Emerson 250-400kVA manual Module Output Meter. If the load is less than

Page 61

 

 

 

UPS Alarm and Status Messages

 

 

 

 

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

An overload condition is active on B phase.

Press “SILENCE” to silence the audible alarm.

 

 

B phase load condition exceeds 105%.

 

 

Check the Module Output Meter and note the B

 

 

A countdown timer is displayed on the One-Line

 

 

phase load percentage.

 

 

Display in response to this alarm, and indicates

 

 

If possible, reduce B phase loading.

 

 

the time remaining until a transfer to bypass

 

 

If the steady state load remains above 105%, allow

Inv Overload Ph B

occurs. The length of time remaining until transfer

 

 

is directly proportional to the severity of the

the UPS to transfer to bypass and contact your

 

 

factory-authorized service provider.

 

 

overload.

 

 

If the displayed load percentage is less than 100%

 

 

This alarm is self-clearing. When the condition is

 

 

and the alarm is still active, contact your factory-

 

 

no longer present, the alarm and any control

 

 

authorized service provider.

 

 

activity tied to the alarm reverts to normal.

 

 

 

 

 

 

 

 

 

An overload condition is active on C phase.

Press “SILENCE” to silence the audible alarm.

 

 

C phase load condition exceeds 105%.

 

 

Check the Module Output Meter and note the C

 

 

A countdown timer is displayed on the One-Line

 

 

phase load percentage.

 

 

Display in response to this alarm, and indicates

 

 

If possible, reduce C phase loading.

 

 

the time remaining until a transfer to bypass

 

 

If the steady state load remains above 105%, allow

Inv Overload Ph C

occurs. The length of time remaining until transfer

 

 

is inversely proportional to the severity of the

the UPS to transfer to bypass and contact your

 

 

factory-authorized service provider.

 

 

overload.

 

 

If the displayed load percentage is less than 100%

 

 

This alarm is self-clearing. When the condition is

 

 

and the alarm is still active, contact your factory-

 

 

no longer present, the alarm and any control

 

 

authorized service provider.

 

 

activity tied to the alarm reverts to normal.

 

 

 

 

 

 

 

 

 

This message is displayed in response to an

 

 

 

overload on one or more output phases.

Press “SILENCE” to silence the audible alarm.

 

 

When an overload occurs, the controls display a

 

 

countdown timer that displays the time remaining

Observe the load percentages for each phase on

 

 

until a transfer to bypass occurs. The length of the

the Module Output Meter. If the load is less than

 

 

timer is inversely proportional to the amplitude of

100%, attempt to transfer back to Inverter by

Inv Ovld Exceeded

the overload. When the timer reaches zero, the

pressing “Transfer,” “UPS.”

 

 

UPS transfers to bypass and populates the Active

If the transfer is successful, investigate the reason

 

 

Event Window with this alarm.

for the overload and take appropriate action.

 

 

This fault is non-latching. When the underlying

If the transfer is unsuccessful, contact your factory-

 

 

condition is no longer present, this fault and any

authorized service provider.

 

 

control activity tied directly to this fault reverts to

 

 

 

normal.

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Check the One-Line Display to determine the state

 

 

 

of the UPS. If both the Rectifier and Inverter are

 

 

 

shut off, press “RESET” to attempt to clear any

 

 

 

latched alarms or faults.

 

 

This summary event indicates a potentially

Attempt a restart by pressing “Startup,” “Manual

 

 

serious problem in the Inverter.

Start,” and follow the prompts to place the UPS

 

 

The controls react to an Inverter fault in different

back in service.

Inverter Fault

ways depending on the root event that caused the

If the startup fails, contact your factory-authorized

 

 

fault. If bypass is available, the controls transfer to

service provider.

 

 

static bypass.

If the Rectifier and Inverter appear to be running,

 

 

A restart may or may not be possible

press “RESET” to attempt to clear any latched

 

 

 

alarms or faults, then attempt a transfer by pressing

 

 

 

“Transfer,” “UPS.” If the transfer is successful,

 

 

 

contact your factory-authorized service provider.

 

 

 

If the transfer is unsuccessful, contact your factory-

 

 

 

authorized service provider.

 

 

The controls have detected voltage on the

 

 

 

Inverter (Line side) side of the Inverter Static

Press “SILENCE” to silence the audible alarm.

 

 

Switch.

 

 

Turn off Control Power to clear the event. Wait 5

 

 

This indicates that an SCR is shorted.

ISS SCR Shorted

minutes before re-applying Control Power.

With the Output SCRs turned off, there should be

 

 

no voltage present inside the UPS.

If the fault fails to clear, contact your factory-

 

 

authorized service representative.

 

 

This is a non-recoverable fault, and inhibits

 

 

 

 

 

normal start up of the UPS.

 

 

 

 

 

55

Image 61
Contents Liebert NXL Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Battery Mode Bypass ModeMaintenance Bypass OptionsIntroduction Main component locations FeaturesMimic display Monitor/mimic display example Utility fail Monitor/mimic display example Normal power flowMonitor/mimic display example Load on bypass, UPS On Menu tree Touchscreen Navigation Main Display ScreenRating Parameters Configurations Menu RatingSystem Settings parameters User SettingsAdjustable setpoints parameters Adjustable SetpointsCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown menu Shutdown MenuTransfer Menu Transfer/retransfer commandsTime remaining display Battery Management MenuDisplay summary see Figure Metering ResetHelp SilenceLoad on bypass, UPS available OK to TransferInput power fail, load on battery Input Power Failure-Load on BatteryEmergency Module Off Off BatteryRemote Emergency Power Off Manual ProceduresStartup Procedure Startup commands Transfer Procedure Load Transfer ProceduresRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass UPS Shutdown Procedure Shutdown ProceduresSystem Shutdown Procedure Automatic OperationsCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Automatic Transfers to Bypass, UPS System FaultsSafety Precautions Routine Maintenance Liebert ServicesAir Filters Record LogUPS component service life Battery MaintenanceLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Detecting Trouble Torque specifications, unless otherwise labeledRack-Mounted Batteries Torque RequirementsUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Environmental specifications Battery OperationParameter Specification Environmental ConditionsBattery & DC Parameters Electrical specificationsLiebert NXL Model Size 250 Input ParametersSystem Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Event Message Event Definition Recommended Action Liebert NXL alarm and status messagesObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Iti Ne tTi n That