|
|
| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Observe the | |
|
|
| orange, black, or gray, the battery discharging | |
|
|
| condition is normal. | |
|
|
| If the input line on the | |
|
|
| check the Active Event Window for potential fault | |
|
|
| conditions that could explain why the UPS is on | |
|
|
| battery. An example of this could be “Rectifier | |
|
|
| Fault.” | |
|
| The UPS is on battery. | Monitor the UPS during the battery discharge. The | |
|
| display shows the discharge curve of the battery. | ||
|
| The most common reason for going to battery is a | ||
|
| loss of rectifier input power (power outage). | When the Battery Voltage Line touches the End of | |
Batt Discharging | Discharge Line, the UPS shuts down. | |||
This alarm is | ||||
|
| Check the bypass line on the | ||
|
| no longer present, the alarm and any control | ||
|
| the line feeding the Static Bypass Switch (BPSS) is | ||
|
| activity tied to the alarm reverts to normal. | ||
|
| green, the unit can be transferred to bypass by | ||
|
|
| ||
|
|
| pressing “Transfer,” “Bypass” to transfer the load to | |
|
|
| the bypass source. Note that transferring to bypass | |
|
|
| could expose the load to an outage if the bypass | |
|
|
| source fails. | |
|
|
| If the battery is discharging because of a fault such | |
|
|
| as “Rectifier Fault” in the Active Event Window | |
|
|
| rather than an actual power outage, transfer to | |
|
|
| bypass if available, and contact your factory- | |
|
|
| authorized service provider. | |
|
| The batteries are being equalized. |
| |
|
| Battery equalization stops automatically based on | In normal operation, no user response is required. | |
|
| the Equalize Time Setting. | Equalize charge can be terminated at any time by | |
Batt Equalizing | This status message is | |||
pressing “Battery Management,” “Manual Battery | ||||
|
| condition is no longer present, the message and | ||
|
| Equalize,” “Stop.” | ||
|
| any control activity tied to the status event reverts | ||
|
| to normal. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| Detected battery ground current exceeds the trip | Are any Battery Circuit Breakers tripped? | |
|
| Perform a visual inspection of the batteries in the | ||
|
| setting. | ||
|
| tripped string(s). Look for signs of leaking battery | ||
|
| A possible symptom that could cause this alarm is | ||
|
| acid or excessively corroded battery terminals. | ||
|
| a leaking battery. | If there are no visible signs of defective batteries, | |
|
| This alarm has a higher detection setpoint than | ||
|
| press “RESET” to try and clear the alarm. | ||
Batt Ground Fault | “Battery Ground Fault Current Warning,” and if | |||
Close any open breakers one at a time, pressing | ||||
|
| present, means that the Battery Ground Fault | ||
|
| “RESET” after each one to see which string is | ||
|
| Current is excessive. | ||
|
| causing the alarm. The string reporting the fault, | ||
|
| This alarm could cause Battery Breakers to trip if | ||
|
| when online, will not allow the alarm to reset. | ||
|
| the “Battery Ground Fault Trip Enable” setting is | ||
|
| Once the location is identified, or if the battery string | ||
|
| enabled. | ||
|
| tests are inconclusive, contact your factory- | ||
|
|
| ||
|
|
| authorized service provider. | |
|
|
|
|
44