Emerson 250-400kVA Attempt to manually close the disconnect by

Page 60

 

 

 

UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

An active Input Current Limit alarm means the

Press “SILENCE” to silence the audible alarm.

 

 

detected input current (RMS) exceeds the limit

 

 

setpoint (default is 125%). This may be normal

Observe the meters on the One-Line Display for

 

 

depending on various operating conditions, such

input voltage level, battery charge/discharge

Input Current Limit

as input voltage level, output load level, and

current, and output load percentage kW. Investigate

 

 

whether the batteries have recently discharged.

any abnormal readings.

 

 

This alarm is self-clearing. When the condition is

If the reason for the alarm cannot be determined,

 

 

no longer present, the alarm and any control

contact your factory-authorized service provider.

 

 

activity tied to the alarm reverts to normal.

 

Input Disconnect

The rectifier disconnect device indicates that it is

 

(Q1) Open

 

in the open position.

 

Input Disconnect

The externally mounted input isolator indicates

 

(Q11) Open

 

that it is in the open position.

 

 

 

The Input Filter Disconnect is locked open.

 

 

 

The Input Filter Disconnect Cycle counter has

Press “SILENCE” to silence the audible alarm.

 

 

exceeded the setpoint. The Input Filter

 

 

Disconnect opens automatically as determined by

Attempt to manually close the disconnect by

 

 

the disconnect settings, or because of an unusual

pressing “Startup,” “Device Control,” “Close Trap.”

Input Filter Cycle

condition.

If the condition which caused the filter disconnect to

An example of a setting would be to automatically

lock open is still present, it re-opens.

 

 

 

 

open the filter disconnect under light load

If the disconnect cannot be manually closed or the

 

 

conditions to improve the input power factor. An

alarm cannot be cleared, contact your factory-

 

 

example of an unusual condition would be

authorized service provider.

 

 

unbalanced currents on the input, possibly

 

 

 

because of a suspect component in the filter itself.

 

 

 

This summary alarm means there is a problem

Press “SILENCE” to silence the audible alarm.

 

 

with input power. It is not acceptable to the

 

 

Rectifier.

Examine the One-Line Display. The Rectifier input

Input Not Avail

If the unit is running normally when this event

line feeding the Input Breaker should be green. If

occurs, the UPS goes to battery.

not, investigate source power to the UPS.

 

 

 

 

This alarm is self-clearing. When the condition is

If input power is good, and this alarm is active,

 

 

no longer present, the alarm and any control

contact your factory-authorized service provider.

 

 

activity tied to the alarm reverts to normal.

 

 

 

This is a summary event caused by an

 

 

 

interruption in communication between the

 

 

 

controls and a device on the Controller Area

 

 

 

Network (CAN).

Press “SILENCE” to silence the audible alarm.

 

 

The Internal Communication Error event indicates

Internal Comm

Press “RESET” to clear the alarm.

a loss of communications between the controls

If the alarm cannot be reset, or if the alarm condition

Error

 

and an external device.

 

returns, contact your factory-authorized service

 

 

The Internal Communication Error is displayed

 

 

provider.

 

 

when the controls detect a loss of communication

 

 

to a device on the Controller Area Network (CAN).

 

 

 

An infrequent occurrence that resets immediately

 

 

 

is probably not serious.

 

 

 

An overload condition is active on A phase.

Press “SILENCE” to silence the audible alarm.

 

 

A phase load condition exceeds 105%.

 

 

Check the Module Output Meter and note the A

 

 

A countdown timer is displayed on the One-Line

 

 

phase load percentage.

 

 

Display in response to this alarm, and indicates

 

 

If possible, reduce A phase loading.

 

 

the time remaining until a transfer to bypass

 

 

If the steady state load remains above 105%, allow

Inv Overload Ph A

occurs. The length of time remaining until transfer

the UPS to transfer to bypass and contact your

 

 

is directly proportional to the severity of the

factory-authorized service provider.

 

 

overload.

 

 

If the displayed load percentage is less than 100%

 

 

This alarm is self-clearing. When the condition is

 

 

and the alarm is still active, contact your factory-

 

 

no longer present, the alarm and any control

 

 

authorized service provider.

 

 

activity tied to the alarm reverts to normal.

 

 

 

 

 

 

 

54

Image 60
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions Normal Mode General DescriptionModes of Operation Bypass Mode Battery ModeMaintenance Bypass OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Event Management Status Reports MenuStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Reset MeteringHelp SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Load Transfer Procedures Transfer ProcedureRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass Shutdown Procedures UPS Shutdown ProcedureSystem Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersBattery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery retorque values Torque specifications, unless otherwise labeled Detecting TroubleRack-Mounted Batteries Torque RequirementsReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Battery Operation Environmental specificationsParameter Specification Environmental ConditionsElectrical specifications Battery & DC ParametersLiebert NXL Model Size 250 Input ParametersLiebert NXL Model Size System ParameterPhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ne t ItiTi n That