Operation

Event Management

This menu item permits changing how the Liebert NXL handles Alarms, Faults and Status informa- tion. Each event can be configured for the following:

Latch (yes/no)—Event stays active in the event window, even if the fault condition has been cleared, until user acknowledges it by pressing the “Reset” button.

Audible (yes/no)—Will set Audible alarm when event occurs

Event log (yes/no)—Will display event in Event log when it occurs

NOTE

You must press “Save” for changes to take effect.

See Table 7 for a list of alarms, fault and status messages.

Figure 14 Typical Event Management Parameters

2.2.3Status Reports Menu

This menu accesses the events records.

Event Log—Up to 1024 time/date stamped events are captured in the log. The oldest record will be overwritten with a new record once the buffer reaches 1024 events.

System Status

Total Operating Hours—Total number hours the UPS has been operational

Battery Operating Time—A running total of the battery discharge time for all events since the log was last cleared

2.2.4Startup Menu

This menu is used to start the UPS and individual devices.

Manual—This will begin the UPS startup. See 2.4 - Manual Procedures for details.

Devices

Close Trap—This will start the Input filter, if installed

Close MBD/BCB—If MBD is motor operated, the Close command will Enable and energize the motor to close. If MBD is not motorized, the Close command will Enable the breaker UVR. The MBD/BCB must be closed manually. If no MBD is selected, do not display this setting.

14

Image 20
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions Modes of Operation Normal ModeGeneral Description Bypass Mode Battery ModeMaintenance Bypass OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Startup Menu Event ManagementStatus Reports Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Reset MeteringHelp SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Load Transfer Procedures Transfer ProcedureRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass Shutdown Procedures UPS Shutdown ProcedureSystem Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersBattery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery retorque values Matching Battery Cabinets-OptionalBattery voltage, nominal and float Torque specifications, unless otherwise labeled Detecting TroubleRack-Mounted Batteries Torque RequirementsCorrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Battery Operation Environmental specificationsParameter Specification Environmental ConditionsElectrical specifications Battery & DC ParametersLiebert NXL Model Size 250 Input ParametersPhysical Parameters & Standards, in mm Liebert NXL Model SizeSystem Parameter Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ne t ItiTi n That