AIR2.9.1 LOW OIL PRESSURE SWITCH 2.9.2 HIGH TEMPERATURE SWITCHFigure 2.2 - Low Oil Pressure and High Temperature Switches 2.6 STOPPING THE GENERATOR2.10 ADDITIONAL INFORMATION 2.9.3 FIELD BOOST2.10.1 25-HOUR BREAK-IN PERIOD 2.9.4 OVERVOLTAGE PROTECTIONFigure 3.1 - Oil Maintenance Features 3.1 CHECKING THE ENGINE OIL LEVEL3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER 2.10.4 OPERATION IN HIGH GRASS OR BRUSH3.3 MAINTAINING THE ENGINE AIR CLEANER 3.3.1 CLEANING THE FOAM PRECLEANERFigure 3.2 - Engine Air Cleaner 3.3.2 CLEANING OR REPLACING THE PAPER FILTER3.4 CLEAN AIR INTAKE 3.7 CLEAN SPARK ARRESTORFigure 3.3 - Cleaning Air Intake Figure 3.4 - Setting the Spark Plug Gap3.8 CLEANING THE GENERATOR 3.9 BATTERY MAINTENANCEDo NOT use a forceful spray of water to clean Use tools with insulated handles Wear rubber gloves and boots3.12 OUT OF SERVICE PROCEDURE 3.13 ADJUSTING VALVE CLEARANCE3.12.1 REMOVAL FROM SERVICE 3.12.2 RETURN TO SERVICE3.14 RV GENERATOR SERVICE INTERVAL Figure 3.8 - Tightening Jam NutINSTALLATION INSTRUCTIONS SHOULD ATTEMPT INSTALLATIONPART ONLY QUALIFIED ELECTRICIANS OR CONTRACTORSNOTICE TO INSTALLER FIRE HAZARDS 1.2 SAFETY 1.1 PURPOSE AND SCOPE OF THE MANUAL1.4 EQUIPMENT DESCRIPTION 1.5 GENERATOR ENGINE OPERATING SPEEDMajor Features VIEW FROM TOP2.1 LOCATION AND SUPPORT 2.1.1 GENERATOR LOCATION2.1.2 GENERATOR SUPPORT 2.1.3 SUSPENDED MOUNTING2.2 GENERATOR COMPARTMENTS 2.1.4 GENERATOR RESTRAINT2.2.2 COMPARTMENT CONSTRUCTION 2.2.1 COMPARTMENT SIZE2.2.4 ACOUSTICS 2.2.3 SOUND INSULATING MATERIALSFigure 2.6 - Types of Lock Seams Figure 2.7 - Typical Noise Abatement 2.2.5 COMPARTMENT FLOOR CUTOUTS Figure 2.8 - Compartment Floor Cutout Drawing 0D8716-CVIEW FROM TOP All measurements are in millimeters, 25.4 mm = 1”2.3.2 TESTING THE INSTALLATION 2.3 COOLING AND VENTILATING AIR2.4 GASOLINE FUEL SYSTEM 2.3.1 GENERATOR AIRFLOW2.5 EXHAUST SYSTEM 2.4.1 FUEL TANK2.4.2.2 Flexible Fuel Line 2.4.2 GENERATOR FUEL SUPPLY LINE 2.4.2.1 Rigid Fuel Lines2.5.2 EXHAUST SYSTEM SAFETY Figure 2.12 - Spark Arrestor Installation2.6 ELECTRICAL CONNECTIONS 2.5.1 SPARK ARRESTOR2.6.2 WIRING 2.6.1 ELECTRICAL JUNCTION BOX2.6.3 GENERATOR AC CONNECTIONS 2.6.4 CONDUIT2.6.5 ISOLATING DIFFERENT POWER SOURCES 2.6.6 POWER SUPPLY CORDFigure 2.14 - Transfer Switch Isolation Method 2.7 BATTERY INSTALLATION 2.8 OPTIONAL ACCESSORIES2.7.1 RECOMMENDED BATTERY 2.7.2 BATTERY CABLES3.1 POST INSTALLATION TESTS 3.4 TESTING UNDER LOADDo not make any unnecessary adjustments 3.2 BEFORE INITIAL START-UP3.5 INSTALLATION CHECKLIST Appendix 1 - Notes 34 Generac Power Systems, IncTROUBLESHOOTING GUIDE PROBLEMCAUSE CORRECTIONAppendix 3 - Electrical Data 36 Generac Power Systems, IncBROWN Data PowerQUIETPACT Appendix 3 - Electrical38 Generac Power Systems, Inc Appendix 4 - Exploded Views and Parts ListsEnclosure - Drawing No. 0D8352-E TO CARBAppendix 4 - Exploded Views and Parts Lists PART NO. QTYDESCRIPTION 40 Generac Power Systems, Inc Appendix 4 - Exploded Views and Parts Lists 42 Generac Power Systems, Inc 25 24Appendix 4 - Exploded Views and Parts Lists 44 Generac Power Systems, Inc ASSEMBLY BRACKET GOVERNOR BOOT CHOKE SOLENOID PLASTICASSEMBLY, GOVERNOR LEVER GASKET CARBURETOR/MANIFOLD46 Generac Power Systems, Inc TAPERED CRANKSHAFT ASSEMBLY SCREW, HHFC M8-1.25 X 35MMVALVE SPRING WEAR WASHER OIL PRESSURE RELIEF COVERCALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONSMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESEMISSION CONTROL SYSTEM WARRANTY EMISSION RELATED PARTS INCLUDE THE FOLLOWING1 Utility 2 Lawn and Garden Equipment 3 Recreational Vehicle RV Generator 4 Industrial Mobile IM GeneratorGENERAC POWER SYSTEMS’ THREE-YEAR LIMITED WARRANTY WARRANTY SCHEDULE - COMMERCIAL APPLICATIONSWARRANTY SCHEDULE - CONSUMER/PERSONAL APPLICATIONS GENERAC POWER SYSTEMS, INC