Carrier 69UG15 Rotor Damage, Terminal Strip Cleaning, Winding Insulation Testing, Wire Ohm, Pair

Page 36

b. Generator Windings (Drying)

WARNING

Do not direct water or steam into the generator openings. Do not allow any soap and water solutions to enter the alternator.

WARNING

High voltage (dielectric) testing must not be performed to the machine without first observing NEMA rules. The insulation of this generator winding may be safely checked by using a megger. A high megger reading indicates good insulation.

Generators that have been in transit, recently steam cleaned or in storage for long periods may be subjected to extreme temperature and moisture changes. This can cause excessive condensation, and the generator windings should be thoroughly dried out before bringing the generator up to full nameplate voltage. If this precaution is not taken, serious damage to the generator can result. The following steps should be taken to effectively dry the generator windings:

1.Dry windings by placing generator in drying oven or hot room, or dry with warm air blower directed through windings.

2.If the generator has been operated and is being placed into storage for any period of time, a P.D. George #11127 type air-dry fungus resistant varnish should be applied.

The finest insulation job can be very quickly broken down by carelessly applying high voltage to windings in a moisture saturated condition. Failure to follow these guidelines could easily cause a breakdown, making it necessary to return the generator to the factory for repair.

c. Rotor Damage

If a rotor becomes defective, it should be returned to the factory with full nameplate data. To repair a rotor, the special tooling and technique of the factory are necessary and essential. Should a failure occur, Carrier Transicold should be notified immediately and steps will be taken to return the generator for service.

d. Terminal Strip Cleaning

Open terminal box. Remove dust and debris, and clean terminal strip with wire brush. Reapply protective coating.

4.5.2Generator Repair/Test Procedures a. Restoring Residual Magnetism

The direct current (DC) necessary to magnetize the alternator field is obtained from the exciter. Initially, upon starting the generator, current flow and voltage are induced into the exciter armature by the magnetic lines of force set up by the residual magnetism of the exciter field poles.

Residual magnetism of the exciter field poles may be lost or weakened by a strong neutralizing magnetic field from any source, or if the generator is not operated for a long period of time.

Should the generator fail to build up voltage after being disassembled for any reason, a momentary short-circuit of any two generator leads (L1, L2 and L3) while generator is running should be sufficient to correct this condition.

CAUTION

When trying to restore residual magnetism, be sure to wear safety glasses and non-conductive gloves. Use an insulated 12 gauge (or higher) jumper wire. Cut off all but a few strands from both ends of the jumper wire to help prevent fusing.

As an alternate method, apply either an alternating current or a direct current voltage of approximately 20 volts to any two generator leads (L1, L2 and L3) while generator is running. Do not make a positive connection, but rather touch the leads together until the generator voltage begins to rise, then remove. Insert a 30 ampere fuse into the circuit to prevent any damage in case the build-up voltage is not removed quickly enough. Reflash field if generator output voltage does not build up.

b. Winding Insulation Testing

Continuity test results for the stator winding tests are provided in the following table:

 

 

 

 

 

 

Wire

Ohm*

Wire

Ohm*

Wire

Ohm*

Pair

Pair

Pair

 

 

 

T10-T1

I

T1-T8

I

T4-T5

I

T10-T2

I

T1-T9

I

T4-T6

I

T10-T3

I

T2-T3

I

T4-T7

I

T10-T4

I

T2-T4

I

T4-T8

I

T10-T5

I

T2-T5

0

T4-T9

I

T10-T6

I

T2-T6

I

T5-T6

I

T10-T7

0

T2-T7

I

T5-T7

I

T10-T8

0

T2-T8

I

T5-T8

I

T10-T9

0

T2-T9

I

T5-T9

I

T1-T2

I

T3-T4

I

T6-T7

I

T1-T3

I

T3-T5

I

T6-T8

I

T1-T4

0

T3-T6

0

T6-T9

I

T1-T5

I

T3-T7

I

T7-T8

0

T1-T6

I

T3-T8

I

T7-T9

0

T1-T7

I

T3-T9

I

T8-T9

0

* 0 = no resistance (closed circuit) & I = infinite resistance (open circuit)

4--7

T-343

Image 36
Contents Operation and Service Model 69UG15 Table of Contents Table of Contents List of Illustrations List of TablesTable Number Safety Summary Specific Warning and Caution Statements Configuration Identification Section DescriptionIntroduction PID Volt Generator Set343 Engine Engine Screw ThreadsBattery Charger Operating Controls and InstrumentsIntroduction Control Panel and Related Components a. Gauges and SendersManual Switches Safety DevicesMeters Customer Specific Control Panel and Box Auto Restart Preset Values Indicator Description Auto Restart SequencingIntake Engine Series FuelAuto Restart Sequencing Intake Engine Series Unit Specifications Intake HeaterGenerator Nominal Tank Sizes Fill Capacity Draw CapacityOutdoor Temperature Centigrade Engine DataSAE Winter SummerGenerator SET Installation OperationTypical Generator Set Mounting Quick Mount Generator SET RemovalStarting and Stopping Instructions Cold Engine Preheat TimesControl Circuit Operation Section Troubleshooting RemedyCondition Possible Cause Reference Section Diesel Engine Engine Will Not StartCondition Possible Cause Reference Section Engine Will Not Shut OffStarter Motor Malfunction Malfunction In The Engine Starting CircuitMiscellaneous Engine Troubleshooting Battery Charger Solid StateAlternating Current Generator Auto RE-START Option Remedy Section Service and Preventive Maintenance Preventative Maintenance ScheduleBattery Service Interval Units Description of Procedure UnitsEvery 1000Interval Units HoursServicing Low Oil Pressure Switch Servicing Heater Switch 1. Remove control box coverAttempt to Adjust Engine Speed Preventative Maintenance and Operating Precautions Engine Crankcase BreatherServicing the Alternating Current Generator CoolingTerminal Strip Cleaning Winding Insulation TestingWire Ohm Rotor DamageDiode Testing Bearing ReplacementTerminals see Figure Truss Frame Unidrive Bolt IsolatorEngine Isolator/Shockmount Replacement Generator Install Mount With Large Flare AT TOP FrameBolt Shockmount Unidrive Torque Requirements Engine & Generator SHOCKMOUNTS/ISOLATORS TOP ViewEngine Mount Right Side View Section Schematics Schematic Diagram LegendSchematic Diagram Schematic Diagram 460 Volt Alternating Current Generator Schematic Diagram 230 Volt Alternating Current Generator Based On Drawing 62-11413-00 Rev a Schematic Diagram Schematic Diagram 460 Volt Alternating Current Generator Index Index