Table 1-3 Auto Restart Sequencing (Continued)
| Intake |
| Engine | Engine |
| |
Series | Heater | Fuel |
| |||
Crank | Rest |
| ||||
Attempt | Energized | Solenoid | Engine Status | |||
Duration | Duration | |||||
Number | in | Engaged |
| |||
(Seconds) | (Seconds) |
| ||||
| Seconds |
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
| If the engine starts: | |
|
|
|
|
| a. Run sequence begins. | |
|
|
|
|
| If the engine fails to start: | |
4 | 30 | X | Up To 15 | 25 | a. Intake heater will | |
b. Fuel solenoid will | ||||||
|
|
|
|
| c. Crank output will | |
|
|
|
|
| d. Overcrank LED will flash four times. Wait | |
|
|
|
|
| two seconds and repeat. | |
|
|
|
|
| e. Unit will rest five hours and proceed to | |
|
|
|
|
| the next series. | |
|
|
|
|
|
| |
|
|
|
|
| If the engine starts: | |
|
|
|
|
| a. Run sequence begins. | |
|
|
|
|
| If the engine fails to start: | |
5 | 30 | X | Up To 15 | 25 | a. Intake heater will | |
b. Fuel solenoid will | ||||||
|
|
|
|
| c. Crank output will | |
|
|
|
|
| d. Overcrank LED will flash five times. Wait | |
|
|
|
|
| two seconds and repeat. | |
|
|
|
|
| e. Unit will rest five hours and proceed to | |
|
|
|
|
| the next series. | |
|
|
|
|
|
| |
|
|
|
|
| If the engine starts: | |
|
|
|
|
| a. Run sequence begins. | |
|
|
|
|
| If the engine fails to start: | |
6 | 30 | X | Up To 15 | 25 | a. Intake heater will | |
b. Fuel solenoid will | ||||||
|
|
|
|
| c. Crank output will | |
|
|
|
|
| d. Overcrank LED will illuminate solid and | |
|
|
|
|
| lock out future crank attempts. | |
|
|
|
|
| e. To reset, turn unit power switch OFF and | |
|
|
|
|
| back ON. | |
|
|
|
|
|
|
|