Emerson 250-400kVA manual Manual Procedures, Remote Emergency Power Off

Page 29

Operation

2.3.6Remote Emergency Power Off

The Remote Emergency Power Off (REPO) mode will transfer the critical load to the bypass line and remove power from all UPS module components except the controls, bypass circuit breaker and the static switch.

The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS system. It usually is installed in the same room as the critical load equipment. This mode can also be initiated by an automatic contact closure in the same external circuit as the manually operated switch.

When the Remote Emergency Power Off switch is operated, all UPS circuit breakers are opened, including the bypass circuit breaker. All power through the UPS is removed from the load. Typically, the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS controls. Refer to 2.5 - Shutdown Procedures.

Figure 29 Remote emergency power off

Bypass

BFB

Input

CB1

DC Bus

CB2

Module Output

Battery System

MBD

2.4Manual Procedures

The Liebert NXL UPS is designed to function while unattended by an operator. Many important func- tions are handled automatically by the system control logic, as explained in 2.6 - Automatic Opera- tions. Other procedures must be performed manually.

Manual procedures available to the operator include Startup, Load Transfers and Shutdowns. These procedures are performed by using the touchscreen and some manually operated circuit breakers and switches.

The touchscreen lists all steps required for each manual procedure. This section lists step-by-step con- trols to operate and conditions to observe in the following manual procedures:

Startup—including initial startup, recovering from input power failure, recovering from battery shutdown and recovering from shutdowns for emergencies or maintenance.

Load Transfers—including transfers from UPS to bypass and retransfers from bypass to the UPS system.

Maintenance Bypass Load Transfers—including transferring from internal bypass to mainte- nance bypass and transferring from maintenance bypass to internal bypass.

Shutdowns—including module shutdowns for maintenance and emergency shutdowns.

NOTE

The following procedure assumes that the UPS installation inspection and initial startup have been performed by Liebert Services. A Liebert-authorized representative must perform the initial system startup to ensure proper system operation.

23

Image 29
Contents Liebert NXL Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Specifications Figures Page Important Safety Instructions Modes of Operation Normal ModeGeneral Description Battery Mode Bypass ModeMaintenance Bypass OptionsIntroduction Main component locations FeaturesMimic display Monitor/mimic display example Utility fail Monitor/mimic display example Normal power flowMonitor/mimic display example Load on bypass, UPS On Menu tree Touchscreen Navigation Main Display ScreenRating Parameters Configurations Menu RatingSystem Settings parameters User SettingsAdjustable setpoints parameters Adjustable SetpointsCell Count Adjustment Startup Menu Event ManagementStatus Reports Menu Shutdown menu Shutdown MenuTransfer Menu Transfer/retransfer commandsTime remaining display Battery Management MenuDisplay summary see Figure Metering ResetHelp SilenceLoad on bypass, UPS available OK to TransferInput power fail, load on battery Input Power Failure-Load on BatteryEmergency Module Off Off BatteryRemote Emergency Power Off Manual ProceduresStartup Procedure Startup commands Transfer Procedure Load Transfer ProceduresRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass UPS Shutdown Procedure Shutdown ProceduresSystem Shutdown Procedure Automatic OperationsCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Automatic Transfers to Bypass, UPS System FaultsSafety Precautions Routine Maintenance Liebert ServicesAir Filters Record LogUPS component service life Battery MaintenanceLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery retorque values Matching Battery Cabinets-OptionalBattery voltage, nominal and float Detecting Trouble Torque specifications, unless otherwise labeledRack-Mounted Batteries Torque RequirementsCorrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Environmental specifications Battery OperationParameter Specification Environmental ConditionsBattery & DC Parameters Electrical specificationsLiebert NXL Model Size 250 Input ParametersPhysical Parameters & Standards, in mm Liebert NXL Model SizeSystem Parameter Specifications Event Message Event Definition Recommended Action Liebert NXL alarm and status messagesObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Iti Ne tTi n That