Generac 004700-0 Battery Installation, Optional Accessories, Recommended Battery, Battery Cables

Page 33
◆2.6.7 GROUND FAULT CIRCUIT INTERRUPTERS

Section 2 – Installation

QUIETPACT 40G Recreational Vehicle Generator

2.6.7 GROUND FAULT CIRCUIT INTERRUPTERS

The National Electrical Code (NFPA 70, 551-7) requires that you install ground fault circuit inter- rupters (GFCIs) on all external and some internal electrical receptacles. Contact your manufacturer or dealer for recommendations.

2.7BATTERY INSTALLATION

2.7.1 RECOMMENDED BATTERY

Install a battery that meets the following requirements:

The battery must be a 12-volt, automotive type storage battery.

For prevailing ambient temperatures above 32° F (0° C), use a battery rated 70 amp-hours and capa- ble of delivering 400 cold-cranking amperes.

For prevailing ambient temperatures below 32° F (0° C), use a battery rated 95 amp-hours and capa- ble of delivering 400 cold-cranking amperes.

NOTE:

If the battery is to be used to power other vehicle accessories, as well as start the generator, you may need a battery with a larger capacity.

2.7.2 BATTERY CABLES

Using battery cables that are too long or too small in diameter may cause a drop in voltage, which causes starting problems. For the best cold weather starting, the voltage drop between battery terminals and the generator connection point should not exceed 0.12 volts per 100 amperes of cranking current.

PRIMEPACT generators are rated at about 100 DC amperes of cranking current.

Select battery cables based on (a) cable length and (b) prevailing ambient temperatures. Generally, the longer the cable and the colder the weather, the larg- er the cable size must be, as shown in the chart.

Figure 2.16 – Connecting Battery Cables

POS

FUEL

NEG

2.7.4 BATTERY COMPARTMENT

Install the generator battery in its own, vented com- partment. Place the battery compartment away from any source of heat, sparks or flame.

Provide ventilation openings in the battery compart- ment. The minimum size of openings should be 2 square inches at the top of the compartment. Mount the battery on a strong, rigid supporting structure, where leaks and spills of battery fluid will not cause damage.

2.8OPTIONAL ACCESSORIES

A plug-in receptacle (Figure 2.17) is provided on the generator set. Use this receptacle to connect an optional remote-mounted start/stop panel to the gen- erator. Installation of such a panel will permit you to start and stop the generator engine from any conve- nient location inside the vehicle.

Figure 2.17 – Remote Panel Plug-in Receptacle

6

14A

14A

5

15

15

4

18

18

3

14

14

2

17

17

1

0

0

2.7.3 BATTERY CABLE CONNECTIONS

1.Connect the battery cable from the battery post or terminal indicated by a POSITIVE, POS or (+) to the lug on the starter contactor (Figure 2.16).

NOTE:

Check to be sure the battery cable boot for the starter cable has been installed.

2.Connect the battery cable from the battery post indicated by a NEGATIVE, NEG or (-) to the frame ground connection (Figure 2.16).

3.Connect cables so the connectors are clean and tight.

12.00"

WIRE

WIRE

LENGTH (mm)

FUNCTION

No.

COLOR

 

 

 

 

 

GROUND

0

WHITE

12.0 (305)

14

RED

12.0 (305)

ENGINE RUN SIGNAL

15

ORANGE

12.0 (305)

12 VDC

17

YELLOW

12.0 (305)

START

18

BROWN

12.0 (305)

STOP

14A

BLUE

12.0 (305)

PRIME

P/N: 0D9099-B

Generac® Power Systems, Inc. 31

Image 33
Contents This manual should remain with the unit Air-cooled Recreational Vehicle GeneratorsModel QUIETPACT 40G GENERA OHVICONTENTS AUTHORIZED SERVICE DEALER LOCATIONOPERATION AND MAINTENANCE HOW TO OBTAIN SERVICESafety Rules Part II - Installation InstructionsAdjustments Exploded Views and Parts ListsDespite the safe design of this generator GENERAL HAZARDSParts of the generator are rotating and/or hot during operation. Exercise care near running generatorsELECTRICAL HAZARDS FIRE HAZARDSEXPLOSION HAZARDS Model 004700-0 - QUIETPACT 40G 1.1 GENERATOR IDENTIFICATIONModel Number kW Rating1.5 SPECIFICATIONS 1.3 SAFETYDo not overload the generator. Some installa 1.2 GENERATOR APPLICABILITY1.5.5 GENERATOR Generac does not recommend using any1.5.2 FUEL CONSUMPTION 1.5.3 ENGINE OIL REQUIREMENTS2.4.1 INSTALLATION 2.1.2 START/STOP SWITCH2.1 GENERATOR CONTROL PANEL 2.2 OPTIONAL REMOTE START/STOP PANEL2.4.2 ENGINE LUBRICATION 2.5 STARTING THE GENERATOR2.4.3 FUEL SUPPLY 2.4.4 COOLING AND VENTILATING AIR2.9.2 HIGH TEMPERATURE SWITCH 2.9.1 LOW OIL PRESSURE SWITCHFigure 2.2 - Low Oil Pressure and High Temperature Switches 2.6 STOPPING THE GENERATOR2.9.3 FIELD BOOST 2.10 ADDITIONAL INFORMATION2.10.1 25-HOUR BREAK-IN PERIOD 2.9.4 OVERVOLTAGE PROTECTION3.1 CHECKING THE ENGINE OIL LEVEL Figure 3.1 - Oil Maintenance Features3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER 2.10.4 OPERATION IN HIGH GRASS OR BRUSH3.3.1 CLEANING THE FOAM PRECLEANER 3.3 MAINTAINING THE ENGINE AIR CLEANERFigure 3.2 - Engine Air Cleaner 3.3.2 CLEANING OR REPLACING THE PAPER FILTER3.7 CLEAN SPARK ARRESTOR 3.4 CLEAN AIR INTAKEFigure 3.3 - Cleaning Air Intake Figure 3.4 - Setting the Spark Plug Gap3.9 BATTERY MAINTENANCE 3.8 CLEANING THE GENERATORDo NOT use a forceful spray of water to clean Use tools with insulated handles Wear rubber gloves and boots3.13 ADJUSTING VALVE CLEARANCE 3.12 OUT OF SERVICE PROCEDURE3.12.1 REMOVAL FROM SERVICE 3.12.2 RETURN TO SERVICEFigure 3.8 - Tightening Jam Nut 3.14 RV GENERATOR SERVICE INTERVALSHOULD ATTEMPT INSTALLATION INSTALLATION INSTRUCTIONSPART ONLY QUALIFIED ELECTRICIANS OR CONTRACTORSNOTICE TO INSTALLER FIRE HAZARDS 1.1 PURPOSE AND SCOPE OF THE MANUAL 1.2 SAFETY1.4 EQUIPMENT DESCRIPTION 1.5 GENERATOR ENGINE OPERATING SPEEDVIEW FROM TOP Major Features2.1.1 GENERATOR LOCATION 2.1 LOCATION AND SUPPORT2.1.2 GENERATOR SUPPORT 2.1.3 SUSPENDED MOUNTING2.1.4 GENERATOR RESTRAINT 2.2 GENERATOR COMPARTMENTS2.2.2 COMPARTMENT CONSTRUCTION 2.2.1 COMPARTMENT SIZE2.2.4 ACOUSTICS 2.2.3 SOUND INSULATING MATERIALSFigure 2.6 - Types of Lock Seams Figure 2.8 - Compartment Floor Cutout Drawing 0D8716-C Figure 2.7 - Typical Noise Abatement 2.2.5 COMPARTMENT FLOOR CUTOUTSVIEW FROM TOP All measurements are in millimeters, 25.4 mm = 1”2.3 COOLING AND VENTILATING AIR 2.3.2 TESTING THE INSTALLATION2.4 GASOLINE FUEL SYSTEM 2.3.1 GENERATOR AIRFLOW2.4.1 FUEL TANK 2.5 EXHAUST SYSTEM2.4.2.2 Flexible Fuel Line 2.4.2 GENERATOR FUEL SUPPLY LINE 2.4.2.1 Rigid Fuel LinesFigure 2.12 - Spark Arrestor Installation 2.5.2 EXHAUST SYSTEM SAFETY2.6 ELECTRICAL CONNECTIONS 2.5.1 SPARK ARRESTOR2.6.1 ELECTRICAL JUNCTION BOX 2.6.2 WIRING2.6.3 GENERATOR AC CONNECTIONS 2.6.4 CONDUIT2.6.5 ISOLATING DIFFERENT POWER SOURCES 2.6.6 POWER SUPPLY CORDFigure 2.14 - Transfer Switch Isolation Method 2.8 OPTIONAL ACCESSORIES 2.7 BATTERY INSTALLATION2.7.1 RECOMMENDED BATTERY 2.7.2 BATTERY CABLES3.4 TESTING UNDER LOAD 3.1 POST INSTALLATION TESTSDo not make any unnecessary adjustments 3.2 BEFORE INITIAL START-UP3.5 INSTALLATION CHECKLIST 34 Generac Power Systems, Inc Appendix 1 - NotesPROBLEM TROUBLESHOOTING GUIDECAUSE CORRECTIONAppendix 3 - Electrical Data 36 Generac Power Systems, IncBROWN Power DataQUIETPACT Appendix 3 - ElectricalAppendix 4 - Exploded Views and Parts Lists 38 Generac Power Systems, IncEnclosure - Drawing No. 0D8352-E TO CARBAppendix 4 - Exploded Views and Parts Lists PART NO. QTYDESCRIPTION 40 Generac Power Systems, Inc DESCRIPTION 25 24 42 Generac Power Systems, IncDESCRIPTION 44 Generac Power Systems, Inc BOOT CHOKE SOLENOID PLASTIC ASSEMBLY BRACKET GOVERNORASSEMBLY, GOVERNOR LEVER GASKET CARBURETOR/MANIFOLD46 Generac Power Systems, Inc SCREW, HHFC M8-1.25 X 35MM TAPERED CRANKSHAFT ASSEMBLYVALVE SPRING WEAR WASHER OIL PRESSURE RELIEF COVERYOUR WARRANTY RIGHTS AND OBLIGATIONS CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENTMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESEMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTY1 Utility 2 Lawn and Garden Equipment 3 Recreational Vehicle RV Generator 4 Industrial Mobile IM GeneratorWARRANTY SCHEDULE - COMMERCIAL APPLICATIONS GENERAC POWER SYSTEMS’ THREE-YEAR LIMITED WARRANTYWARRANTY SCHEDULE - CONSUMER/PERSONAL APPLICATIONS GENERAC POWER SYSTEMS, INC