Generac 004700-0 Post Installation Tests, Before Initial Start-Up, Testing Under Load, Danger

Page 34
◆ 2.8.1 REMOTE START/STOP PANEL

Section 3 – Post-Installation Start-up Adjustments

QUIETPACT 40G Recreational Vehicle Generator

2.8.1 REMOTE START/STOP PANEL

3.3 INITIAL START

A remote mounted Start/Stop panel (Figure 2.18) is available that allows the user to start and stop the generator engine conveniently from inside the vehicle. The remote panel includes a Start/Stop switch, hourmeter, generator run lamp and a wire harness. The hourmeter should be used in conjunction with the maintenance operations found in Part I of this manual.

Figure 2.18 – Optional Remote Panel

3.1POST INSTALLATION TESTS

The air-cooled generator set was factory tested and adjusted. You should not be required to adjust the unit any further except under special circumstances.

Do not make any unnecessary adjustments.

!Factory settings are correct for most applica- tions. When making adjustments, however, be careful to avoid overspeeding the engine.

3.2BEFORE INITIAL START-UP

Before starting, complete the following:

1.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick “FULL” mark (cross- hatched area) with the recommended oil. Do not fill above the FULL mark.

2.Check the fuel supply. Gas fuel lines must have been properly purged and leak tested in accor- dance with applicable fuel codes. All fuel shutoff valves in the fuel supply lines must be open.

3.3 INITIAL STARTFigure 2.18 – Optional Remote Panel DANGER

If a liquid propane (LP) gas fuel system has

!been installed, it must be properly tested for leaks before operating the system in compli- ance with ANSI A119.2/NFPA 501C. No leakage is permitted. You must be sure no gasoline fuel vapors enter the vehicle interior.

When you are absolutely certain that the unit has been properly installed and prepared for use, start the engine as follows:

1.Turn off all electrical loads. Do this by setting the generator’s main circuit breakers to their “OFF” (or open) position.

2.Refer to Part I, Section 2.5, “Starting the Generator” (Page 8), for cranking and starting instructions. The engine may require more cranking for initial starting since the fuel lines have to be primed (use of the primer switch will shorten this time).

3.Let the engine warm up for about five minutes to allow internal temperatures to stabilize.

4.Carefully inspect the engine/generator for fuel, oil and exhaust system leaks. Before proceeding to the next step, correct any leakage immediately.

5.When all tests and adjustments at no-load are completed, apply electrical loads and check for proper operation under load. See Section 3.4. Run the unit at least 30 minutes with loads applied.

6.Turn off all electrical loads by setting the genera- tor’s main circuit breakers to their “OFF” (or open) position.

7.Let the unit run at no-load for a few minutes to stabilize internal engine/-generator temperatures. Then, shut down the engine.

NOTE:

The generator set was thoroughly tested and adjusted at the factory before shipping. No addi- tional adjustment should be necessary. Only qual- ified service technicians who have been trained should perform adjustments outlined in this man- ual.

3.4TESTING UNDER LOAD

Apply electrical loads equal to about 75 to 100 per- cent of the unit's rated wattage/amperage capacity.

Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling air- flow is available. You must not allow the unit to over- heat during prolonged operation.

NOTE:

The generator engine is equipped with a high tem- perature switch. The switch has normally closed (N.C.) contacts. When the engine temperature is too high, switch contacts close, and the engine shuts down automatically.

GENERAC RECOMMENDS THAT YOU TEST THE GENERATOR FOR ADEQUATE COOLING.

32 Generac® Power Systems, Inc.

Image 34
Contents Model QUIETPACT 40G Air-cooled Recreational Vehicle GeneratorsThis manual should remain with the unit GENERA OHVIOPERATION AND MAINTENANCE AUTHORIZED SERVICE DEALER LOCATIONCONTENTS HOW TO OBTAIN SERVICEAdjustments Part II - Installation InstructionsSafety Rules Exploded Views and Parts ListsParts of the generator are rotating and/or hot GENERAL HAZARDSDespite the safe design of this generator during operation. Exercise care near running generatorsFIRE HAZARDS ELECTRICAL HAZARDSEXPLOSION HAZARDS Model Number 1.1 GENERATOR IDENTIFICATIONModel 004700-0 - QUIETPACT 40G kW RatingDo not overload the generator. Some installa 1.3 SAFETY1.5 SPECIFICATIONS 1.2 GENERATOR APPLICABILITY1.5.2 FUEL CONSUMPTION Generac does not recommend using any1.5.5 GENERATOR 1.5.3 ENGINE OIL REQUIREMENTS2.1 GENERATOR CONTROL PANEL 2.1.2 START/STOP SWITCH2.4.1 INSTALLATION 2.2 OPTIONAL REMOTE START/STOP PANEL2.4.3 FUEL SUPPLY 2.5 STARTING THE GENERATOR2.4.2 ENGINE LUBRICATION 2.4.4 COOLING AND VENTILATING AIRFigure 2.2 - Low Oil Pressure and High Temperature Switches 2.9.1 LOW OIL PRESSURE SWITCH2.9.2 HIGH TEMPERATURE SWITCH 2.6 STOPPING THE GENERATOR2.10.1 25-HOUR BREAK-IN PERIOD 2.10 ADDITIONAL INFORMATION2.9.3 FIELD BOOST 2.9.4 OVERVOLTAGE PROTECTION3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER Figure 3.1 - Oil Maintenance Features3.1 CHECKING THE ENGINE OIL LEVEL 2.10.4 OPERATION IN HIGH GRASS OR BRUSHFigure 3.2 - Engine Air Cleaner 3.3 MAINTAINING THE ENGINE AIR CLEANER3.3.1 CLEANING THE FOAM PRECLEANER 3.3.2 CLEANING OR REPLACING THE PAPER FILTERFigure 3.3 - Cleaning Air Intake 3.4 CLEAN AIR INTAKE3.7 CLEAN SPARK ARRESTOR Figure 3.4 - Setting the Spark Plug GapDo NOT use a forceful spray of water to clean 3.8 CLEANING THE GENERATOR3.9 BATTERY MAINTENANCE Use tools with insulated handles Wear rubber gloves and boots3.12.1 REMOVAL FROM SERVICE 3.12 OUT OF SERVICE PROCEDURE3.13 ADJUSTING VALVE CLEARANCE 3.12.2 RETURN TO SERVICE3.14 RV GENERATOR SERVICE INTERVAL Figure 3.8 - Tightening Jam NutPART INSTALLATION INSTRUCTIONSSHOULD ATTEMPT INSTALLATION ONLY QUALIFIED ELECTRICIANS OR CONTRACTORSNOTICE TO INSTALLER FIRE HAZARDS 1.4 EQUIPMENT DESCRIPTION 1.2 SAFETY1.1 PURPOSE AND SCOPE OF THE MANUAL 1.5 GENERATOR ENGINE OPERATING SPEEDMajor Features VIEW FROM TOP2.1.2 GENERATOR SUPPORT 2.1 LOCATION AND SUPPORT2.1.1 GENERATOR LOCATION 2.1.3 SUSPENDED MOUNTING2.2.2 COMPARTMENT CONSTRUCTION 2.2 GENERATOR COMPARTMENTS2.1.4 GENERATOR RESTRAINT 2.2.1 COMPARTMENT SIZE2.2.3 SOUND INSULATING MATERIALS 2.2.4 ACOUSTICSFigure 2.6 - Types of Lock Seams VIEW FROM TOP Figure 2.7 - Typical Noise Abatement 2.2.5 COMPARTMENT FLOOR CUTOUTSFigure 2.8 - Compartment Floor Cutout Drawing 0D8716-C All measurements are in millimeters, 25.4 mm = 1”2.4 GASOLINE FUEL SYSTEM 2.3.2 TESTING THE INSTALLATION2.3 COOLING AND VENTILATING AIR 2.3.1 GENERATOR AIRFLOW2.4.2.2 Flexible Fuel Line 2.5 EXHAUST SYSTEM2.4.1 FUEL TANK 2.4.2 GENERATOR FUEL SUPPLY LINE 2.4.2.1 Rigid Fuel Lines2.6 ELECTRICAL CONNECTIONS 2.5.2 EXHAUST SYSTEM SAFETYFigure 2.12 - Spark Arrestor Installation 2.5.1 SPARK ARRESTOR2.6.3 GENERATOR AC CONNECTIONS 2.6.2 WIRING2.6.1 ELECTRICAL JUNCTION BOX 2.6.4 CONDUIT2.6.6 POWER SUPPLY CORD 2.6.5 ISOLATING DIFFERENT POWER SOURCESFigure 2.14 - Transfer Switch Isolation Method 2.7.1 RECOMMENDED BATTERY 2.7 BATTERY INSTALLATION2.8 OPTIONAL ACCESSORIES 2.7.2 BATTERY CABLESDo not make any unnecessary adjustments 3.1 POST INSTALLATION TESTS3.4 TESTING UNDER LOAD 3.2 BEFORE INITIAL START-UP3.5 INSTALLATION CHECKLIST Appendix 1 - Notes 34 Generac Power Systems, IncCAUSE TROUBLESHOOTING GUIDEPROBLEM CORRECTION36 Generac Power Systems, Inc Appendix 3 - Electrical DataBROWN QUIETPACT DataPower Appendix 3 - ElectricalEnclosure - Drawing No. 0D8352-E 38 Generac Power Systems, IncAppendix 4 - Exploded Views and Parts Lists TO CARBPART NO. QTY Appendix 4 - Exploded Views and Parts ListsDESCRIPTION 40 Generac Power Systems, Inc Appendix 4 - Exploded Views and Parts Lists 42 Generac Power Systems, Inc 25 24Appendix 4 - Exploded Views and Parts Lists 44 Generac Power Systems, Inc ASSEMBLY, GOVERNOR LEVER ASSEMBLY BRACKET GOVERNORBOOT CHOKE SOLENOID PLASTIC GASKET CARBURETOR/MANIFOLD46 Generac Power Systems, Inc VALVE SPRING WEAR WASHER TAPERED CRANKSHAFT ASSEMBLYSCREW, HHFC M8-1.25 X 35MM OIL PRESSURE RELIEF COVERMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENTYOUR WARRANTY RIGHTS AND OBLIGATIONS PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES1 Utility 2 Lawn and Garden Equipment EMISSION CONTROL SYSTEM WARRANTYEMISSION RELATED PARTS INCLUDE THE FOLLOWING 3 Recreational Vehicle RV Generator 4 Industrial Mobile IM GeneratorWARRANTY SCHEDULE - CONSUMER/PERSONAL APPLICATIONS GENERAC POWER SYSTEMS’ THREE-YEAR LIMITED WARRANTYWARRANTY SCHEDULE - COMMERCIAL APPLICATIONS GENERAC POWER SYSTEMS, INC