Emerson 250-400kVA manual Electrical specifications, Liebert NXL Model Size 250, Input Parameters

Page 46

 

 

 

 

 

SPECIFICATIONS

Table 6

Electrical specifications

 

 

 

 

 

 

 

 

 

 

 

Liebert NXL Model Size

250

 

300

 

400

 

 

 

 

 

 

Input Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage to Rectifier, VAC

 

480V 3-phase, 3-wire

 

 

 

 

 

 

 

Input Voltage to Bypass, VAC

 

480V 3-phase, 3- or 4-wire

 

 

 

 

 

 

 

 

Permissible Input Voltage Range, VAC

 

 

70% to 110%

 

 

 

 

 

 

 

 

Input Frequency, Hz

 

60

 

 

 

 

 

 

 

 

 

Permissible Input Frequency Range, Hz

 

 

55 to 65

 

 

 

 

 

Input THDi at nominal voltage at full load, %

<10% with 6-pulse and passive filter

 

 

 

 

 

 

 

Input Power Factor at nominal voltage

 

>= 0.92

 

 

 

 

 

 

Flexi Power Walk-In, sec

3 to 30 (selectable) in 1 sec. Increments

 

 

 

 

 

 

Battery & DC Parameters

 

 

 

 

 

 

 

 

 

 

 

Battery Type

VRLA (Valve Regulated Lead Acid) or FLA

 

 

(Flooded Lead Acid)

 

 

 

 

 

 

Nominal Battery Bus, VDC

 

 

480V

 

 

 

 

 

 

 

 

Battery Float Voltage, VDC

 

 

540V

 

 

 

 

 

 

 

End-Cell Voltage, VDC

 

384 (for VRLA / FLA)

 

 

 

 

 

 

 

DC Ripple Voltage in float & Const V Ch.mode, %

 

<1 (RMS value) < 3.4% Vpp

 

 

 

 

 

 

 

Temperature Compensated Battery Charging

 

Standard (with temperature probe)

 

 

 

 

 

 

 

Output Parameters

 

 

 

 

 

 

 

 

 

 

 

Inverter Type

IGBT-based Sine-Sine PWM Controlled

 

 

 

 

 

 

 

Output Power, kW

225

 

270

 

360

 

 

 

 

 

 

 

 

Output Voltage

 

 

480VAC, 3-ph, 4-w

 

 

 

 

 

 

 

Output Voltage Regulation, %

 

< 1% (3-phase RMS average)

 

 

 

 

 

 

 

Output Voltage Regulation (100% Unb. Load)

 

< 2% (3-phase RMS average)

 

 

 

 

 

 

 

 

Output Frequency, Hz

 

60

 

 

 

 

 

 

 

 

 

Output Frequency Regulation, %

 

± 0.1

 

 

 

 

 

 

 

 

 

Output THDu at Nominal Voltage (Linear Load), %

 

<2%

 

 

 

 

 

 

 

 

Output THDu at nominal voltage Including a 100kVA Non Linear

 

 

2.5% (max)

 

 

Load per EN 62040-3, %

 

 

 

 

 

 

 

 

 

 

Capacity to Handle Step Load, %

 

 

0-100 or 100-0

 

 

 

 

 

Transient Recovery (Linear Loads), %, msec

within 5% peak to peak in one-line cycle

 

 

 

 

 

 

Capacity to Handle Leading PF Load

 

Up to 0.8 with the following ratings:

 

 

 

 

 

 

 

a - 0.5 lag to 0.9 lag

 

a - Subject to maximum kVA rating

 

 

 

 

 

 

 

b - 0.9 lag to Nom

 

b - Subject to maximum kW rating

 

 

 

 

 

 

 

c - at 0.95 Lead

 

c - Subject to maximum. kW rating

 

 

 

 

 

d - at 0.9 Lead

d - Subject to 12,5% kW derate or same rating

 

 

and 10°C temp. derate

 

 

 

 

 

 

e - at 0.8 Lead

e - Subject to 25% kW derate or 12,5% kW derate and

 

 

10°C Temp. Derate

 

 

 

 

 

 

Voltage Displacement, ° el

120° ±1° el (with 100% unbalanced load)

 

 

 

 

 

 

 

Compliance to FCC Class-A

 

 

Standard

 

 

 

 

 

 

 

 

 

110% for 60 minutes

 

 

 

 

 

 

 

Overload Conditions, % FL

 

125% for 10 minutes

 

 

 

 

 

 

 

 

 

 

 

150% for 1 minute

 

 

 

 

 

 

 

 

40

Image 46
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Maintenance Bypass Bypass ModeBattery Mode OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Help ResetMetering SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Re-Transfer Procedure Load Transfer ProceduresTransfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass System Shutdown Procedure Shutdown ProceduresUPS Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersLimited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Rack-Mounted Batteries Torque specifications, unless otherwise labeledDetecting Trouble Torque RequirementsUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Parameter Specification Battery OperationEnvironmental specifications Environmental ConditionsLiebert NXL Model Size 250 Electrical specificationsBattery & DC Parameters Input ParametersSystem Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ti n Ne tIti That