6.OPERATIONAL LIMITS OF THE GENERATOR

6-1 AC OUTPUT

Electric appliances normally have rating levels showing the rated voltage, frequency, power consumption (input power), and other things. The power consumption specified on such a label is required to drive the appliance. However, when an appliance is connected to the generator, the power factor and starting current should also be taken into account.

6-l-l NET RESISTANCE LOAD

Incandescent lamps, electric heaters etc. can be run on the generator having a capacity equivalent to the total of the respective appliances. Each of these appliances normally has a power factor of 1.0.

Example: The generator having a rated voltage output of 1000 W can provide enough power to operate up to ten 100 W lamps.

6-l-2 ELECTRIC APPLIANCES WITH A POWER FACTOR OF LESS THAN 1.0

Fluorescent lamps and mercury lamps normally have a low power factor, and accordingly, the generator is required to generate approximately 1.2 to 2 times the power consumed by each loaded appliance.

Example: With the generator having a rated voltage output of 1000 W, six to ten 80 W mercury lamps can be operated.

6-l-3 MOTOR LOAD

Generally, motors require a large starting current every time they are started or begin rotating. The motor starting load supplied from the generator becomes the largest when starting a normal operation mode. The rates of power supply, which the generator is required to produce for motor loads, are categorized into two cases, depending on the types of the motor used and load condition at the time of starting.

(1)Motors (mainly rectifier motors) used for electric drills and similar devices:

Normally, the motors used for electric drills and similar appliances require the generator to produce approximately 1.2 to 3 times the power consumed at the time of starting.

Example: To drive a 300 W electric drill, a generator with a maximum output of about 400 W to 900 W or more is necessary.

(2)Motors (mainly induction motors) used for pumps and compressors:

As pumps and compressors have loads even when they are started, the generator is required to produce 3 to 5 times the power consumed during normal running.

Example: To drive a 200 W submersible pump, a generator with a maximum output of 600 W to 1000 W or more is necessary.

6-l-4 IN THE CASE WHERE POWER CONSUMPTION IS NOT DISPLAYED ON THE RATING PANEL

Sometimes, the rating panel of an electric appliance does not carry its power consumption, but only shows the mechanical equivalent to the power consumption. In this case, it is necessary to

-14 -

Image 18
Contents Rozh -J &ii Foreword Contents Assembly Specifications ItemsPower Factor AC OutputOutput Max Rated 800 W Frequency 50 Hz Voltage 110 Output MaxFrequency 60 Hz Voltage 12ov DC Output Under no load is approximately from 18V up toFeatures Component Identification CHOKE-RUN-STOPFunction of Each Component L-5 Crankshaft 4CONNECTING ROD and PistonMain Bearing Cover CamshaftAIR Cleaner Carburetor‘CC Description of Main OperationsVoltage Regulation Under Load Fis Output Waveform Current @ Curr&t @ Operational Limits of the Generator Load Electric Battery Capacity Wire Length Measuring Procedures II ’ Mj 1 mIPage To Measure Insulation Resist Control Panel Functional Check of Each Component L aOne section, replace with Assy 83 AVR Windings, or peripheral temperature Cleaning of Slip Ring ResistanceValue El 10.7J-z At rated rpm Exciting coilDisassembly and Assembly Precautions Tools DriverPrecautions Nection Description By unscrewing three SequenceI Part to remove j IFront cover DescriptionI2 Remove the front cover M5 x 8 screwsBe careful not to Description PrecautionsPart to Sequencej remOve Damage the fuel PipePart to Sequence, remove LpannerSpanner That 1wiring Remove $Ez End cover Description Precautions@ Driver Remove the connector Assembling, be Part toRemOve ’Rear ‘bracket Description See Fig. g-3-10SequenceI Rpearfito~~ Description Pull away the stator cover’ plastic hammer Siw‘ Necessary Precautions Part to / Sequencej remove ’ JFront Ibracket Description13 m/m box Spanner RemOve DescriptionPrecautions Necessary Tools Blower i 1 1housing I10 m/m box spannerNecessary Precautions . tools @ Driver Brace nuts 112m/m box ’spanner 10 m/m box jspanner Precautions Bolt has only to be loosenedOne M6 x 12 bolt ’Governor Remove the governor lever j LeverIgnition coil from 26 i &cocci*nRemove the starting pully Crank case by takingFront and hook ’ the minus driver Pull out the intake valve and the exhaust valveNotch Spanner 1spring retainer’s RetainerISequenceI Part to Camshaft DescriptionCrankcase Tappets to distin Guish them from one Be careful not to open the joint too wide, or it will break Remove the crankshaft Be careful not toAssembly Procedure WTolerances of new installed parts Connecting rod is joined to the piston with the piston pin Piston and Piston RingConnecting ROD Tappets and CamshaftIntake Valve and Exhaust Valve WV&e h valve guide clearance =53Tappet Adjustment Breather Plate and Tappet Cover Cylinder HeadIgnition Plug Ignition COIL, Exciting COIL, Flywheel and Starting PulleyGovernor Lever Speed Control Nut Muffler and Muffler CoverHead Cover and Blower Housing 1’7 Recoil StartorFront Bracket Rear Bracket and Stator Brash Holder Bracket Cover Page Fuel Pipe Connection Front Cover and Element CoverConnection of Coupler and Plug Secure the side cover with four M 5 x 8 screws Carburetor Schematic Diagram of the Fuel System By-Pass Choke Disassembly and Assembly of Carburetor 184 Safety Precautions Troubleshooting Starting failur Cock is closed Pzlzq L1Ill IISymptoms AIgnition coil ’ \ r?J Hanging posi- tion is not normal Abration 7Symptoms 0Governor system III Seat Case Case there Abnormal Operation Is too much Pour Lubri Been changed Replace Periodically 1Symptoms Voltemeter Stator sub-coil Symptoms LNo DC voltage is output Voltag,eistoo high QParts LSymptoms Symptoms Voltage Is abnormally low Parts For Adjustment Criteria TableUel con Limit Items Adjustment Criteira Description Tools Wiring Diagram LT-TwMaintenance Checks and Maintenance for Every 200 Hours Every Month Page Page Issue EMD-GS0095