| REMEDY/ | |
CONDITION | POSSIBLE CAUSE | REFERENCE | |
|
| SECTION | |
3.3 ALTERNATING CURRENT GENERATOR (CONTINUED) |
| ||
|
|
| |
| Generator overloaded | Check | |
| Clogged ventilating screens | Clean | |
| High temperature surrounding generator | Section 4.4.5 | |
Overheating | Insufficient air circulation | Section 4.5.1 | |
| Unbalanced load | Balance | |
| Dry bearing | Section 4.5.1/ | |
|
| 4.5.3 | |
|
|
| |
| Bad bearing | Section 4.5.1/ | |
|
| 4.5.3 | |
| Rotor scrubbing on stator | Section 4.5.1/ | |
Mechanical Noise | Loose laminations | 4.5.3 | |
| Section 4.5.4/ | ||
|
| Replace | |
| Loose or misaligned coupling | Section 4.5.4 | |
|
|
| |
| Static charge | Check ground to | |
Generator frame produces shock |
| frame | |
when touched | Grounded armature of field coil | Section 4.5.4/ | |
|
| Replace | |
|
|
| |
3.4 AUTO |
|
| |
|
|
| |
| Wait 30 seconds for intake heater to be activated | Wait | |
| Coolant level below the low coolant sensor | 1.10.j. | |
| Relay defective | Check/Replace | |
| Ignition switch defective | Check/Replace | |
|
| Switch | |
When the Ignition switch is placed in | 3 amp Fuse is bad | Check and | |
the RUN position, nothing |
| Replace Fuse | |
no lights illuminate | Loose connector on module | Tighten | |
|
| connector | |
| Auto restart module is bad | Check for 12 | |
|
| volts at Pin 4/ | |
|
| Replace module | |
| Miswired connectors | Check/Correct | |
|
| wiring | |
|
|
| |
Alarm sounds, but engine does not | No voltage at Pin 2 of the connector | Trace/Correct | |
Check Starter Solenoid | See 3.1.1 | ||
crank | |||
Auto restart module is bad | Replace module | ||
| |||
|
|
| |
Engine starts, but the starter does | Speed Sensor wiring loose | Check/Correct | |
Speed Sensor is bad | Replace | ||
not disengage | |||
Auto restart module is bad | Replace module | ||
| |||
|
|
|
|